User, Installations and Maintenance Manual

7.5  Operating mode

The following modes are available for this water heater

7.5.1  ECO 

The display shows the symbol 

With this mode only the heat pump is used within the product 

operating limits to ensure maximum possible energy saving.

The heat pump is switched on 5 minutes after selecting this 

mode or from the last switch-off.

In case of switching off, within the first 5 minutes, the heat pump 

will remain on anyway to ensure at least 5 minutes of continu-

ous operation.

7.5.2  AUTOMATIC

The display shows the symbol 

 

+  .

With this mode the heat pump is used and, if necessary, also the 

heating element, within the product operating limits, to ensure 

best possible comfort.

The heat pump is switched on 5 minutes after selecting this 

mode or from the last switch-off.

In case of switching off, within the first 5 minutes, the heat pump 

will remain on anyway to ensure at least 5 minutes of continu-

ous operation.

7.5.3  BOOST

The display shows the symbols 

 +   flashing.

This mode uses the heat pump and the heating element, within 

the product operating limits, to ensure faster heating.

The heat pump is switched on 5 minutes after selecting this 

mode or from the last switch-off.

In case of switching off, within the first 5 minutes, the heat pump 

will remain on anyway to ensure at least 5 minutes of continu-

ous operation.

The heating element is switched on immediately.

7.5.4  ELECTRIC

The display shows the symbol  .

With this mode only the heating element is used within the prod-

uct operating limits and is useful in situations of low inlet air 

temperatures.

7.5.5  VENTILATION

The display shows the message 

.

With this mode only the electronic fan inside the equipment 

is used and is useful for recirculating the air in the installation 

room if desired.

In automatic mode the fan will be adjusted to the minimum 

speed.

7.5.6  HOLIDAY

The display shows the symbol  .

This mode is useful when away for a limited time and then au-

tomatically finding the equipment working in automatic mode.

Using the + and - buttons it is possible set the days of absence 

during which the equipment is to remain in standby mode.

Press   and then on off to confirm.

7.5.7  Solar Mode 

+  or 

+ +  or 

 (

Only for models

 

PCV3)

When the solar mode is activated from the installer menu, only 

ECO - AUTOMATIC - HOLIDAY will be available.

When the symbol   on the display flashes, the solar mode is 

not operating and the unit works in the set mode: ECO, AUTO

-

MATIC or HOLIDAY.

When the symbol   on the display is lit up, the energy pro-

duced by the solar system is used to heat the water inside the 

tank via the solar coil.

7.5.8  Photovoltaic Mode 

+  or 

+ +  or 

When the photovoltaic mode is activated from the installer 

menu, only ECO - AUTOMATIC - HOLIDAY will be available.

When the symbol   on the display flashes, the photovoltaic 

mode is not operating and the unit works in the set mode: ECO, 

AUTOMATIC or HOLIDAY.

When the symbol   on the display is lit up, the energy pro-

duced by the photovoltaic system is used to heat the water in-

side the tank.

With ECO mode selected, the heat pump will operate until the 

set-point is reached and the heating element is switched on until 

the photovoltaic set-point set from the installer menu is reached.

Otherwise, with AUTOMATIC mode selected, the heating ele-

ment can also be switched on before reaching the set-point of 

this mode if the conditions require it.

7.5.9  

Off-Peak Mode 

 + 

 or 

 +   + 

When the photovoltaic mode is activated from the installer 

menu, only ECO - AUTOMATIC will be available.

When the symbol 

  on  the  display  flashes,  the  Off-Peak 

mode is not operating and the unit remains on standby and the 

heat pump and heating element are off.

Otherwise, when the symbol   on the display is lit up, the unit 

works in the ECO or AUTOMATIC mode.

Содержание EKHHE200CV3

Страница 1: ...EKHHE200CV3 EKHHE200PCV3 EKHHE260CV3 EKHHE260PCV3 User Installations and Maintenance Manual Domestic Hot Water Heat Pump Monobloc type...

Страница 2: ...floor 15 6 3 Aeraulic connections 15 6 4 Securing and connections of this appliance 17 6 5 Hydraulic connections 17 6 6 Integration with solar thermal system only for models EKHHE200PCV3 EKHHE260PCV3...

Страница 3: ...y with the appliance This appliance may be used by children 8 years of age or older and those with reduced physical sensory or mental capacity or lack of experience or knowledge if they are properly s...

Страница 4: ...fixing bracket provided for this purpose and adhesives are not considered to be a reliable fixing means This product is designed to be used at a maximum altitude of 2000 m Refer to description and il...

Страница 5: ...be attached to the water mains The minimum inlet water pressure for the correct operation of the appliance is 0 15 MPa 1 5 bar For models that incorporate a heat exchanger solar coil the circuit must...

Страница 6: ...d water open the hot water taps and then operate the drain valve of the safety device The pressure relief valve must be operated regularly to remove scale deposits and to ensure that it is not blocked...

Страница 7: ...ing symbols are used in the manual to highlight the most important information Caution Procedures to be followed Information Suggestions 2 1 Products Dear Customer Thank you for purchasing this produc...

Страница 8: ...ng operations use a forklift or an adequate pallet truck The packed equipment can be placed horizontally and back down to facilitate undoing the anchoring screws Unpacking must done carefully so as no...

Страница 9: ...ATTENTION Horizontal transport is allowed only for the last km according to that indicated see Positions not allowed for transport and han dling making sure supports are positioned in such a way at th...

Страница 10: ...gement for solar coil Inlet Only for models EKHHE200PCV3 EKHHE260PCV3 13 Prearrangement for solar coil outlet Only for models EKHHE200PCV3 EKHHE260PCV3 14 Steel tank with vitreous enamel coating accor...

Страница 11: ...CV3 UM A 1 G 250 250 250 250 mm B 490 493 mm C 1 2 G 600 600 600 600 mm D 705 785 705 785 mm E 1 G 876 5 1162 876 5 1162 mm G 1142 1427 1142 1427 mm H 1607 1892 1607 1892 mm I 3 4 G 250 250 mm L 3 4 G...

Страница 12: ...60 1960 W Rated current 8 5 8 5 8 5 8 5 A Total max absorbed power 2030 2030 2030 2030 W Max current 8 93 8 93 8 93 8 93 A Heating time 1 BOOST MODE 3 58 5 06 3 58 5 06 h min Storage Storage capacity...

Страница 13: ...r animals or serious dam age to property or the environment NB If the possibility of a product fault or failure can cause damage to people animals and property it is nec essary to provide for a separa...

Страница 14: ...installation The product must be installed in a suitable place i e to allow normal use and adjustment operations as well as routine and extraordinary maintenance The necessary operating space must th...

Страница 15: ...In addition to the spaces indicated in 6 1 the heat pump re quires adequate air ventilation Create a dedicated air channel as indicated in fig 12 Internal compartment Exterior fig 12 Example of air ou...

Страница 16: ...nt To ensure maximum product performance the grille must be selected from those with low pressure loss To avoid the formation of condensation water insulate the air extraction pipes and the ducted air...

Страница 17: ...the connection points Ref Function Model 200 l 260 l 1 Cold water inlet 1 G 2 Solar coil outlet 3 4 G 3 Solar coil inlet 3 4 G 4 Recirculation 3 4 G 5 Hot water outlet 1 G 6 Condensate drain 1 2 G A P...

Страница 18: ...ec tronic controller not supplied that has a voltage free contact type output to be connected to the DIG 1 input of the equipment see 6 7 1 Remote connections To use the equipment in this configuratio...

Страница 19: ...to verify conformity to the regulations in force and that the electrical system can suitably withstand the water heater s maximum power consumption val ues refer paragraph 4 2 for technical character...

Страница 20: ...s allows the equipment to be activated only when there is a signal coming from outside with prefer ential tariff If the electric contactor has a voltage free contact which closes when the preferential...

Страница 21: ...T1000 Solar collector Probe T5AL250V Solar thermal cut out fig 26 Equipment wiring diagram Description of connections available on the power board CN1 Air defrost and water NTC probes CN2 Not usable C...

Страница 22: ...place the ther mal cut out inside an adequate enclosure fixed to the wall Connect the thermal cut out in series with line L and neu tral N power supply connections of solar circulating pump for all po...

Страница 23: ...button lock function is automatically activated to prevent possible interactions with the water heater e g by children etc At the same time the backlighting level of the buttons and display decreases...

Страница 24: ...ation room if desired In automatic mode the fan will be adjusted to the minimum speed 7 5 6 HOLIDAY The display shows the symbol This mode is useful when away for a limited time and then au tomaticall...

Страница 25: ...30 min Anti legionella cycle activation time P29 0 23 h 23 h 7 6 2 Defrost function The display shows the symbol This equipment has an automatic evaporator defrost function which is activated when the...

Страница 26: ...Inlet air probe fault P04 P04 Evaporator inlet probe fault P05 P05 Evaporator outlet probe fault P06 P06 Compressor flow probe fault P07 P07 Solar collector probe fault P08 P08 High pressure protectio...

Страница 27: ...tons and pressing the and buttons together for 3 seconds The label of the first parameter is shown on the display with the letter A Pressing the button displays its value and pressing this button agai...

Страница 28: ...ifiable P4 Antilegionella duration 0 90 min 30 min Modifiable P5 Defrosting mode 0 compressor stop 1 hot gas 1 Modifiable P6 Electrical heater usage during defrosting 0 OFF 1 ON 0 Modifiable P7 Delay...

Страница 29: ...king period in AUTO mode for heating rate calculation 10 80 min 30 min Modifiable P32 Temperature threshold for electrical heater usage in AUTO mode 0 20 C 4 C Modifiable P33 Electronic expansion valv...

Страница 30: ...tact If not replace it with an IEC 60127 2 II certified time delay 5 A fuse Water cannot be heated via the heat pump in ECO or AUTOMATIC mode Switch the equipment off then switch it on again after a f...

Страница 31: ...powering it fig 28 9 2 Heating element safety thermostat reset This equipment has a manual reset safety thermostat connect ed in series with the heating element immersed in water which interrupts the...

Страница 32: ...ium is a weakly charged metal compared to the material of which the inside of the boiler is coated therefore it attracts first the negative charges that form with the heating of water consuming itself...

Страница 33: ...s that make up the equipment Unauthorized disposal of the product by the user involves the application of the administrative sanctions provided for by cur rent legislation The main materials that make...

Страница 34: ......

Страница 35: ......

Страница 36: ...2020 12 Copyright 2020 Daikin...

Отзывы: