background image

5 Configuration

Installation manual

16

EHVH/X04~1 EHVH/X08~16S26CB

Daikin Altherma – Low temperature split

4P384971-1E – 2018.02

#

Code

Description

[7.7.2.1]

[0-00]

[0-01]

[0-02]

[0-03]

Weather-dependent curve (heating):

[0-00]

[0-01]

Ta

Tt

[0-03]

[0-02]

▪ T

t

:  Target  leaving  water  temperature

(additional)

▪ T

a

: Outdoor temperature

[7.7.2.2]

[0-04]

[0-05]

[0-06]

[0-07]

Weather-dependent curve (cooling):

[0-04]

[0-05]

Ta

Tt

[0-07]

[0-06]

▪ T

t

:  Target  leaving  water  temperature

(additional)

▪ T

a

: Outdoor temperature

Leaving water temperature: Delta T source

#

Code

Description

[A.3.1.3.1]

[9-09]

Heating: required temperature
difference between entering and
leaving water.

In case a minimum temperature
difference is required for the good
operation of the heat emitters in heating
mode.

[A.3.1.3.2]

[9-0A]

Cooling: required temperature
difference between entering and
leaving water.

In case a minimum temperature
difference is required for the good
operation of the heat emitters in cooling
mode.

Leaving water temperature: Modulation

#

Code

Description

[A.3.1.1.5]

[8-05]

Leaving water temperature modulation:

▪ 0 (No): Disabled

▪ 1  (Yes):  Enabled.  The  leaving  water

temperature  is  calculated  according
to  the  difference  between  desired
and actual room temperature.
This  allows  better  matching  of  the
heat 

pump 

capacity 

to 

actual

required  capacity  and  results  in  less
start/stop  cycles  of  the  heat  pump
and more economic operation.

#

Code

Description

N/A

[8-06]

Leaving water temperature maximum
modulation:

0°C~10°C (default: 3°C)

Requires modulation to be enabled.

This is the value by which the desired
leaving water temperature is increased
or lowered.

INFORMATION

When  leaving  water  temperature  modulation  is  enabled,
the  weather‑dependent  curve  needs  to  be  set  to  a  higher
position  than  [8-06]  plus  the  minimum  leaving  water
temperature  setpoint  required  to  reach  a  stable  condition
on  the  comfort  setpoint  for  the  room.  To  increase
efficiency, modulation can lower the leaving water setpoint.
By  setting  the  weather‑dependent  curve  to  a  higher
position, it cannot drop below the minimum setpoint. Refer
to the illustration below.

a

+[8-06]

−[8-06]

b

Ta

Tt

a

Weather-dependent curve

b

Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.

Leaving water temperature: Emitter type

#

Code

Description

[A.3.1.1.7]

[9-0B]

Reaction time of the system:

▪ 0:  Quick. 

Example: 

Small  water

volume and fan coils.

▪ 1:  Slow. 

Example: 

Large  water

volume, floor heating loops.

Depending on the system water volume
and the heat emitters type, the heat up
or cool down of a space can take
longer. This setting can compensate for
a slow or a quick heating/cooling
system by adjusting the unit capacity
during the heat up/cool down cycle.

5.2.6

Domestic hot water control

#

Code

Description

[A.4.1]

[6-0D]

Domestic hot water Type:

▪ 0 (Reheat only): Only reheat operation

is allowed.

▪ 1  (Reheat  +  sched.):  Same  as  2,  but

between the scheduled heatup cycles,
reheat operation is allowed.

▪ 2  (Scheduled  only):  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

[A.4.5]

[6-0E]

The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.

Содержание EHVH08S18CB

Страница 1: ...ature split English Installation manual Daikin Altherma Low temperature split EHVH04S18CB EHVH08S18CB EHVH08S26CB EHVH11S18CB EHVH11S26CB EHVH16S18CB EHVH16S26CB EHVX04S18CB EHVX08S18CB EHVX08S26CB EH...

Страница 2: ...ohjeidemme mukaisesti za p edpokladu e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim do...

Страница 3: ...Basic configuration 13 5 2 1 Quick wizard Language time and date 13 5 2 2 Quick wizard Standard 13 5 2 3 Quick wizard Options 14 5 2 4 Quick wizard Capacities energy metering 15 5 2 5 Space heating co...

Страница 4: ...stic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into the piping can lead to excessive corrosion 3 2 1 To check the water volume and flow rate M...

Страница 5: ...rmostat 2 d a Refer to name plate on outdoor unit b Minimum cable section 0 75 mm c Cable section 2 5 mm d Cable section 0 75 mm till 1 25 mm maximum length 50 m Voltage free contact shall ensure the...

Страница 6: ...on of the piping can cause malfunctioning of the unit To facilitate service and maintenance 2 shut off valves are provided Mount the valves on the space heating water inlet and space heating water out...

Страница 7: ...isconnect the water supply hose from the fill valve 4 4 4 To fill the domestic hot water tank 1 Open every hot water tap in turn to purge air from the system pipe work 2 Open the cold water supply val...

Страница 8: ...over to external heat source control Space cool heat operation control CAUTION Do NOT push or place redundant cable length in the unit 4 5 3 To connect the main power supply 1 Connect the main power s...

Страница 9: ...the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax 1 Connect the backup heater power supply For 3V models a double pole fuse is used for F1B For 9W mo...

Страница 10: ...e shape of the backside of the user interface by overtightening the mounting screws Fix the wallplate of the user interface to the wall 4 Connect as shown in 4A Connect as shown in 4A 4B 4C or 4D 5 Re...

Страница 11: ...put cable to the appropriate terminals as shown in the illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie...

Страница 12: ...indoor unit 4 6 2 To close the indoor unit 1 Close the switch box cover 2 Reinstall the top plate 3 Reinstall the front panel NOTICE When closing the indoor unit cover make sure that the tightening t...

Страница 13: ...rface will return to the default home screen To modify an overview setting Example Modify 1 01 from 15 to 20 1 Go to A 8 Installer settings Overview settings 2 Go to the corresponding screen of the fi...

Страница 14: ...6 an error code will appear and the system will NOT operate A 2 2 A D 02 Domestic hot water pump 0 No NOT installed 1 Secondary rtrn Installed for instant hot water 2 Disinf shunt Installed for disin...

Страница 15: ...led 100 pulse kWh 5 Installed 1000 pulse kWh A 2 2 9 D 09 Optional external kWh meter 2 0 No NOT installed 1 Installed 0 1 pulse kWh 2 Installed 1 pulse kWh 3 Installed 10 pulse kWh 4 Installed 100 pu...

Страница 16: ...nabled This is the value by which the desired leaving water temperature is increased or lowered INFORMATION When leaving water temperature modulation is enabled the weather dependent curve needs to be...

Страница 17: ...trol Averaging time Ext amb sensor offset Forced defrost Commissioning Test run UFH screed dryout Air purge Actuator test run Standard Unit type Compressor type Indoor software type BUH type Backup he...

Страница 18: ...unit are fully open The air purge valve is open at least 2 turns The pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water vol...

Страница 19: ...p heater step 1 test Backup heater step 2 test Pump test INFORMATION Make sure that all air is purged before executing the test run Also avoid disturbances in the water circuit during the test run Sol...

Страница 20: ...OUT Space heating cooling water IN Domestic hot water hot water out Domestic hot water cold water in Field installed Shut off valve with drain fill valve Field installed Shut off valve with drain fil...

Страница 21: ...ess Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless O...

Страница 22: ...by PCB English Translation 230 V AC supplied by PCB 230 V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical me...

Страница 23: ...main X2M 1 4 add X2M 1a 4 main X2M 1 2 3 4 add X2M 1a 2a 3 4 main X2M 1 2 4 add X2M 1a 2a 4 NC valve X2M 5 7 NO valve X2M 6 7 2 core 2 core 2 core 2 core 2 core 2 core signal 5 core 3 core 4 or 3 core...

Страница 24: ...4P384971 1E 2018 02 Copyright 2014 Daikin 4P384971 1 E 00000006...

Отзывы: