background image

16

17  FULLY COMMUNICATING DAIKIN SYSTEM

NOTE: 

For a detailed procedure of thermostat commission-

ing process, please visit the Daikin 

One

+ website at 

http://www.daikinone.com

17.1 Overview

A fully communicating Daikin system is a system that 

includes a compatible air handler and air conditioner or 

heat pump with a  communicating thermostat.  
A fully communicating Daikin heating/air conditioning sys-

tem differs from a non-communicating/traditional system 

in the manner in which the indoor unit, outdoor unit and 

thermostat interact with one another.  In a traditional sys-

tem, the thermostat sends commands to the indoor and 

outdoor units via analog 24 VAC signals.  It is a one-way 

communication path. The indoor and outdoor units typically 

do not return information to the thermostat.
For a fully communicating Daikin system, the indoor unit, 

outdoor unit, and thermostat “communicate” digitally with 

one another.  It is now a two-way communications path.  

The thermostat still sends commands to the indoor and 

outdoor units and may also request and receive information 

from both the indoor and outdoor units. This information 

may be displayed on the communicating thermostat. The 

indoor and outdoor units also interact with one another. The 

outdoor unit may send commands to or request information 

from the indoor unit. This two-way digital communications 

between the thermostat and subsystems (indoor/outdoor 

unit) is the key to unlocking the benefits and features of 

the fully comunicating Daikin system.
Two-way digital communications is accomplished using 

only two wires. The thermostat and air handler controls 

are powered with 24 VAC. A maximum of 4 wires between 

the air handler and thermostat is required to operate the 

system. An inverter equipped outdoor unit does not re-

quire 24 VAC. Only the 2 digital communication wires are 

required between the air handler and inverter unit (pins 1 

and 2 on the thermostat connector.)

17.2 Airflow Consideration

Airflow demands are managed differently in a fully com

-

municating system than in a non-communicating wired 

system.  The system operating mode (as determined by the 

thermostat) determines which unit calculates the system 

airflow demand. If the indoor unit is responsible for deter

-

mining the airflow demand, it calculates the demand and 

sends it to the ECM motor. If the outdoor unit or thermostat 

is responsible for determining the demand, it calculates 

the demand and transmits the demand along with a fan 

request to the indoor unit. The indoor unit then sends the 

demand to the ECM motor. Table 11 lists the various fully 

communicating Daikin systems, the operating mode, and 

airflow demand source.

For example, assume the system is a heat pump matched 

with an air handler. With a call for low stage cooling, the 

heat pump will calculate the system’s low stage cooling 

airflow demand. The heat pump will then send a fan request 

along with the low stage cooling airflow demand to the air 

handler. Once received, the air handler will send the low 

stage cooling airflow demand to the ECM motor. The 

ECM motor then delivers the low stage cooling airflow.  

See the applicable fully communicating Daikin System 

air conditioner or heat pump installation manual for the 

airflow delivered during cooling or heat pump heating.

In continuous fan mode, the communicating thermostat 

provides the airflow demand. The communicating 

thermostat provides 4 continuous fan speeds (25%, 50%, 

75% and 100% of maximum airflow). During continuous 

fan operation, the thermostat sends a fan request along 

with the continuous fan demand to the air handler. The air 

handler, in turn, sends the demand to the ECM motor. The 

ECM motor delivers the requested continuous fan airflow.

17.3 Thermostat Wiring

NOTE: 

Refer to section Electrical Connections for 

208/230 volt line connections to the air handler

.

NOTE: 

It is

 

STRONGLY

 

recommended that no more 

than two wires be connected in a single terminal. If two 

wires are used in a terminal, it is recommended the 

same type of wire be used (i.e. Both stranded or solid 

for secure connection).

 

Failure to do so may result in 

intermittent operation.

Typical 18 AWG thermostat wire may be used to wire the 

system components.  Two hundred fifty (250) feet is the 

maximum of wire between indoor unit and outdoor unit,  

and one hundred twenty five (125) feet between indoor 

unit and thermostat.

17.3.1 Two-Wire Outdoor and Four-Wire Indoor 

Wiring

Typical wiring will consist of two wires between the 

indoor unit and outdoor unit and four wires between 

the indoor unit and thermostat.  Figure 20 shows the 

required wires are: data lines, 1 and 2; “R” (24 VAC 

hot) and “C” (24 VAC common).

17.4 Network Troubleshooting

Occasionally the need to troubleshoot the network may 

arise.  The integrated air handler control has some on-

board tools that can be used to troubleshoot the network.  

These tools are: red communications LED, green receive 

(Rx) LED, and the learn button. Refer to the 

Communi-

cations Troubleshooting Chart

 at the end of this manual 

for error codes, possible causes and corrective actions
•  Red communications LED – Indicates the status of 

the network. The Communications Troubleshooting 

Chart on the following page indicates the LED status 

and the corresponding potential problem.

•  Green receive LED – Indicates network traffic.  The 

following table indicates the LED status and the corre-

sponding potential problem.
•  Learn button – Used to reset the network.  Depress 

the button for approximately 2 seconds to reset the 

network.

Содержание EEV Series

Страница 1: ...ting 15 16 1 Electrostatic Discharge ESD Precautions 15 16 2 Diagnostic Chart 15 16 3 Fault Recall 15 17 Fully Communicating Daikin System 16 17 1 Overview 16 17 2 Airflow Consideration 16 17 3 Thermo...

Страница 2: ...venir si un appareil produisant du monoxyde de carbone continue de fonctionner au sein de la zone confin e Failure to properly reconnect sensor wires may result in Error codes and the unit not operati...

Страница 3: ...consult the white busi ness pages the yellow page section of the local telephone book or contact HOMEOWNER SUPPORT DAIKIN NORTH AMERICA LLC 190001 KERMIER ROAD WALLER TEXAS 77484 855 770 5678 5 PRE IN...

Страница 4: ...is for the secondary drain line if used 6 2 Horizontal Left Installation No field modifications are permissible for this application Drain port labeled B in Figure 1 is the primary drain for this appl...

Страница 5: ...to the corner post using screw mount wire ties 3 Secure the insulated connectors to the corner using two screws and the mounting wire ties provided 2 Connect the junction connectors and slide the ins...

Страница 6: ...t in panel damage UPFLOW Figure 3 DOWNFLOW Figure 4 HORIZONTAL LEFT Figure 5 HORIZONTAL RIGHT Figure 6 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel B...

Страница 7: ...ep 1 as shown in Figure 10 8 Two drain ports located at the bottom drain pan horizon tally oriented are to be used for upflow and downflow applications and the two on the side drain pan vertically ori...

Страница 8: ...s 8 CONDENSATE DRAIN LINES The coil drain pan has a primary and a secondary drain with 3 4 NPT female connections The connectors required are 3 4 NPT male either PVC or metal pipe and should be hand t...

Страница 9: ...24x20x1 actual dimension must be less than 23 x20 filter can be installed on a B C and D cabinet respectively the cabinet size is the seventh letter of the model number Washable versions are available...

Страница 10: ...22 27 40 1200 7 11 14 19 22 33 45 56 1400 6 10 12 16 19 29 38 48 1600 5 8 10 14 17 25 33 42 1800 5 7 9 12 15 22 30 37 2000 4 7 8 11 13 20 27 33 208 1 60 SUPPLY VOLTAGE TEMP RISE F Table 6 CFM HEAT KI...

Страница 11: ...ckouts on the cabinet sides are used for electrical 208 240 197 253 Nominal Input Minimum Voltage Maximum Voltage ELECTRICAL VOLTAGE Table 7 HIGH VOLTAGE Disconnect ALL power before servicing or insta...

Страница 12: ...ayed LEDs on the PCB as there may be a tolerance difference between displayed and actual measured Maximum Measured CFM Allowed Up Flow Down Flow HZ Flow DV24FECB14 910 870 870 DV36FECC14 1450 1390 139...

Страница 13: ...seconds normal operation resumes and the error message is removed The switch is closed as part of the default factory setting The error will be maintained in the equipment s fault history See Figures...

Страница 14: ...motor is oriented with the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure 15 4 Accessory...

Страница 15: ...tatic electricity i e do not move or shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discharge y...

Страница 16: ...ating mode and airflow demand source For example assume the system is a heat pump matched with an air handler With a call for low stage cooling the heat pump will calculate the system s low stage cool...

Страница 17: ...e installing this unit Power line terminal C from Indoor unit must connect to terminal C on thermostat and power line terminal R from indoor unit must connect to terminal R on thermostat Verify wires...

Страница 18: ...system Check communications wiring data 1 data 2 wires Check wire connections at terminal block Verify air handler installation type non communicating traditional or communicating Check data 1 data 2...

Страница 19: ...rminals TB4 and TB5 if not used After recovering the system EF will still be displayed on the indoor PCB about 30 seconds AUXILIARY CONTACTS OPEN will still be displayed on the thermostat within 45 se...

Страница 20: ...ck the connections and the rotation of the motor Verify the input voltage at the motor Verify ductwork is appropriately sized for system Resize replace ductwork if needed Replace motor 70 E_70 EEV dis...

Страница 21: ...TO MOTOR LOW INDOOR AIRFLOW Minor Error Code without EH mode LOW INDOOR AIRFLOW Major Error Code EH mode only EEV DISCONNECTION DETECTED LIQUID SIDE THERMISTOR ABNORMALITY GAS SIDE THERMISTOR ABNORMA...

Страница 22: ...y DISPLAY The display consists of 2 digits DISPLAY BUTTON LAYOUT The display buttons shown can be used to navigate and select items FAULT CODE HISTORY NAVIGATION This mode will allow the user to see t...

Страница 23: ...more than 2 sec Release Fault Recall between 2 to 5 sec Hold Fault Recall for more than 5 sec Flashing Display First Error Code Last Error Code Press Fault Recall for Error Code Press Fault Recall fo...

Страница 24: ...REEN RX LED INDICATES NETWORK TRAFFIC USE LEARN BUTTON TO RESET NETWORK 7 DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT 8 THE POSITION OF SELECTOR SWITCHES DS1 DS6 INDICATE FACTORY SETTING 9...

Страница 25: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your furn...

Страница 26: ...26 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 27: ...27 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 28: ...ranty protection except that failure by California and Quebec residents to register their product does not diminish their warranty rights For Product Registration please register by following this lin...

Отзывы: