6 Installation
Installation manual
11
EKHWS150~300D3V3
Domestic hot water tank with option kit for air to water heat pump
system
4P510672-1B – 2018.01
X2M
X1M
X5M
c
b
a
b+c+d
d
a
a
Thermistor cable
b
Booster heater power supply cable
c
3-way valve cable
d
Booster heater cable
6.5.3
To connect the electrical wiring on the
outdoor unit
For EBLQ/EDLQ only:
1
Install the booster heater power supply sticker in the unit switch
box on the location shown in the illustration below.
2
Mount the contactor K3M and terminal block X4M. Fix the
contactor with the 2 contactor fixing screws supplied. Fix the
terminal block with the 2 tapping screws supplied.
3
Install the jumper wire from the accessory bag in between
terminals X2M/7 and X2M/8.
4
Connect the earth wire of the booster heater power supply
cable to the switch box earthing screw.
5
Connect the N and L wires of the booster heater power supply
cable to the lower contactor terminals of K3M.
6
Connect the upper terminals of X4M/1 and X4M/2 to the upper
contactor terminals of K3M.
7
Connect the signal wires of contactor K3M (discard the
connector) to control box terminals X8M/1 and X8M/2.
8
Connect the wires of the thermistor cable to the control box
terminals X2M/3 and X8M/4.
9
Connect the earth wire of the control box terminal X4M to the
switch box earthing screw (located above the terminal).
10
Connect the booster heater cable (field supply) to the control
box terminals X4M/1+2+earth.
11
Connect the 3-way valve cable to control box terminals X8M/3,
X8M/4 and X8M/5.
12
Fix the cables to the cable tie mountings with cable ties to
ensure strain relief.
13
When routing out cables, make sure that these do not obstruct
mounting of the unit cover.
INFORMATION
Only the relevant field wiring is shown.
5
4
3
2
1
X8M
X1M
X4M
K3M
X2M
A1P
1 2
2
X4M
4
3
8
7
R5T
>50 mm
M3S
M3S
L
BRN
BLU
BLK
N Y
L
BLK
BLU
BRN
N Y
X2M
5 4 3
F2B
N
X8M
L
2
K3M
1
230 V AC
3 kW
L N
V3
6.5.4
To connect the electrical wiring on the
domestic hot water tank
WARNING
Make sure all field wiring is insulated from the surface of
the inspection hole or can resist temperatures to 90°C.
1
Remove the switch box cover from the tank.
2
Route the booster heater power supply cable and the thermistor
cable (for EKHWS200: ONLY booster heater power supply
cable) through one of the recesses at the bottom of the tank
and then through the cable conduit that leads to the tank switch
box.