4
|
Components
Service manual
234
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
INFORMATION
All thermistors have a resistance tolerance of 3%.
Does the measured resistance of the
thermistor match with the
temperature determined resistance?
Action
Yes
Thermistor is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
No
Replace the specific PCB, see
99].
Repair procedures
To remove the external thermistor
1
See the documentation of the specific thermistor for more details.
2
To install the external thermistor, see
To install the external thermistor
1
Install the specific thermistor. See the documentation of the specific
thermistor if needed for more details.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.20 User interface
4.20.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To check the power supply to the remote controller user interface
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the user interface panel from the unit, see
202].
Make sure to keep it connected electrically.
2
Turn ON the power to the unit.
3
Measure the voltage on the connector X1B pins 1-2 on the remote controller
user interface main PCB.
Result:
The measured voltage MUST be 12 V DC.
Does the user interface receive power? Action
Yes
Check if the user interface functions
correctly, see
draft – 31/05/2022 15:53