8
|
Piping installation
Installer reference guide
74
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
▪
Domestic hot water tank – Disinfection.
For the disinfection function of the
domestic hot water tank, see
178] and
▪
Hygienic measures.
The installation must be in compliance with the applicable
legislation and may require additional hygienic installation measures.
▪
Recirculation pump.
In accordance with the applicable legislation, it may be
required to connect a recirculation pump in between the hot water end point
and the recirculation connection of the domestic hot water tank.
c
d
a
b
a
Recirculation connection
b
Hot water connection
c
Shower
d
Recirculation pump
8.1.2 Formula to calculate the expansion vessel pre-pressure
The pre-pressure (Pg) of the vessel depends on the installation height difference
(H):
Pg=0.3+(H/10) (bar)
8.1.3 To check the water volume and flow rate
The outdoor unit has an expansion vessel of 7 litre with a factory-set pre-pressure
of 1 bar.
To make sure that the unit operates properly:
▪
You MUST check the minimum and maximum water volume.
▪
You might need to adjust the pre-pressure of the expansion vessel.
Minimum water volume
Check that the total water volume in the installation is higher than the minimum
water volume, the internal water volume of the outdoor unit NOT included:
If…
Then the minimum water volume
is…
Cooling operation
10 l
Heating/defrost operation and…