manualshive.com logo in svg
background image

4 Installation

Installation manual

4

EK2CB07CAV3

Daikin Altherma low temperature monobloc option box

4P405546­1 – 2015.03

4.3

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.3.1

About electrical compliance

Equipment  complying  with  EN/IEC  61000­3­12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low­voltage
systems with input current >16 A and ≤75 A per phase.).

4.3.2

To connect the electrical wiring on the
option box

1

Insert the wiring from the bottom of the option box.

2

Make sure the low voltage wiring is located on the right. Route it
through the intake hole and fasten it with cable ties:

a

b

c

a

Low voltage wiring

b

High voltage wiring

c

Main power supply

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 25 mm.

4.3.3

To connect the option box power supply

1

Connect option box terminal X1M to control box terminal X1M.

X2M

X8M

A4P

X2M

X8M

X1M

A4P

3

2

1

X1M

3

2

1

1

GND

2

L

3

N

2

Fix  the  cable  with  cable  ties  to  the  cable  tie  mountings  to
ensure strain relief and to make sure that it does NOT come in
contact with sharp edges.

CAUTION

Do NOT push or place redundant cable length in the unit.

4.3.4

To connect the interconnection cable
between option box and control box

1

Connect the connectors from the accessory bag to X5A on A1P
of both the control box and the option box PCB.

2

Connect the connectors by way of a field­supplied cable.

X5A

A4P

X5A

A4P

a

b

a

a

Connectors (accessory)

b

Interconnection cable (field supply)

4.3.5

To connect the electrical meters

INFORMATION

In case of an electrical meter with transistor output, check
the  polarity.  The  positive  polarity  MUST  be  connected  to
X2M/7  and  X2M/9;  the  negative  polarity  to  X2M/8  and
X2M/10.

1

Connect the electrical meters cable to the appropriate terminals
as shown in the illustration below.

X2M

X8M

X1M

A4P

7

8

9

10

S5P S6P

2

Fix the cable with cable ties to the cable tie mountings.

Содержание EK2CB07CAV3

Страница 1: ...Installation manual Daikin Altherma low temperature monobloc option box English Installation manual Daikin Altherma low temperature monobloc option box EK2CB07CAV3 ...

Страница 2: ...umentation set This document is part of a documentation set The complete set consists of Document Contains Format General safety precautions Safety instructions that you must read before installing Paper in the box of the outdoor unit Outdoor unit installation manual Installation instructions Paper in the box of the outdoor unit Control box installation manual Installation instructions Paper in th...

Страница 3: ...ctric meter 2 per meter b 5 Power consumption digital inputs 2 per input signal b 6 Alarm output 2 b 7 Space cooling heating ON OFF output 2 b 8 Changeover to external heat source 2 b a Cable section 2 5 mm b Minimum cable section 0 75 mm NOTICE More technical specifications of the different connections are indicated on the inside of the option box 4 Installation 4 1 Opening the units 4 1 1 To ope...

Страница 4: ...connect the option box power supply 1 Connect option box terminal X1M to control box terminal X1M X2M X8M A4P X2M X8M X1M A4P 3 2 1 X1M 3 2 1 1 GND 2 L 3 N 2 Fix the cable with cable ties to the cable tie mountings to ensure strain relief and to make sure that it does NOT come in contact with sharp edges CAUTION Do NOT push or place redundant cable length in the unit 4 3 4 To connect the interconn...

Страница 5: ...to the appropriate terminals as shown in the illustration below X2M X8M X1M A4P 15 13 2 Fix the cable with cable ties to the cable tie mountings 4 3 8 To connect the space cooling heating ON OFF output 1 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below X8M X1M 1 2 2 Fix the cable with cable ties to the cable tie mountings 4 3 9 T...