2
x
Set-up and installation
DAIKIN EKHHP(3/5)00AA2V3
DAIKIN Hot water heat pump
008.1423444_02 – 09/2015
Installation and maintenance manual
11
–
Pay attention to the stipulated tightening torque
(see section 2.1).
– Design the lines as such that the sound attenuation cowl
can be applied without any problem following assembly.
–
Water shortage protection:
The temperature monitoring
of the controller safely switches off the DAIKIN EKHHP in
the event of a water shortage. No additional water short-
age protection is needed in the construction. Neverthe-
less, regular checking of the fill level is necessary in order
to ensure function as intended.
–
Avoid damages caused by deposits and corrosion:
Observe the requirements for the buffer water storage
(see section 1.5.6).
● Carefully insulate pipe lines against heat loss and so as to
avoid the formation of condensation (insulation thickness at
least 20 mm).
If the installation conditions require the hydraulic
connection to be directly upwards, the cover
hood can be cut out along the broken line.
Fig. 2-4
Creating the hood cut-out
WARNING!
There is a danger of scalding at hot water tem-
peratures over 60°C. This is possible, when
solar energy is used, with a connected external
heating device, when the Legionella protection
is activated or when the domestic hot water
target temperature is set higher than 60°C.
● Install scald protection (hot water mixer).
Fig. 2-5
Hydraulic connection - legend see tab. 2-2
(Example EKHHP500AA2V3 with
Solar and optional
auxiliary heater)
1
Cold water connection
2
Hot water distribution network
3
Feed
Solar or for other heat source*
4
Return
Solar or for other heat source*
6
Circulation*
7
Customer's side: Check valve, return valve
7a
Circulation brakes (2 in number) Recommended accessory
8a
Feed
Solar or for other heat source*
8b
Return
Solar or for other heat source*
9
Gas line (refrigerant)
10
Liquid line (refrigerant)
EKHHP
DAIKIN Heat pump indoor unit
EKSRPS4A
DAIKIN Solar regulation and pump unit*
FLG FlowGuard - Solar regulating valve with flow indicator*
ERWQ
DAIKIN Heat pump external unit
FLS FlowSensor - Solar flow and feed flow temperature
measurement*
P
K
Boiler circulation pump*
P
Z
Circulation pump*
SK
Solar panel field*
SV
Customer's side: Safety over-pressure valve
W
EX
External heat generator*
*
Optional
Tab. 2-2 Legend for fig. 2-5
Содержание EKHHP300AA2V3
Страница 2: ...15 17...
Страница 40: ...008 1423444_02 09 2015 Copyright Daikin...