3 Operation

Operation manual

7

EKRTETS
Room thermostat
4P677096-1 – 2021.10

INFORMATION

The  open  window  function  will  NOT  work  in  the  following
situations:

▪ EKRTETS  is  installed  as  floor  sensor  (parameter  20  –

"rEGU" is set to "FLR").

▪ The  room  thermostat  is  in  holiday  mode  or  in  OFF

mode.

▪ The 

temperature 

drops 

below 

the 

anti-freeze

temperature set in the user menu.

▪ The  unit  operation  mode  is  set  to  cooling  (reversible

mode).

INFORMATION

If  enabled,  the  open  window  function  will  still  respect  the
anti-freeze  temperature  (parameter  06  –  "HG"  in  the  user
menu).  This  means  that  the  room  thermostat  will  keep
heating to maintain the anti-freeze temperature (by default
10°C).

To enable or disable the open window function

1

Press and hold 

 for 5 seconds.

Result: 

The  first  parameter  (

rEGU

)  of  the  installer  menu

appears.

2

Use 

 and 

 to select parameter 33 (

Win

).

3

Use 

 and 

 to change the parameter value to 

yes

 (enabled,

default value) or 

no

 (disabled).

4

Press 

 to confirm.

5

Use 

 and 

 to select to parameter 37 (

End

).

6

Press 

 to exit the installer menu.

Result: 

The open window function is enabled/disabled.

3.3.3

Dew prevention

For  reversible  systems,  the  room  thermostat  offers  2  ways  of
managing humidity in order to prevent condensation while cooling.

Humidity percentage threshold

You  can  set  a  threshold  value  for  the  humidity  percentage.
Whenever the room thermostat detects that the humidity percentage
exceeds  the  set  threshold,  cooling  demand  is  ceased  to  prevent
condensation.  Whenever  this  is  the  case, 

blinks  on  the  room

thermostat display. To change the threshold value (default 55%), set
the value for parameter 34 ("

rH

") to the desired value in the installer

menu.

Dew prevention function with floor temperature sensor

If the optional external temperature sensor EKRTETS is installed as
floor  temperature  sensor,  parameter  35  ("

dEv

")  can  be  set  to  "yes"

in the installer menu to enable the dew prevention function.

When  enabled,  this  function  will  continuously  compare  the
temperature  measured  by  the  floor  temperature  sensor  against  the
dew  point.  The  dew  point  is  calculated  based  on  the  room
temperature and humidity. When the floor temperature drops below
or  comes  too  close  to  the  dew  point,  cooling  demand  is  stopped
temporarily to prevent any condensation on the floor. While the dew
prevention function is active,

blinks on the room thermostat display.

3.4

User menu

The user menu allows you to set basic room thermostat parameters.

3.4.1

To enter the user menu

1

Press and hold 

 for 5 seconds.

Result: 

The first parameter (rF INI) of the user menu appears on the

display.

To exit the user menu, use the navigation buttons to select the "End"

parameter and press 

.

3.4.2

To modify parameters in the user menu

Prerequisite: 

You are in the user menu.

1

Use 

 and 

 to cycle between parameters.

2

Press 

 to select the parameter.

3

Modify the desired parameter using 

 and 

.

4

After making changes, press 

 to save.

3.4.3

User parameters

INFORMATION

Some  parameters  relating  to  functions  described  in  this
manual are NOT available in the user menu and can ONLY
be found in the installer menu.

Parameter

Description

Possible values

(a)

#

Name

00

rF INI

Radio configuration mode

01

dEG

Temperature unit used
on display

°C

▪ °F

02

__:__

Time format used on
display

24H 

(24 

hour

display)

▪ 12H (12 hour display)

03

dst

Daylight summer time
change

yes

 (enabled)

▪ no (disabled)

04

AirC

Internal temperature
sensor calibration.

See 

"4 Temperature

sensor
calibration"

 [

4

 8] for

more information.

05

AMbC

External temperature
sensor calibration

06

HG

Anti-freeze temperature
in holiday mode

10°C

▪ Range: 0.5°C~10°C

07

ITCS

Intelligent Temperature
Control System

(b)

yes

 (enabled)

▪ no (disabled)

08

Clr ALL

Clear user settings: press and hold 

 for 5

seconds to reset all setpoints and user
parameters to their default settings.

09

CHAn

10

VErS

Software version

11

End

Exit the user menu. Press 

 to exit.

(a)

The default values are listed in 

bold

.

(b)

If enabled, this function will activate the installation in advance
(up to a maximum of 2 hours) to ensure that the desired setpoint
is reached at the appropriate time according to the set program.
With every program change, the room thermostat measures the
time taken by the installation to reach the setpoint to compensate
for any temperature differences that may be present at different
times. This allows you to make program changes without needing
to adjust the temperature in advance, because the room
thermostat does this automatically.

Содержание EKRTRB

Страница 1: ...Operation manual Room thermostat English Operation manual Room thermostat EKRTRB EKRTETS...

Страница 2: ...ite or via your installer The original documentation is written in English All other languages are translations 2 Room thermostat Overview The EKRTRB room thermostat is a programmable wireless digital...

Страница 3: ...et the other values as desired 4 After setting the last value the room thermostat will ask you to confirm and save your changes Press LED blinking green to save the date and time settings Result The r...

Страница 4: ...timer mode automatically 2 Select the duration with and and press to confirm 3 Adjust the desired setpoint with and 4 Press to start the function Result The room thermostat displays the remaining dur...

Страница 5: ...0 minutes Symbol Setpoint Meaning First step of the day the room thermostat follows the comfort mode temperature setpoint during this step Leaving step optional adds an additional step to the current...

Страница 6: ...ing heating of your reversible unit To make use of reversible mode it must be enabled in the installer settings first For more information see To enable reversible mode 46 To change the unit operation...

Страница 7: ...floor temperature drops below or comes too close to the dew point cooling demand is stopped temporarily to prevent any condensation on the floor While the dew prevention function is active blinks on...

Страница 8: ...he batteries When blinks on the room thermostat display the batteries of the room thermostat need to be replaced Once the battery indicator starts blinking the room thermostat will still be able to fu...

Страница 9: ...aller floor sensor problem is blinking and Err is shown on the room thermostat display Contact your installer humidity measurement problem If after checking all above items it is impossible to fix the...

Страница 10: ......

Страница 11: ......

Страница 12: ...4P677096 1 2021 10 Copyright 2021 Daikin 4P677096 1 0000000X Verantwortung f r Energie und Umwelt...

Отзывы: