13
|
Maintenance and service
Installer reference guide
100
E120B
R32 Split series – Domestic hot water tank
4P680077-1A – 2022.11
NOTICE
The booster heater sealing must be replaced after every check. Tighten the booster
heater screws to 10 N•m of torque.
13.3 To drain the domestic hot water tank
DANGER: RISK OF BURNING/SCALDING
The water in the tank can be very hot.
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Close the cold water supply.
Prerequisite:
Open all the hot water tapping points to allow air to enter the
system.
1
Remove the water inlet connection, the water will flow out of the tank.
a b
a
DHW – hot water OUT (screw connection, ½”)
b
DHW – cold water IN (screw connection, ½”)