Installation manual
29
EKHBRD011~Y1
Indoor unit for air to water heat pump system
4PW60970-1B
The request signals for space heating can be implemented in 2
different ways (installer choice):
■
thermo ON/OFF signal (from external room thermostat)
■
status signal (active/not active) from the corresponding
temperature reducing device (
)
The electrical connections on the unit should be done on the optional
demand PCB.
The configuration of pattern A is done by field settings:
1
Select the appropriate pattern: [7-02]=0
2
Turn on multiple set point 1: [7-03]=0
➞
[7-03]=1
Turn on multiple set point 2: [7-04]=0
➞
[7-04]=1
3
Enter the temperature multiple set point 1: [A-03] (see below)
Enter the temperature multiple set point 2: [A-04] (see below)
Configuration example:
Multiple set point control according to pattern B
The basic setup of multiple set point pattern B is the same as a
normal classic design, so again no domestic water heating and
space heating is possible simultaneously.
Multiple set point pattern B is focused on space heating operation
and allows using multiple water set points in combination with the
remote controller or external room thermostat.
The configuration of pattern B allows 3 space heating set points and
1 domestic hot water set point.
The request signals for space heating can be implemented in 2
different ways (installer choice):
■
thermo ON/OFF signal (from external room thermostat)
Indoor unit
Domestic hot water tank
Temperature reducing device
Space 1
Space 1
Space 2
Space 2
Balancing bottle
Set
point
Field
setting
Thermo status
Domestic
hot water
70°C
(a)
(a) The water temperature needed to reach this set point of course is higher
than 70°C.
[b-03]
OFF
ON
OFF
OFF
OFF
Space 1
65°C
[A-03]
OFF
ON/OFF
ON
ON
OFF
Space 2
35°C
[A-04]
OFF
ON/OFF
ON
OFF
ON
Resulting heat pump water
OFF
>70°C
65°C
65°C
35°C
Space 1
DHW
Space 2
TRD
TRD
TRD
TRD
Space 1
DHW
Space 2
NOTE
■
If the system is configured according to pattern A,
nor the remote controller room thermostat
function (default OFF if multiple set point is
selected) nor the external room thermostat (as
replacement of the remote controller room
thermostat function) may be used.
■
The remote controller water temperature value is
ignored when pattern A is active.
■
It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high
water temperatures towards floor heating loops,
etc.).
■
It is the installers responsibility to make sure the
water circuit is well balanced (e.g. when a
domestic hot water request occurs, there will be
sufficient flow towards other appliances as well,
etc.)
■
Daikin does not offer any temperature reducing
device (
). This system only provides the
possibility to use multiple set points.
■
It is advised to only use the automatic storage
functionality for domestic water heating when
applying pattern A (with a high set point
temperature).
Space 1
DHW
Space 2
Space 0
M
A
TRD
TRD
4PW60970-1B_digital_EN.book Page 29 Thursday, September 2, 2010 1:15 PM
Содержание EKHBRD011ABV1
Страница 44: ...NOTES 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...
Страница 45: ...NOTES 4PW60970 1B_digital_EN book Page 2 Thursday September 2 2010 1 15 PM...
Страница 46: ...NOTES 4PW60970 1B_digital_EN book Page 3 Thursday September 2 2010 1 15 PM...
Страница 47: ...V1 Y1 NOTES 5 5 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...
Страница 48: ...4PW60970 1B Copyright 2010 Daikin 4PW60970 1B_digital_EN book Page 1 Thursday September 2 2010 1 15 PM...