5 Operation

Operation manual

12

EKHWET90~120BAV3

R32 Split series – Domestic hot water tank

4P680075-1B – 2022.02

ambient  temperatures  too  cold,  raise  the  slope  so  that  the  tank
temperature  is  heated  increasingly  more  at  decreasingly  lower
ambient temperatures.

▪ Change  the 

offset

  to  equally  increase  or  decrease  the  target

temperature  of  the  tank  for  different  ambient  temperatures.  For
example,  if  the  tank  temperature  is  always  a  bit  too  cold  at
different  ambient  temperatures,  shift  the  offset  up  to  equally
increase the tank target temperature for all ambient temperatures.

Examples

Weather-dependent curve when slope is selected:

X1

X2

c

d

Y1

Y2

Y3

Y4

a

b

Weather-dependent curve when offset is selected:

Y1

Y2

Y3

Y4

X1

X2

a

b

c

d

Item

Description

a

WD curve before changes.

b

WD curve after changes (as example):

▪ When  slope  is  changed,  the  new  preferred

temperature  at  X1  is  unequally  higher  than  the
preferred temperature at X2.

▪ When  offset  is  changed,  the  new  preferred

temperature  at  X1  is  equally  higher  as  the  preferred
temperature at X2.

c

Slope

d

Offset

X1, X2

Examples of outdoor ambient temperature

Y1, Y2,

Y3, Y4

Examples of desired tank temperature. The icon
corresponds to the heat emitter for that zone:

: Domestic hot water tank

Possible actions on this screen

Select slope or offset.

Increase or decrease the slope/offset.

When slope is selected: set slope and go to offset.

When offset is selected: set offset.

Confirm changes and return to the submenu.

5.8.4

Using weather-dependent curves

Configure weather-dependent curves as following:

To define the setpoint mode

To use the weather-dependent curve, you need to define the correct
setpoint mode:

Go to setpoint mode …

Set the setpoint mode to …

Tank

[5.B] 

Tank

 > 

Setpoint mode

Restriction: 

Only available to

installers.

Weather dependent

To change the type of weather-dependent curve

To change the type for the tank, go to [5.E] 

Tank

.

▪ [5.E] 

Tank

 > 

WD curve type

Restriction: 

Only available to installers.

To change the weather-dependent curve

Zone

Go to …

Tank

Restriction: 

Only available to

installers.

[5.C] 

Tank

 > 

WD curve

INFORMATION

Maximum and minimum setpoints

You cannot configure the curve with temperatures that are
higher  or  lower  than  the  set  maximum  and  minimum
setpoints  for  the  tank.  When  the  maximum  or  minimum
setpoint is reached, the curve flattens out.

To fine-tune the weather-dependent curve: slope-offset curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of the tank:

You feel …

Fine-tune with slope and

offset:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Slope

Offset

OK

Cold

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

See 

"5.8.3 Slope-offset curve"

 [

4

 11].

To fine-tune the weather-dependent curve: 2-points curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of the tank:

You feel …

Fine-tune with

setpoints:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Y2

(a)

Y1

(a)

X1

(a)

X2

(a)

OK

Cold

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

(a)

See 

"5.8.2 2-points curve"

 [

4

 11].

Содержание EKHWET90BAV3

Страница 1: ...Operation manual R32 Split series Domestic hot water tank English Operation manual R32 Split series Domestic hot water tank EKHWET90BAV3 EKHWET120BAV3...

Страница 2: ...ure the best possible performance Request the installer to inform you about the settings that he used to configure your system Check if he has filled in the installer settings tables If NOT request hi...

Страница 3: ...onic products may NOT be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts MUST be do...

Страница 4: ...User interface of the indoor unit 4 Quick guide 4 1 User permission level The amount of information you can read and edit in the menu structure depends on your user permission level User Standard mod...

Страница 5: ...ser interface the screen darkens Pressing any button or rotating any dial awakens the display Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the...

Страница 6: ...7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule Level 5 Tank Powerful operation Comfort setpoint Eco setpoint Reheat setpoint Schedule WD curve WD curve type D Wireless gateway Mode Re...

Страница 7: ...uiet mode active e3 Outdoor unit f Indoor unit domestic hot water tank f Wall mounted indoor unit with integrated tank g Holiday mode Holiday mode active h Malfunction A malfunction occurred See 8 1 T...

Страница 8: ...alues c Selected setting and value Possible actions on this screen Go through the list of settings Change the value Go to the next setting Possible actions on this screen Confirm changes and proceed 5...

Страница 9: ...vailable again During the afternoon and evening you consume hot water again and the DHW tank temperature decreases again At 00 00 the next day the cycle repeats 5 6 3 Scheduled reheat mode In schedule...

Страница 10: ...1 Select the day of which you want to clear the content For example Friday Mon Sat Wed Fri Thu Tue Sun User defined C 2 Select Delete Delete Edit Copy 3 Select OK to confirm To program the schedule f...

Страница 11: ...on its weather dependent curve This curve defines how much the target temperature of the tank must be at different outdoor temperatures Because the slope of the curve depends on local circumstances s...

Страница 12: ...t Confirm changes and return to the submenu 5 8 4 Using weather dependent curves Configure weather dependent curves as following To define the setpoint mode To use the weather dependent curve you need...

Страница 13: ...oster heater is allowed either after a certain amount of time has passed since start of DHW operation refer below or when outdoor unit is unable to perform DHW Quick mode timer When Quick mode is chos...

Страница 14: ...taller 8 2 To check the malfunction history Conditions The user permission level is set to advanced end user 1 Go to 8 2 Information Malfunction history You see a list of the most recent malfunctions...

Страница 15: ...e malfunction a We recommend to purge air with the air purge function of the unit to be performed by the installer If you purge air from the heat emitters or collectors mind the following WARNING Air...

Страница 16: ...4P680075 1B 2022 02 Copyright 2021 Daikin 4P680075 1 B 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: