9

4-1/2"

47-9/16"

7-1/2"

4-1/16 DIA.

POWER THRU

THE CURB

RETURN

19-3/8

31-3/8

LOW VOLTAGE

ENTRANCE

HIGH VOLTAGE ENTRANCE

(REMOVE PLUG)

electrical entrance and thru curb

(bottom view of unit) 

Low Voltage Control Wiring 

1.  A 24V thermostat must be installed for unit operation 

unless the unit is equipped with factory installed 

DDC control.

2. 

Locate thermostat or remote sensor in the 

conditioned space where it will sense average 

temperature. Do not locate the device where it may 

be directly exposed to supply air, sunlight or other 

sources of heat. Follow installation instructions 

packaged with the thermostat.

3.  Use #18 AWG wire for 24V control wiring runs not 

exceeding 75 feet. Use #16 AWG wire for 24V 

control wiring runs not exceeding 125 feet. Use #14 

AWG wire for 24V control wiring runs not exceeding 

200 feet. Low voltage wiring may be National 

Electrical Code (NEC) Class 2 where permitted by 

local codes.

4.  Route thermostat wires from sub-base terminals 

to the unit. Control wiring should enter through the 

condenser panel opening or through curb indicated 

in “Electrical Entrance” figure. Connect thermostat 

and any accessory wiring to low voltage terminal 

block TB1 in the main control box.

NOTE:  Field-supplied conduit may need to be 

installed depending on unit/curb configuration. 

Use #18 AWG solid conductor wire whenever 

connecting thermostat wires to terminals on 

sub-base. DO NOT use larger than #18 AWG wire. 

A transition to #18 AWG wire may be required 

before entering thermostat sub-base.

 

NOTE: Refer to unit wiring diagrams for 

thermostat or remote sensor connections.

CIRCULATING AIR AND FILTERS

Ductwork

The supply duct from the unit through a wall may be 

installed without clearance. However, minimum unit 

clearances must be maintained (see “Clearances” section). 

The supply duct should be provided with an access panel 

large enough to inspect the air chamber downstream of 

the heat exchanger. A cover should be tightly attached to 

prevent air leaks.

Ductwork dimensions are shown in the roof curb 

installation manual.

If desired, supply and return duct connections to the unit 

may be made with flexible connections to reduce possible 

unit operating sound transmission.

CONDENSATE DRAIN CONNECTION

Condensate Drain Connection

A 3/4” female NPT drain connection is supplied on the 

end of the unit and bottom of the drain pan for condensate 

piping. An external trap must be installed for proper 

condensate drainage. Hand tighten drain fitting to the drain 

connection.

DRAIN

CONNEC

TI

ON

UN

IT

2" MINIMUM

FLEX

IBLE

TU

BING-HOSE

OR PIPE

3" MINIMUM

A POSI

TIVE

 LIQUID

SEAL IS REQUIRED

drain connection 

Install condensate drain trap as shown. Use 3/4” drain line 

and fittings or larger. Do not operate without trap. 

Horizontal Drain 

Drainage of condensate directly onto the roof may be 

acceptable; refer to local code. It is recommended that a 

small drip pad of either stone, mortar, wood or metal be 

provided to prevent any possible damage to the roof. 

Vertical Drain

To use the bottom drain connection, remove the drain plug 

from the bottom connection and install it in the horizontal 

connection.

Содержание DBC0363B Series

Страница 1: ...t specified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting to install...

Страница 2: ...ce CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use a...

Страница 3: ...ld also where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any co...

Страница 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Страница 5: ...ntenance and proper unit operation A clearance of 48 is recommended on all sides of the unit to facilitate possible parts replacement to allow service access and to insure proper ventilation and conde...

Страница 6: ...to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit...

Страница 7: ...MUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE All line voltage connections must be made through weatherproof fittings All exterior power supply and ground wiring must be in approved weatherproo...

Страница 8: ...f unit due to operation on improper line voltage or with excessive phase unbalance constitutes product abuse and is not covered by the warranty It may cause severe damage to the unit s electrical comp...

Страница 9: ...may be required before entering thermostat sub base NOTE Refer to unit wiring diagrams for thermostat or remote sensor connections CIRCULATING AIR AND FILTERS Ductwork The supply duct from the unit t...

Страница 10: ...d for temporary heating or cooling inspect the coils fans and motors for unacceptable levels of construction dust and dirt and install new filters Contractor Responsibility The installing contractor m...

Страница 11: ...it is best to have a variable pitched motor sheave for the purpose of airflow balancing but once the balance has been achieved fixed sheaves maintain alignment and minimize vibration more effectively...

Страница 12: ...ck that the compressor is operating correctly The scroll compressors in these units MUST operate in the proper rotation To ensure the compressors are operating in the correct direction check the compr...

Страница 13: ...e by redirecting refrigerant flow through the refrigerant circuit external to the compressor This is accomplished by the reversing valve Hot discharge vapor from the compressor is directed to the indo...

Страница 14: ...ilters should be cleaned or replaced These few steps will help to keep the product up time to a maximum The Service section that follows should help in identifying problems if the unit does not operat...

Страница 15: ...STATIC BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 7 1481 1020 0 57 0 8 1370 1020 0 53 0 9 1434 1080 0 62 1247 102...

Страница 16: ...250 950 0 42 989 885 0 30 DBC036 C HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 8 1539 1020 0 59 0 9 1...

Страница 17: ...FM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 1996 1200 1 05 1872 1135 0 88 1741 1075 0 74 0 7 1922 1200 1 01 1790 1135 0 84 1650 1075 0 70 0 8 1985 1265 1 17 1845 1200 0 97 1703 1135...

Страница 18: ...HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 1895 1075 0 81 0 7 1958 1135 0 93 1802 1075 0 76 0 8 18...

Страница 19: ...BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2237 1245 1 27 2072 1175 1 03 0 7 2333 1315 1 48 2164 1245 1 23 1990 1175 0 99 0...

Страница 20: ...65 DBC060 C HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2394 1245 1 37 2239 1175 1 12 0 7 2320 1245...

Страница 21: ...175 1 05 1900 1110 0 86 DBC072 S HIGH STATIC BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2630 1385 1 88 2492 1315...

Страница 22: ...1110 0 84 DBC072 S HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2655 1385 1 90 2520 1315 1 62 2369 1...

Страница 23: ...5 0 26 DBH036 C HIGH STATIC BELT DRIVE DOWNSHOT ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 8 1587 1020 0 61 0 9 1456 1020 0 56 1 0 151...

Страница 24: ...0 35 Note VL34 and AK61 pulleys used on standard static unit DBH036 C HIGH STATIC BELT DRIVE HORIZONTAL ESP In H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP C...

Страница 25: ...O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2003 1075 0 85 0 7 1898 1075 0 81 0 8 1936 1135 0 91 1788 1075 0 76 0 9 1979 1200 1 05 1833 1135 0...

Страница 26: ...RNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 1885 1075 0 80 0 7 1955 1135 0 92 1791 1075 0 76 0 8 1865 1135 0 88 1691 1075 0 72 0 9 1948 1200 1 03 1...

Страница 27: ...H2 O TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2397 1310 1 53 2278 1245 1 31 2145 1180 1 10 2003 1115 0 92 0 7 2334 1310 1 48 2208 1245 1 26 2...

Страница 28: ...TURNS OPEN 0 1 2 3 4 5 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 6 2421 1310 1 55 2297 1245 1 32 2161 1180 1 11 2016 1115 0 92 0 7 2357 1310 1 50 2227 1245 1 27 2083 11...

Страница 29: ...7 4 17 4 25 25 9 6 8 7 27 0 26 1 35 35 1 7 1 5 19 1 18 9 25 25 9 6 8 7 1 7 1 5 28 7 27 6 35 35 EH B 3S05 3 76 5 00 10 4 12 0 17 4 19 3 25 25 9 6 8 7 29 3 30 2 35 35 1 7 1 5 19 4 21 2 25 25 9 6 8 7 1 7...

Страница 30: ...30 9 6 8 7 30 8 29 9 40 40 1 7 1 5 22 9 22 7 30 30 9 6 8 7 1 7 1 5 32 5 31 4 40 40 EH B 3S05 3 76 5 00 10 4 12 0 21 2 21 2 30 30 9 6 8 7 30 8 30 2 40 40 1 7 1 5 22 9 22 7 30 30 9 6 8 7 1 7 1 5 32 5 3...

Страница 31: ...7 1 5 55 0 62 0 60 70 9 6 8 7 1 7 1 5 67 0 72 9 70 80 EH B 3S20 15 0 19 9 41 5 47 9 57 9 65 8 60 70 9 6 8 7 69 9 76 7 70 80 1 7 1 5 60 0 67 7 60 70 9 6 8 7 1 7 1 5 72 0 78 6 80 80 DBC0484B 460 3 60 1...

Страница 32: ...7B 575 3 60 1 4 36 33 1 0 25 0 55 Belt Drive Standard Static 1 5 2 3 8 3 15 3 5 11 8 15 0 6 8 9 15 3 5 0 6 12 4 15 EH B 7S05 5 4 81 8 89 15 3 5 13 3 15 0 6 9 64 15 3 5 0 6 14 15 EH B 7S10 10 9 62 14 9...

Страница 33: ...76 5 00 10 4 12 0 25 1 25 1 40 40 9 6 8 7 34 7 33 8 50 45 1 7 1 5 26 8 26 6 40 40 9 6 8 7 1 7 1 5 36 4 35 3 50 45 EH B 3S10 7 51 10 0 20 8 24 1 30 1 34 1 40 40 9 6 8 7 42 1 44 9 50 45 1 7 1 5 32 2 35...

Страница 34: ...5 55 0 62 0 60 70 9 6 8 7 1 7 1 5 67 0 72 9 70 80 EH B 3S20 15 0 19 9 41 5 47 9 57 9 65 8 60 70 9 6 8 7 69 9 76 7 70 80 1 7 1 5 60 0 67 7 60 70 9 6 8 7 1 7 1 5 72 0 78 6 80 80 DBC0604B 460 3 60 1 7 0...

Страница 35: ...575 3 60 1 5 13 39 5 1 0 33 0 67 Belt Drive Standard Static 1 1 2 8 28 15 3 5 11 8 15 0 6 8 88 15 3 5 0 6 12 4 15 EH B 7S05 5 4 81 8 28 15 3 5 11 9 15 0 6 8 88 15 3 5 0 6 12 6 15 EH B 7S10 10 9 62 13...

Страница 36: ...1 5 31 7 31 5 45 45 9 6 8 7 1 7 1 5 41 3 40 2 50 50 EH B 3S10 7 51 10 0 20 8 24 1 33 6 37 6 45 45 9 6 8 7 45 6 48 4 50 50 1 7 1 5 35 7 39 4 45 45 9 6 8 7 1 7 1 5 47 7 50 3 50 60 EH B 3S15 11 3 15 0 3...

Страница 37: ...6 8 7 71 4 78 2 80 80 1 7 1 5 61 5 69 2 70 70 9 6 8 7 1 7 1 5 73 5 80 1 80 90 EH B 3S30 21 6 28 8 60 0 69 3 82 6 94 1 90 100 9 6 8 7 94 6 105 100 110 1 7 1 5 84 7 96 0 90 100 9 6 8 7 1 7 1 5 96 7 107...

Страница 38: ...0 DBC0727S 575 3 60 1 6 35 55 3 1 0 33 0 67 2 speed Belt Drive High Static 2 2 4 11 15 3 5 14 5 20 0 6 11 6 15 3 5 0 6 15 1 20 EH B 7S05 5 4 81 11 15 3 5 14 5 20 0 6 11 6 15 3 5 0 6 15 1 20 EH B 7S10...

Страница 39: ...45 EH B 3S10 7 51 10 0 20 8 24 1 43 5 47 5 45 50 9 6 8 7 53 1 56 2 60 60 1 7 1 5 45 2 49 0 50 50 9 6 8 7 1 7 1 5 54 8 57 7 60 60 EH B 3S15 11 3 15 0 31 3 36 1 56 5 62 5 60 70 9 6 8 7 66 1 71 2 70 80...

Страница 40: ...H0367B 575 3 60 1 3 78 36 5 1 0 17 0 39 Belt Drive Standard Static 1 5 2 3 7 42 15 3 5 10 9 15 0 6 8 02 15 3 5 0 6 11 5 15 EH B 7S05 5 4 81 13 4 15 3 5 16 9 20 0 6 14 15 3 5 0 6 17 5 20 EH B 7S10 10 9...

Страница 41: ...37 5 43 3 68 1 75 4 70 80 9 6 8 7 77 7 84 1 80 90 1 7 1 5 69 8 76 9 70 80 9 6 8 7 1 7 1 5 79 4 85 6 80 90 EH B 3S20 15 0 19 9 41 5 47 9 73 1 81 1 80 90 9 6 8 7 82 7 89 8 90 90 1 7 1 5 74 8 82 6 80 90...

Страница 42: ...3 29 3 30 0 5 25 5 30 4 3 0 5 29 8 30 EH B 4S15 15 18 32 6 35 4 3 36 9 40 0 5 33 1 35 4 3 0 5 37 4 40 EH B 4S18 18 21 7 37 1 40 4 3 41 4 45 0 5 37 6 40 4 3 0 5 41 9 45 EH B 4S20 20 24 1 40 1 45 4 3 44...

Страница 43: ...3 5 23 8 25 0 6 20 9 25 3 5 0 6 24 4 25 EH B 7S15 15 14 4 26 3 30 3 5 29 8 30 0 6 26 9 30 3 5 0 6 30 4 35 EH B 7S18 18 17 3 29 9 30 3 5 33 4 35 0 6 30 5 35 3 5 0 6 34 35 EH B 7S20 20 19 2 32 4 35 3 5...

Страница 44: ...7 5 43 3 72 3 79 5 80 80 9 6 8 7 81 9 88 2 90 90 1 7 1 5 74 0 81 0 80 90 9 6 8 7 1 7 1 5 83 6 89 7 90 90 EH B 3S20 15 0 19 9 41 5 47 9 77 2 85 2 80 90 9 6 8 7 86 8 93 9 90 100 1 7 1 5 78 9 86 7 80 90...

Страница 45: ...4 3 30 7 35 0 5 26 9 30 4 3 0 5 31 2 35 EH B 4S15 15 18 34 35 4 3 38 3 40 0 5 34 5 35 4 3 0 5 38 8 40 EH B 4S18 18 21 7 38 5 40 4 3 42 8 45 0 5 39 40 4 3 0 5 43 3 45 EH B 4S20 20 24 1 41 5 45 4 3 45...

Страница 46: ...4 25 0 6 21 1 25 3 5 0 6 24 6 25 EH B 7S15 15 14 4 26 6 30 3 5 30 1 35 0 6 27 2 30 3 5 0 6 30 7 35 EH B 7S18 18 17 3 30 2 35 3 5 33 7 35 0 6 30 8 35 3 5 0 6 34 3 35 EH B 7S20 20 19 2 32 6 35 3 5 36 1...

Страница 47: ...THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal duct covers 48 5 16 74 A...

Страница 48: ...975 X X X DBC048 1300 X X X X X DBC060 1625 X X X X X DBC072 1950 X X X X X X DBH036 975 X X X DBH048 1300 X X X X X DBH060 1625 X X X X X Note Adjust the pulley setting as needed to achieve the mini...

Страница 49: ...NSOR PB POWER DISTRIBUTION BLOCK PLF FEMALE PLUG CONNECTOR PLM MALE PLUG CONNECTOR TB TERMINAL BLOCK TR TRANSFORMER REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL AT LEAST 105 C...

Страница 50: ...E PU BR BK PU BR BK RD OR BK RD OR BK RD YL L2 208 230 460 575V 3PH 60Hz FB1 F1 F1 F1 5 BK PU BK PLF PLM CM BK BK RD OR POWER AND CONTROLS WIRING DIAGRAM DBC036 060 3 PHASE 1 SPD BELT DRIVE 2 1 2 1 GR...

Страница 51: ...P FUSE BLOCKS 1 2 3 ARE OPTIONAL IF OPTIONAL SAFETY EQUIPMENT SUCH AS A PHASE MONITOR FLOAT SWITCH OR SMOKE DETECTOR IS INSTALLED UNPLUG JUMPER PLUG AND PLUG IN SAFETY DEVICE IF MULTIPLE SAFETIES ARE...

Страница 52: ...52...

Страница 53: ...53...

Страница 54: ...2020 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincomf...

Отзывы: