EKHBRD011~0Y17
Indoor unit for air to water heat pump system and options
4P402192-1B – 2017.09
Operation manual
18
9
Automatic temperature compensation
00
Installation related setting
0
–2~2
0.2
°C
01
Installation related setting
0
–5~5
0.5
°C
02
Installation related setting
0
–5~5
0.5
°C
A
Option setup
00
Installation related setting
0
0~2
1
—
01
Installation related setting
0
0~2
1
—
02
Installation related setting
10
5~15
1
°C
03
Installation related setting
35
25~80
1
°C
04
Installation related setting
65
25~80
1
°C
b
Domestic hot water set points
00
Set point: reheat minimum temperature
35
35~65
1
°C
01
Set point: reheat maximum temperature
45
35~75
1
°C
02
Status: weather dependent domestic water
heating
1 (ON)
0/1
—
—
03
Set point: storage temperature
70
45~75
1
°C
04
Automatic maximum hot water tank storage
temperature
70
55~75
1
°C
C
Leaving water temperature limits
00
Installation related setting
80
37~80
1
°C
01
Installation related setting
25
25~37
1
°C
02
Not applicable. Do not change the default value.
20
18~22
1
°C
03
Not applicable. Do not change the default value.
5
5~18
1
°C
d
Domestic water heating retention times
00
Installation related setting
10
5~20
1
—
01
Installation related setting
30
10~60
5
—
02
Installation related setting
15
5~30
5
—
E
Service mode
00
Installation related setting
0
0/1
—
—
01
Not applicable. Do not change the default value.
0 (OFF)
0/1
—
—
02
Not applicable. Do not change the default value.
0 (OFF)
0/1
—
—
03
Not applicable. Do not change the default value.
1
0~2
1
—
04
Installation related setting
0
0~2
1
—
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
4PEN402192-1B_2017_09.book Page 18 Friday, October 6, 2017 8:45 PM