5.  Install heating element part of the heater kit (Figure 2) in the heater box using screws from heater box cover.  Ensure the elements 

are positioned in the retaining bracket as shown in Figure 3.  It may be necessary to remove the horizontal supply cover to observe 

the bracket.  The heater box cover can be discarded. 

6.  Install electric panel part of the kit to the left side of the heater box using 3 screws supplied with this IO (Figure 4).

A

HEATING

ELEMENT

SCREWS FROM UNIT

FIGURE 3

BACK RODS OF HEATER KIT

TO BE PLACED IN SLOTS OF

RETAINER BRACKET

DETAIL A

7.  Connect power to kit.

•  Remove power cable from the box.
•  Connect leads to breakers with one lead for each power leg.
•  Route all leads through the blower deck and into the control box  as shown in Figure 4.
•  Connect the leads to the single point black with the far left lug (L1), the middle lug (L2), and the far right lug (L3).

NOTE:

 Single phase kits will only have 2 lugs (L1 and L2).

 

FIGURE 4

HEATING ELEMENT

CONNECT 9-PIN CONNECTOR

FROM UNIT TO 9-PIN CONNECTOR

OF HEATER KIT

BLACK WIRES FROM HEATER KIT

POWER BLOCK

3 SCREWS

Содержание EHS Series

Страница 1: ...flict between existing practices and the content of this manual the precautions listed here take precedence Description These installation instructions supplement the electric heater kits for installation in the following models DRC036 DRC048 DRC060 DRC072 DRH036 DRH048 DRH060 DRH072 DBC036 DBC048 DBC060 DBC072 DBH036 DBH048 DBH060 DBH072 These instructions should be used only as a supplement to i...

Страница 2: ...re 4 A HEATING ELEMENT SCREWS FROM UNIT FIGURE 3 BACK RODS OF HEATER KIT TO BE PLACED IN SLOTS OF RETAINER BRACKET DETAIL A 7 Connect power to kit Remove power cable from the box Connect leads to breakers with one lead for each power leg Route all leads through the blower deck and into the control box as shown in Figure 4 Connect the leads to the single point black with the far left lug L1 the mid...

Страница 3: ... and DBH models 13 Close control box door 14 Reconnect power to the unit 15 Test unit to ensure it is functioning properly 16 Place Heater wiring diagram beside unit diagram UNITS HEATER KIT MODEL NUMBER kW MINIMUM SCFM EH S05 5 EH S10 10 EH S15 15 EH S05 5 EH S10 10 EH S15 15 EH S18 18 EH S20 20 EH S05 5 EH S10 10 EH S15 15 EH S20 20 EH S05 5 EH S10 10 EH S15 15 EH S20 20 1950 AIR FLOW FOR ELECTR...

Страница 4: ...d forgiving to operate We use qual ity materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www daikincomfort com for information on Products Warranties Customer Services Parts Contractor Program and Training Financing Options 2019 CUSTOMER FEEDBACK Daikin is very interested in all product comments ...

Отзывы: