Installation manual

33

EKHBX016BB3V3S

Indoor unit for air to water heat pump system

4PW62598-1 – 10.2010

Dual set point control

Applies only to installations with different heat emitter which require
different set points.

Dual set point control makes it possible to generate 2 different set
points.

[7-02] Dual set point control status: defines whether the dual
set point control is enabled (1) or disabled (0).

[7-03] Second set point heating: specifies the second set
point temperature in heating operation.

[7-04] Second set point cooling: specifies the second set
point temperature in cooling operation.

[8] Domestic water heating mode timer

Applies only to installations with a domestic hot water tank.

The 'domestic water heating mode timer' field settings defines the
minimum and maximum domestic water heating times, minimum time
between two domestic water heating cycles by heat pump, and
booster heater delay time.

[8-00] Minimum running time: specifies the minimum time
period during which heat pump domestic water heating mode
should be activated, even when the target domestic hot water
temperature for heat pump (T

HP OFF

) has already been

reached.

[8-01] Maximum running time: specifies the maximum time
period during which heat pump domestic water heating mode
can be activated, even when the target domestic hot water
temperature for heat pump (T

HP OFF

) has not yet been

reached.
The actual maximum running time will automatically variate
between [8-01] and [8-01]+[8-04] depending on the outdoor
temperature. See figure in chapter 

"[8-04]" on page 34

.

[8-02] Anti-recycling time: specifies the minimum required
interval between two heat pump domestic water heating
mode cycles.
The actual anti-recycling time will automatically variate
between [8-02] and 0 depending on the outdoor temperature.
See figure in chapter 

"[8-04]" on page 34

.

1

Heat pump domestic water heating mode (1=active, 0=not 
active)

2

Hot water request for heat pump (1=request, 0=no request)

t

Time

INFORMATION

There is no indication available which set point is active!

NOTICE

The first set point heating/cooling is the set point
selected on the user interface.
-

In heating mode the first set point can be a fixed 
value or weather dependent.

-

In cooling mode the first set point can be a fixed 
value or weather dependent.

The second set point heating [7-03] should be linked
to the heat emitters which requires the highest set
point in heating mode. Example: fan coil unit.

The second set point cooling [7-04] is always a fixed
value. It should be linked to the heat emitters which
requires the lowest set point in cooling mode.
Example: fan coil unit.

The actual second set point heating value depends on
the selected value of setting [7-03].
-

In case [7-03]=1~24, the actual second set point 
will be first set point heating increased with [7-03] 
(the maximum is 55°C).
In this way the second set point heating is linked to 
the first set point heating.

-

In case [7-03]=25~55, the actual second set point 
heating is equal to [7-03].

The selection of second set point or first set point is
determined by the terminals (X2M: 1, 2, 4).
The second set point has always priority on the first
set point.

INFORMATION

When dual set point control is enabled, heating/cooling
selection always has to be done on the user interface.

NOTICE

It is the responsibility of the installer to make sure no
unwanted situations can occur.

It is very important that the water temperature to the floor
heating loops never becomes too high in heating mode or
never too cold in cooling mode. Failure to observe this rule
can result in construction damage or discomfort. For
example in cooling mode condensation on the floor can
occur when water towards the floor heating loops is too
cold (dew point).

X2M

1

2

3

4

SP1

SP2

SP1

First set point contact

SP2

Second set point contact

INFORMATION

Note that when the unit is configured to work with a
room thermostat (refer to 

"8.2. Room  thermostat

installation configuration" on page 

23

), the

maximum running timer will only be taken into
account when there is a request for space heating
or space cooling. When there is no request for
space heating or space cooling, domestic water
heating by the heat pump will continue until the
'heat pump OFF temperature' (see field settings

"[6]" on page 31

) is reached. When no room

thermostat is installed, the timer is always taken
into account. 

INFORMATION

If the outdoor temperature is higher than the field
setting to which parameter [4-02] is set, and lower
than the field setting to which parameter [F-01], then
field settings of parameters [8-01], [8-02], and [8-04]
are not considered.

Parameter [F-01] is only applicable for EKHBX* indoor
units.

t

1

0

1

0

[8-01]

[8-02]

[8-00]

Содержание EKHBX016BB3V3S

Страница 1: ...INSTALLATION MANUAL EKHBX016BB3V3S Indoor unit for air to water heat pump system...

Страница 2: ...35 48 142 101 502 2 3 4 5 48 39 96 361 1 1 4 1 1 4 MBSP 895 922 830 469 260 B B T T 350 300 500 2x 2x 1x 1x 1x 1 2 3 4 5 30 90 2 1 3 4 1 2 3 4...

Страница 3: ...condo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za d...

Страница 4: ...cable 20 Connection of the valve control cables 20 Connection of the bottom plate heater 21 Connection of the pump 21 Connection to a bene t kWh rate power supply 21 7 4 Relocation of the digital cont...

Страница 5: ...eration of the unit always contact your local dealer for advice and information Improper installation or attachment of equipment or accessories could result in electric shock short circuit leaks re or...

Страница 6: ...the indoor unit and allows remote alarm output heating cooling ON OFF output bivalent operation permission signal for the auxiliary boiler or additional external backup heater permission signal Refer...

Страница 7: ...oom thermostat optional Pump operation and space heating When the room thermostat T is connected to the indoor unit the pump 5 will operate when there is a heating request from the room thermostat and...

Страница 8: ...stic water heating mode 2 Only applicable for tank with built in electrical booster heater EKHW INFORMATION Details on pump con guration can be found under 8 3 Pump operation con guration on page 24 N...

Страница 9: ...application without the room thermostat connected to the indoor unit but with the heating only room thermostat set heating only controlling the oor heating and the heating cooling thermostat set heat...

Страница 10: ...ays provided by the domestic hot water tank which is connected to the Daikin indoor unit The auxiliary boiler must be integrated in the piping work and in the eld wiring according to the illustrations...

Страница 11: ...o as to achieve the target leaving water temperature as set on the user interface When weather dependent operation is active the water temperature is determined automatically depending on the outdoor...

Страница 12: ...icker inside indoor unit cover 5 Indoor unit cover xing screw INFORMATION The advantage of the dual set point control is that the heat pump will can operate at the lowest required leaving water temper...

Страница 13: ...access to the switch box components e g to connect the eld wiring the switch box service panel can be removed Thereto loosen the front screws and unhitch the switch box service panel 5 2 Main compone...

Страница 14: ...ackup heater thermal protector The backup heater is equipped with a thermal protector The thermal protector is activated when the temperature becomes too high 18 Backup heater thermal fuse The backup...

Страница 15: ...the hydrobox unit on a rm wall and not in nor close to a sound sensitive environment e g bedroom NOTICE The electrical wiring diagram can be found on the inside of the switch box cover R4T H2O t R3T t...

Страница 16: ...vessels Where acidic or alkaline vapour is present 6 2 Dimensions and service space Unit of measurement mm Dimensions of the unit see gure 3 1 Flexible drain hose 2 Water outlet connection 3 Water in...

Страница 17: ...ed with the drain pan kit 6 6 Refrigerant pipework For all guidelines instructions and speci cations regarding refrigerant pipework between the indoor unit and the outdoor unit please refer to the out...

Страница 18: ...door unit If air moisture or dust gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end...

Страница 19: ...er volume in the water circuit is 100 l In this example no action or adjustment is required INFORMATION In most applications this minimum water volume will have a satisfying result In critical process...

Страница 20: ...WORK 7 1 Precautions on electrical wiring work NOTICE Be careful not to deform the unit piping by using excessive force when connecting the piping Deformation of the piping can cause the unit to malfu...

Страница 21: ...y contact S3S Dual set point 2 contact S4S Dual set point 1 contact SS1 DIP switch TR1 Transformer 24 V for PCB V1S Spark suppression 1 V2S Spark suppression 2 X1M X9M Terminal blocks X6Y X9B Connecto...

Страница 22: ...erminal 3 Fix the cable with cable ties to the cable tie mountings to ensure strain relief Item Description Required number of conductors Maximum running current 1 Power supply cable for outdoor unit...

Страница 23: ...to ensure strain relief 3 Depending on the required pump operation set DIP switch SS2 3 and eld setting F 00 See 8 3 Pump operation con guration on page 24 and eld setting F 00 in F Option setup on pa...

Страница 24: ...ill not operate Possible types of bene t kWh rate power supply Possible connections and requirements to connect the equipment to such power supply are illustrated in the gure below 1 Bene t kWh rate p...

Страница 25: ...enabled the screed dry out function can not be enabled When connecting the equipment to a bene t kWh rate power supply change eld setting d 01 When bene t kWh rate power supply is of type 1 or indoor...

Страница 26: ...ECTRIC SHOCK See 2 General safety precautions on page 2 WARNING Switch off the power supply before opening the switch box service panel and making any changes to the DIP switch settings 1 4 3 2 1 ON O...

Страница 27: ...on the pump will then run every 5 minutes during 3 minutes to check the water temperature UI UI UI SS2 3 ON wiring on when space heating or cooling is on y UI UI UI Heating only thermostat SS2 3 ON w...

Страница 28: ...k the switch box on loose connections or damaged electrical components 8 Fixation Check that the unit is properly xed to avoid abnormal noises and vibrations when starting up the unit 9 Damaged equipm...

Страница 29: ...ppropriate eld setting second code 4 Press the pfi button and pfj button to change the set value of the select eld setting 5 Save the new value by pressing the pr button 6 Repeat step 2 through 4 to c...

Страница 30: ...point at high ambient temperature Hi2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should b...

Страница 31: ...eration is only allowed if heat pump is out of operation range of heat pump domestic water heating mode TA 5 03 or TA 35 C or domestic hot water temperature is 2 C lower then the heat pump OFF tempera...

Страница 32: ...ay See operation manual When setting 4 03 2 the booster heater will be allowed to operate when TA 5 03 independent of the status of 5 02 If bivalent operation is enabled and permission signal for auxi...

Страница 33: ...and the backup heater during domestic hot water operation When the space heating priority function is enabled it is assured that the full capacity of the heat pump is used as much as possible for spa...

Страница 34: ...cheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot water user interfa...

Страница 35: ...t the domestic hot water set point is according to your requirements Start with a low domestic hot water storage set point and only increase if you feel that the domestic hot water supply temperature...

Страница 36: ...t set point can be a xed value or weather dependent The second set point heating 7 03 should be linked to the heat emitters which requires the highest set point in heating mode Example fan coil unit T...

Страница 37: ...y applicable in heating mode INFORMATION When heat pump is active in domestic water heating mode the delay time of booster heater is 8 03 When heat pump is not active in domestic water heating mode th...

Страница 38: ...is eld setting allows for distinction between detection of an alarm and detection of a power failure to the unit Bivalent operation Applies only to installations with an auxiliary boiler alternating o...

Страница 39: ...on 5 when bivalent operation function is enabled Daikin shall not be held liable for any damage resulting from failure to observe this rule INFORMATION In case the outdoor unit is NOT ERLQ_CA or ERHQ_...

Страница 40: ...A Outdoor temperature R Range L Local shift value 1 00 1 04 Applicable eld settings of the weather dependent set point 1 E Unit information readout E 00 Readout of the software version example 23 E 01...

Страница 41: ...mperature below which the bottom plate heater will be activated by indoor unit in order to prevent ice build up in the bottom plate of the outdoor unit at lower outdoor temperatures F 03 Bottom plate...

Страница 42: ...heater EKHTS 4 03 5 60 xed 5 C 03 Set point only in combination with domestic hot water tank with built in electrical booster heater EKHW 4 03 5 70 55 80 5 C 04 Interval only in combination with dome...

Страница 43: ...time storage start time 1 00 0 00 23 00 1 00 hour 05 Scheduled time reheat or continuous reheat 0 OFF 0 1 2 1 06 Scheduled time reheat start time 15 00 0 00 23 00 1 00 hour 07 Domestic hot water rehe...

Страница 44: ...04 Not applicable Do not change the default value 0 c Read only C Setup on EKRP1HB digital I O PCB 00 Solar priority mode setting 0 0 1 1 01 Alarm output logic 0 0 1 1 02 X1 X2 function Bivalent opera...

Страница 45: ...point of selected action number F 05 25 0 d 15 55 1 C 07 Time of selected action number F 05 0 d 0 72 12 hour 08 Under oor heating screed dry out program enabled disabled 0 OFF 0 1 1 09 Latest action...

Страница 46: ...displayed To start the test run operation press the y button To test the domestic water heating operation push the v button The test run operation will start without pressing the y button 3 The test r...

Страница 47: ...y out program as follows 1 Set in F 08 Under oor heating screed dry out program enabled disabled to 1 enabled 2 When nished press the z button to exit the FIELD SET MODE 2 Activate 1 Push the z button...

Страница 48: ...applications with domestic hot water tank only and K4M by use of an ohmmeter All contacts of these contactors must be in open position DANGER ELECTRIC SHOCK Before carrying out any maintenance or rep...

Страница 49: ...ring and immediately after operation See 2 General safety precautions on page 2 INFORMATION For problems related to the optional solar kit for domestic water heating refer to the troubleshooting in th...

Страница 50: ...he backup heater operation status eld setting 4 00 is turned on see 8 9 Field settings on page 26 Check whether or not the thermal protector of the backup heater has been activated refer to Main compo...

Страница 51: ...tlet water thermistor is giving the correct read out A1 Indoor unit PCB defective Contact your local dealer A5 Too low during cooling operation or too high during heating operation refrigerant tempera...

Страница 52: ...your local dealer U3 Under oor heating screed dry out program has been stopped by another error or by pushing operation off button or by power failure The error can only be reset in the test mode as...

Страница 53: ...ter drain hose nipple refrigerant liquid side 9 5 mm 3 8 inch refrigerant gas side 15 9 mm 5 8 inch Expansion vessel volume 10 l maximum working pressure MWP 3 bar Internal water volume 5 5 l Pressure...

Страница 54: ......

Страница 55: ......

Страница 56: ...4PW62598 1 10 2010 Copyright 2010 Daikin...

Отзывы: