2

3-6 TON KIT INSTALLATION

WARNING

HIGH VOLTAGE!
Disconnect all power before servicing or installing 

this  unit.  Multiple  power  sources  may  be  present. 

Failure to do so may cause property damage, personal 

injury or death.

General

1.  Disconnect all power to the unit. 
2.  Remove access panel to control box

.

3-6 TON HIGH VOLTAGE WIRING

1.  Refer to Figure 3 for the approximate placement of the 

phase monitor in the control box. 

2.  Using the screws provided in the kit, secure the phase 

monitor to the control box. 

3.  Connect the Power Harness (Refer to Figure 2).

a.  The insulated straight quick connects go to the  

phase monitor. 

b.  Connect Black to L1.
c.  Connect Red to L2.
d.  Connect Orange to L3. 
e.  Connect the opposite end of the harness to the 

corresponding L1, L2, and L3 terminals on the power 

block. 

NOTE:  DBG  MODELS  DO  NOT  HAVE  A  POWER 

BLOCK.  CONNECT  HARNESS  TO  CORRESPONDING 

TERMINALS ON COMPRESSOR CONTACTOR. 

Figure 2

Wiring diagram for all tonnages

Wiring is subject to change. Always refer to the unit wiring diagram and accessory wiring diagram booklet for the most up-to-date wiring.

Содержание DRC

Страница 1: ...ruction Manual Pay special attention to all safety warnings Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking ...

Страница 2: ...rovided in the kit secure the phase monitor to the control box 3 Connect the Power Harness Refer to Figure 2 a The insulated straight quick connects go to the phase monitor b Connect Black to L1 c Connect Red to L2 d Connect Orange to L3 e Connect the opposite end of the harness to the corresponding L1 L2 and L3 terminals on the power block NOTE DBG MODELS DO NOT HAVE A POWER BLOCK CONNECT HARNESS...

Страница 3: ...T c Connect Red wire to Y d Connect Blue wire to C e Unplug the 4 pin safety jumper male plug from the 4 pin safety female plug on the unit f Connect new 4 pin phase monitor male plug into the 4 pin safety female plug on the unit g Connect the 4 pin safety male jumper plug to the 4 pin phase monitor female plug of the phase monitor Figure 3 Control box for 3 to 6 ton units ...

Страница 4: ...ersonal injury or death General 1 Disconnect all power to the unit 2 Remove access panel to control box 7 5 12 5 HIGH VOLTAGE WIRING 1 Refer to Figure 4 for the approximate placement of the phase monitor in the control box 2 Using the screws provided in the kit secure the phase monitor to the control box 3 Connect the Power Harness Refer to Figure 2 a The insulated straight quick connects go to th...

Страница 5: ...T c Connect Red wire to Y d Connect Blue wire to C e Unplug the 4 pin safety jumper male plug from the 4 pin safety female plug on the unit f Connect new 4 pin phase monitor male plug into the 4 pin safety female plug on the unit g Connect the 4 pin safety male jumper plug to the 4 pin phase monitor female plug of the phase monitor Figure 4 Control box for 7 5 12 5 ton units ...

Страница 6: ...6 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 7: ...7 THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 8: ...m on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page 8 Our continuing commitment to quality products may mean a change in specifications without notice 2019 2020 19001 Kermier Rd Waller TX 77484 www daikincomfort com ...

Отзывы: