background image

2 General safety precautions

Installation manual

4

EKMBDXB7V1

Modbus Interface DIII

4P635058-1 – 2020.10

2.2.3

Electrical

DANGER: RISK OF ELECTROCUTION

▪ Turn OFF all power supply before removing the switch

box  cover,  connecting  electrical  wiring  or  touching
electrical parts.

▪ Disconnect the power supply for more than 10 minutes,

and measure the voltage at the terminals of main circuit
capacitors  or  electrical  components  before  servicing.
The  voltage  MUST  be  less  than  50  V  DC  before  you
can touch electrical components. For the location of the
terminals, see the wiring diagram.

▪ Do NOT touch electrical components with wet hands.

▪ Do  NOT  leave  the  unit  unattended  when  the  service

cover is removed.

WARNING

If  NOT  factory  installed,  a  main  switch  or  other  means  for
disconnection,  having  a  contact  separation  in  all  poles
providing  full  disconnection  under  overvoltage  category  III
condition, MUST be installed in the fixed wiring.

WARNING

▪ ONLY use copper wires.

▪ Make sure the field wiring complies with the applicable

legislation.

▪ All field wiring MUST be performed in accordance with

the wiring diagram supplied with the product.

▪ NEVER  squeeze  bundled  cables  and  make  sure  they

do  NOT  come  in  contact  with  the  piping  and  sharp
edges. Make sure no external pressure is applied to the
terminal connections.

▪ Make sure to install earth wiring. Do NOT earth the unit

to  a  utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earth may cause electrical shock.

▪ Make  sure  to  use  a  dedicated  power  circuit.  NEVER

use a power supply shared by another appliance.

▪ Make  sure  to  install  the  required  fuses  or  circuit

breakers.

▪ Make sure to install an earth leakage protector. Failure

to do so may cause electrical shock or fire.

▪ When installing the earth leakage protector, make sure

it  is  compatible  with  the  inverter  (resistant  to  high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.

CAUTION

▪ When  connecting  the  power  supply:  connect  the  earth

cable  first,  before  making  the  current-carrying
connections.

▪ When  disconnecting  the  power  supply:  disconnect  the

current-carrying cables first, before separating the earth
connection.

▪ The length of the conductors between the power supply

stress  relief  and  the  terminal  block  itself  must  be  as
such that the current-carrying wires are tautened before
the  earth  wire  is  in  case  the  power  supply  is  pulled
loose from the stress relief.

NOTICE

Precautions when laying power wiring:

▪ Do  NOT  connect  wiring  of  different  thicknesses  to  the

power  terminal  block  (slack  in  the  power  wiring  may
cause abnormal heat).

▪ When  connecting  wiring  which  is  the  same  thickness,

do as shown in the figure above.

▪ For wiring, use the designated power wire and connect

firmly,  then  secure  to  prevent  outside  pressure  being
exerted on the terminal board.

▪ Use  an  appropriate  screwdriver  for  tightening  the

terminal  screws.  A  screwdriver  with  a  small  head  will
damage  the  head  and  make  proper  tightening
impossible.

▪ Over-tightening the terminal screws may break them.

Install  power  cables  at  least  1  m  away  from  televisions  or  radios  to
prevent  interference.  Depending  on  the  radio  waves,  a  distance  of
1 m may not be sufficient.

WARNING

▪ After  finishing  the  electrical  work,  confirm  that  each

electrical  component  and  terminal  inside  the  electrical
components box is connected securely.

▪ Make sure all covers are closed before starting up the

unit.

NOTICE

Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.

If  there  exists  the  possibility  of  reversed  phase  after  a
momentary black out and the power goes on and off while
the  product  is  operating,  attach  a  reversed  phase
protection  circuit  locally.  Running  the  product  in  reversed
phase can break the compressor and other parts.

2.3

For the user

WARNING

If you are NOT sure how to operate the
unit, contact your installer.

WARNING

Children aged from 8 years and above
and persons with reduced physical,
sensory or mental capabilities or lack
of experience and knowledge can only
use this appliance if they have been

Содержание EKMBDXB7V1

Страница 1: ...Installation manual Modbus Interface DIII English Installation manual Modbus Interface DIII EKMBDXB7V1 ...

Страница 2: ...m 100 mm 50 mm 87 mm 40 mm Max 60 C IP X0 Min 0 C www daikineurope com support and manuals product information UNIT F1 F2 Q1DI 1N 50 Hz 230 V AC 124 mm 2 1 RS485 0 75 1 25 mm2 MAX 500 m Design guide 0 75 1 25 mm2 X3M X1M L N A B F1 F2 RS 485 TO OUT D UNIT 1x 1x ...

Страница 3: ...sures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit DANGER RISK OF BURNING SCALDING Do NOT touch the heating element of the unit water piping or internal parts during and immediately af...

Страница 4: ...connecting the power supply connect the earth cable first before making the current carrying connections When disconnecting the power supply disconnect the current carrying cables first before separating the earth connection The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current carrying wires are tautened before the earth...

Страница 5: ...d or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application e...

Страница 6: ......

Страница 7: ......

Страница 8: ...4P635058 1 2020 10 Copyright 2014 Daikin Verantwortung für Energie und Umwelt 4P357730 1 0000000N ...

Отзывы: