3-6 TON LOW VOLTAGE WIRING
1. Connect the Low Voltage Harness (Refer to Figure 2).
a. The insulated straight quick connects go to the
phase monitor.
b. Connect Purple wire to Y-OUT.
c. Connect Red wire to Y.
d. Connect Blue wire to C.
e. Unplug the 4 pin safety jumper male plug from the 4
pin safety female plug on the unit.
f. Connect new 4 pin phase monitor male plug into the
4 pin safety female plug on the unit.
g. Connect the 4 pin safety male jumper plug to the 4 pin
phase monitor female plug of the phase monitor.
Figure 3
Control box for 3 to 6 ton units