background image

11

Nameplate Voltage - 

That voltage assigned to a piece of 

equipment for the purpose of designating its voltage class 

and for the purpose of defining the minimum and maximum 

voltage at which the equipment will operate.

Utilization Voltage - 

The voltage of the line terminals 

of the equipment at which the equipment must give fully 

satisfactory performance. Once it is established that supply 

voltage will be maintained within the utilization range under 

all system conditions, check and calculate if an unbalanced 

condition exists between phases. Calculate percent voltage 

unbalance as follows: 

AIR FLOW ADJUSTMENTS

When the final adjustments are complete, the current 

draw of the motor should be checked and compared to 

the full load current rating of the motor. The amperage 

must not exceed the service factor stamped on the motor 

nameplate. 

If an economizer is installed, check the unit operating 

balance with the economizer at full outside air and at 

minimum outside air.

High stage airflow setting to be between 300 and 500 

CFM per ton, see Table below. For models with electric 

heat the total airflow must not be less than that required 

for operation of the electric heaters. See Appendix D for 

minimum airflow for specific electric heaters. 

NOTE: Never run CFM below 300 CFM per ton, 

evaporator freezing or poor unit performance is 

possible.

Model

Minimum

Nominal Maximum

DP16HM60

1500

1850

2500

High Stage Airflow Setting, CFM 

(without electric heat) 

EEM - Standard Static Drive Motor

Adjust the CFM for the unit by changing the position of 

the low voltage leads on the terminal block TB1. Refer to 

Appendix A for blower performance at each speed tap  

NOTE: If more than one lead is energized 

simultaneously, the motor will run at the higher 

speed.

Fan speed for G (Fan), Y1 (Low Cool) and W1 (Low Heat) 

are fixed setting on TB1/T1 and cannot be moved.

Purple wire Y2 (High Cool) and Brown wire W2 (High Heat) 

are connected to TB1/T2. These wires can be moved 

together or separately and placed on any unoccupied 

terminal T3-T5.

Note: for proper operation Y2 and W2 should have a higher 

speed setting than the G, Y1 and W1 speed setting.

If Electric Heater kit is installed use the red wire provided 

with the literature kit to jumper terminal TB1/W1 to an 

unoccupied speed tap that satisfies the minimum airflow 

required for the heater kit. This must be a different tap 

than Y2 is connected to. Refer to Appendix D for minimum 

required airflow for electric heaters.

Note: On Heat Pump units, the Yellow (YL) wire 

from relay BR1 to TB1/T2 must always be moved 

to the same terminal location as the Brown (BR) 

wire after adjustments are made, to ensure 

proper blower speed during defrost operation. 

Refrigeration System Checks

This unit is equipped with  thermal expansion  valves. 

Ensure the hold-down bolts on the compressor are secure 

and have not vibrated loose during shipment.  Check 

that the vibration grommets have been installed and 

visually check all piping for damage and leaks and repair 

if necessary.  The entire system has been factory charged 

and tested, making it unnecessary to field charge.  Factory 

refrigerant charge is shown on the unit’s nameplate.

To confirm charge levels or, if a leak occurs and charge 

needs to be added to the system, it is recommended to 

evacuate the system and recharge refrigerant to the unit’s 

nameplate specifications.  This unit has been rated in the 

cooling mode at the AHRI rated conditions of:  indoor (80°F 

db/67°F wb) and outdoor (95°F db).  While operating at this 

condition, the superheat should range from 9°F to 11°F for 

each refrigeration circuit measured at the suction service 

port located near the compressor.

Start-Up Procedure and Checklist

Begin with power turned off at all disconnects.

Air Conditioning  Start-Up Procedure

1.  Ensure the thermostat is set to OFF and Fan is set 

to Auto. 

2.  Inspect all registers and set them to the normal open 

position.

3.  Turn on the electrical supply at the disconnect.
4.  Turn the fan switch to the “ON” position. The blower 

should operate after a 7 second delay. 

5. 

Turn the fan switch to “Auto” position. The blower 

should stop after a 60 second delay. 

6.  Set the thermostat to Cool mode and slowly 

lower the cooling temperature until the unit starts. 

The compressor, blower and fan should now be 

operating. Allow the unit to run 10 minutes, make 

sure cool air is being supplied by the unit.

Содержание DP16H M Series

Страница 1: ...19 Wiring Diagrams 20 Start UpChecklist 21 Only personnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equip...

Страница 2: ...ence CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use...

Страница 3: ...where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or r...

Страница 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Страница 5: ...ES Unit Clearances In situations that have multiple units a 36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenanc...

Страница 6: ...the following bullet points must be observed when installing the unit Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be attached to the unit wit...

Страница 7: ...present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not tamper with factory wiring The intera...

Страница 8: ...vided for this purpose Do not use the ground lug for connecting a neutral conductor Connect power wiring to the electrical power block located within the main control box Control Box control box Conne...

Страница 9: ...g thermostat sub base NOTE Refer to unit wiring diagrams for thermostat or remote sensor connections CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit through a wall may be installed...

Страница 10: ...must first be performed in accordance with this manual Damage or repairs due to failure to comply with these requirements are not covered under the warranty After the machines are used for temporary h...

Страница 11: ...r speed setting than the G Y1 and W1 speed setting If Electric Heater kit is installed use the red wire provided with the literature kit to jumper terminal TB1 W1 to an unoccupied speed tap that satis...

Страница 12: ...unning with the reversing valve in the deenergized heating position After giving the unit time to settle out make sure the unit is supplying heated air Note If the outdoor ambient is above 80 F the un...

Страница 13: ...to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45 F It is also a good practice to provide sufficient supplementary heat to handle the entire h...

Страница 14: ...ficiency or equipment damage due to dust and lint build up on internal parts never operate unit without an air filter installed in the return air system Every application may require a different frequ...

Страница 15: ...15 Wiring Example Electric Heat Wiring Example...

Страница 16: ...0 0 8 1960 1045 0 86 0 2 2189 902 0 81 0 2 2234 960 0 86 0 4 2119 943 0 84 0 4 2162 1003 0 90 0 6 2059 979 0 88 0 6 2101 1042 0 93 0 8 2012 1009 0 90 0 8 2053 1073 0 96 0 2 2254 923 0 88 0 2 2300 982...

Страница 17: ...5 7 2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 6 9 1 0 3 3 5 Direct Drive Standard Static 1 DP16HM60 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83...

Страница 18: ...RB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal du...

Страница 19: ...MODEL NUMBER DP16HM60 kW MINIMUM SCFM AIR FLOW FOR ELECTRIC HEAT 2500 MAXIMUM SCFM HEATER KIT MODEL NUMBER NOMENCLATURE E H S 15 1 2 3 4 5 6 7 Electric Heater Heater Type X Staged S SCR modulating Vol...

Страница 20: ...E INSTALLED NOTES 4 3 2 1 5 6 BLACK BLUE BLUE WITH PINK STRIPE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW YELLOW WITH PINK STRIPE BK BL BL PK BR GR GY OR PK PU RD TN WH YL YL PK HIGH VOL...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 24: ...o the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process an...

Отзывы: