background image

- 8 - 

All  installation  and  management  activities 
must be carried out by qualified personnel. 

Refer  to  the  specific  wiring  diagram  and 
electrical component manual are attached 

with  the  product  before  electrical 
installation.  Site  contractor  shall  do 
termination  at  site  for  wiring  connection 

between  components  that  located  at 
different  AHU  sections  and  delivered 

separately. 

 

IMPORTANT 

MAKE  SURE  ALL  THE  ELECTRIC 

POWER 

DISCONNECT 

AND 

SECURE 

FROM 

SWITCH 

ON 

BEFORE 

DOING 

WIRING 

CONNECTION  

 
5.7.1 Motor Connection 

 

The  electric  supply  to  the  motor  must 
correspond  to  the  rated  voltage  stated  in 
motor  nameplate  and  be  in  conformance 

with  the  National  and  Local  Electric  Code 
and  Regulations.  Motor  supplied  able  to 

operate  within  10%  tolerance  from  the 
nameplate  voltage.  Motor  connection 
details  are  contained  in  the  cover  of  the 

motor terminal box.  (See Figure 22). The 
fan section metal frame must be grounded. 

Suitable  electrical  protection  isolator 
should  be  installed  to  protect  the  motor 

and other electrical equipment. 
Flexible conduit must be used when wiring 
up  fan  motors  to  allow  the  fan  motor  to 

move  freely  on  its  anti-vibration  mounts. 
Cables  passing  through  panels  must  be 

made with gland or grommet.  
For  inverter  control,  refer  to  the  VFD 
manual for wire size and requirements.  

 

 

 

 

 

 

Figure 22 – 3 phases motor connection diagram 

 
5.7.2 Motor Cabling 

 

Motor  wiring  must  go  downward  from 

motor 

terminal 

box 

to 

prevent 

condensation  water  flowing  into  motor 

and lead to a failure. (See Figure 23) 

 

 

Figure 23 

 Motor Cabling 

 

5.8 Drive Belt & Sheave 

 

Improper  sheave  alignment  and  belt 

tension  can  cause  excessive  vibration, 
premature  failure  of  belts  and  bearings. 

See  Figure  24  for  correct  motor  sheave 
and fan sheave alignment. 

Tensioning of the drive belt is achieved by 
moving  the  motor  in  relation  to  the  fan 
(See Figure 25). When inserting new belts, 

do  not  force  belts  over  grooves,  Loosen 
the  adjusting  screw  at  motor  base  until 

belt  can  slide  smoothly  over  the  grooves. 
When all belts are in position, proceed  to 
adjust  belt  tension  using  the  adjusting 

screw and nuts on the motor base. 
Use  recognized  belt  tension  gauge  to 

check  the  belt  tension  by  apply  a  force 
large  enough  at  the  center  of  the  belt  to 

deflect  the  belt  by  16mm  per  meter  (See 
Figure  26).  The  deflection  force  for  any 
belt  should  be  within  the  minimum  and 
maximum force shown in table 1. Readjust 
the  tension  to  maximum  value  when  it 

drops  to  min.  value.  The  deflection  force 
of  factory  setting  is  based  on  “Initial 
Fitting”, re-tensioning as “Retension” after 

the unit has run for 24 hours. 

 

WARNING 

OVER  TENSION  TOWARD  DRIVE 

BELT  WILL  CAUSE  PREMATURE 

FAILURE  OF  BELT  AND  BEARING 

DAMAGE. 

Содержание DM AHU

Страница 1: ...LATION OPERATION MAINTENANCE VER O AHU01 DEC20 15 The design and construction are subject to change without any notice for future improvement MODELS DM AHU DS AHU AHUR VRV AHU Double Skin Modular Air...

Страница 2: ...rtificate which is determined by International National or Local Codes and Regulation Place of service should be equipped with the necessary protective equipment which provide safe maintenance 1 4 Uni...

Страница 3: ...truck 4 Storage For external storage prior to installation the units must be protected from dust rain constant sun exposure and rodents Although covered in shrink wrapped plastic sheeting this is not...

Страница 4: ...carefully assembled to desired unit arrangement The air handling units are design to use section joint brackets to combine two sections Section joints for cabinet and base frame are shown in Figure 5...

Страница 5: ...on joint WARNING CABINET SECTION JOINTS ARE NOT INTENDED FOR LIFTING PURPOSE AND PULLING CABINET FROM A DISTANCE TO JOIN SECTION TOGETHER When the cabinets are penta post to penta post arrangement or...

Страница 6: ...hipped out from factory See Figure 15 Figure 14 Restrained Spring Isolator Figure 15 Removing of U Shaped Plate 5 5 Arrangement VRV AHU Control box and expansion valve kit are installed on the air han...

Страница 7: ...joints or flexible fittings are to be provided in all piping connections particularly those adjacent to heating source to absorb expansion and contraction strains Failure to comply will result in dama...

Страница 8: ...valve and not to a common header When two or more coils are connected to a common suction line never place the bulb on the common line Thermostatic expansion valve is to be equipped with external equa...

Страница 9: ...r control refer to the VFD manual for wire size and requirements Figure 22 3 phases motor connection diagram 5 7 2 Motor Cabling Motor wiring must go downward from motor terminal box to prevent conden...

Страница 10: ...he diameter of smaller pulley Table 2 Adjusted Pitch Diameter Model VPT100Z1 VPT120A1 A2 VPT139A1 A2 VPT156A1 A2 VPT177A1 A2 VPT178B2 Max Pitch mm 96 114 4 133 4 150 4 171 4 171 Min Pitch mm 82 9 96 1...

Страница 11: ...ee Table 2 Figure 27 When the required diameter is obtained adjustable flange is locked by tighten the four clamp screws To get the same diameter in the two grooves of pulleys screw the two mobile fla...

Страница 12: ...out Notes 1 Elbows should not be closer than 2 1 2 times the Duct Equivalent Diameter Refer to Formula 1 2 Dampers should be placed at least fan diameters downstream of the fan discharge Formula 1 Duc...

Страница 13: ...ther For DX coils it is advisable that the refrigerant is to be pumped into the condenser If this is not possible refrigerant shall be purged out WARNING DO NOT HEAT ANY PART ON DX COIL IF REFRIGERANT...

Страница 14: ...20mm 6 1 5 Coils Check the pipe work to coil is correctly connected and the fins are free from foreign matter or damage Check that the condensate drain is trap Ensure good sealing of silicon around th...

Страница 15: ...or cap screw are in secure position CAUTION HIGH AIR TEMPERATURE IN FAN SECTION CAN CAUSE MOTOR OVERHEAT AND DAMAGE ON DRAW THROUGH AIR HANDLERS ADJUST THE DISCHARGE AIR TEMPERATURE OF THE HEATING SE...

Страница 16: ...ling heating efficiency Dry cleaning is done by using a powerful vacuum cleaner on the dust accumulated side If coil is very dirty coils need to be removed for wet cleaning by trained personnel Ensure...

Страница 17: ...IR VELOCITY SHOULD NOT BE LOWER THAN 2 0 m s 7 7 Heat Wheel Heat Pipe The unit should be maintained in line with the manufacturer recommendation Please refer installation and maintenance manual for de...

Страница 18: ...not evenly supported on foundation j Fan assembly s tolerance is out of range a Consult manufacturer b Remove transport bracket c Check pulley alignment d Re tension belts e Replace vibration isolato...

Страница 19: ...he heat wheel baffle top 8 Assembled back the remaining panels 9 2 AHU Water Quality Water quality requirements Water softening treatment must be given in advance to prevent scaling in the heat exchan...

Страница 20: ...Yes No 5 Correct incoming voltage that supplied to motor L1 L2 __________ L2 L3 __________ L3 L1 __________ 6 Rotate fan wheel whether it can rotate freely and without abnormal noise Answer Yes No 7 A...

Страница 21: ...Are the AHU sections joined with section joint properly Answer Yes No 4 Are the joining between AHU sections sealed properly Answer Yes No Start Up Checking 1 Is fan rotated in correct direction Answe...

Отзывы: