EKMV EKMV3C09B7

2-way valve kit/3-way valve kit for fan coil units

4PW65144-1B – 10.2011

Installation manual

4

Electrical connections

For the FWF

1

Install the KRP1B101 box and the EKRP1C11 PCB according to
the installation manual provided with the KRP1B101 kit.

For wiring of the EKRP1C11 PCB: see below.

For the FWC

1

Install the KRP1H98 box and the EKRP1C11 PCB according to
the installation manual provided with the KRP1H98 kit.

For wiring of the EKRP1C11 PCB: see below.

2

Wiring of the EKRP1C11

Power supply

Communication wire

Do not drill any holes in the casing of the unit to install the
option.

Only use the accessories provided by Daikin to install the
option.

The EKRP1C11 can only be used to connect the valves.
The functions mentioned in the installation manual of the
EKRP1C11 can not be used.

1

Communication to fan coil PCB

2

Power supply wire (to fan coil unit)

3

Fuses 5 A - 250 V

4

YC-Y1: connection of first valve

5

X1-Y4: wire to enable the use of the second valve (supplied 
with valve kit)

6

X2-YC: connection of second valve

Do not bundle low and high voltage wires together. Bundle
all wires with the included clamps in order to avoid contact
with fan coil PCB’s or sharp edges.

X1 X2 X3 X4

CN1

Y4

Y3

Y2

Y1

YC

CN2

4

1

5

2

6

3

F1U F2U

CN2

X1 X2 X3 X4

CN1

1 2

L N

3

F1U F2U

FWC

FWF

PCB

supplied with EKRP1C11 kit

CN2

X1 X2 X3 X4

X21A

X27A

X10A

X35A

X11A

CN1

F1U F2U

X33A for 
FWF and 
FWC

supplied with EKRP1C11 kit