Three Phase Models Only

Control Voltage Check

Close the disconnect switch to energize control 

transformer. Check primary and secondary (24V) of control 

transformer. 

AIR FLOW ADJUSTMENTS

NOTE: For 2 Speed Models, airflow adjustments 

must be made on high speed, i.e., 2nd stage cooling 

or in heat mode.

The drive on the supply fan is typically set in the middle of 

the RPM range. The drive motor sheave pitch diameter is 

field adjustable for the required airflow. Upon completion 

of the air flow balancing, we recommend replacing the 

variable pitched motor sheave with a properly-sized fixed 

sheave. A matching fixed sheave will provide longer belt 

and bearing life and vibration free operation. Initially, it 

is best to have a variable pitched motor sheave for the 

purpose of airflow balancing, but once the balance has 

been achieved, fixed sheaves maintain alignment and 

minimize vibration more effectively. Refer to the following 

“Drive Adjustments” section.

When the final adjustments are complete, the current 

draw of the motor should be checked and compared to 

the full load current rating of the motor. The amperage 

must not exceed the service factor stamped on the motor 

nameplate. 

If an economizer is installed, check the unit operating 

balance with the economizer at full outside air and at 

minimum outside air.  Upon completion of the air flow 

balancing, we recommend replacing the variable pitched 

motor sheave with a properly-sized fixed sheave. A 

matching fixed sheave will provide longer belt and bearing 

life and vibration free operation. Initially, it is best to have 

a variable pitched motor sheave for the purpose of airflow 

balancing, but once the balance has been achieved, fixed 

sheaves maintain alignment and minimize vibration more 

effectively.

NOTE: Never run high stage CFM below 300 

CFM per ton, evaporator freezing or poor unit 

performance is possible.

Evaporator Fan Rotation Check

Check that fan rotates clockwise when viewed from the 

drive side of unit and in accordance with rotation arrow 

shown on blower housing. If it does not, reverse any two 

incoming power cables at Single Point Power Block. In this 

case, repeat bearing check.

Do not attempt to change load side wiring. Internal wiring 

assures all motors and compressors will rotate in correct 

direction once evaporator fan motor rotation check has 

been made.

Electrical Input Check

Make preliminary check of evaporator fan ampere draw 

and verify that motor nameplate amps are not exceeded. A 

final check of amp draw should be made upon completion 

of air balancing of the duct system.

Set Evaporator Fan Rpm

Actual RPM’s must be set and verified with a tachometer 

or strobe light. Refer to Appendex A for basic unit fan 

RPM.  Refer also to “Airflow” section of this manual. With 

disconnect switch open, disconnect thermostat wires 

from terminals Y and W. This will prevent heating and 

mechanical cooling from coming on. Place a jumper wire 

across terminals R and G at TB1 terminal block. Close 

disconnect switch; evaporator fan motor will operate so 

RPM can be checked.

BELT DRIVE MODELS ONLY

Refer to “Motor Sheave Adjustments” section.

Bearing Check

Prior to energizing any fans, check and make sure that all 

setscrews are tight so that bearings are properly secured 

to shafts.

Tension and Alignment Adjustment

Correct belt tension is very important to the life of your belt. 

Too loose a belt will shorten its life; too tight, premature 

motor and bearing failure will occur. Check your belt 

drive for adequate “run-in” belt tension by measuring the 

force required to deflect the belt at the midpoint of the 

span length. Belt tension force can be measured using 

a belt tension gauge, available through most belt drive 

manufacturers.

SPAN LENGTH  t

*DEFLECTION

FORCE

  h

C

   d

H

D

Содержание DBC Series

Страница 1: ...erty damage arising from improper service or service procedures If you service this unit you assume responsibility for any injury or property damage which may result In addition in jurisdictions that...

Страница 2: ...B Electrical Data 27 Appendix C Unit Dimensions 40 Appendix D Min Max Airflow 41 Wiring Diagram 42 Start Up Checklist 44 To The Installer Before installing this unit please read this manual to familia...

Страница 3: ...cepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation The mechanical installation of the package...

Страница 4: ...tly on wood floors or on Class A Class B or Class C roof covering material To avoid possible personal injury a safe flat surface for service personnel should be provided As indicated on the unit data...

Страница 5: ...rk must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimeter curbs include duct connection frames to be assemble...

Страница 6: ...nit base frame from fork lift damage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit Your unit ma...

Страница 7: ...65 302 Corner Weight B 359 347 344 401 Corner Weight C 267 300 317 312 Corner Weight D 302 311 290 379 Unit Shipping Weight 1227 1287 1291 1394 Unit Operating Weight 1152 1212 1216 1314 X inches 43 44...

Страница 8: ...ree wire The unit is factory wired for the voltage shown on the unit s data plate NOTE If supply voltage is 208V lead on primary of transformer s must be moved from the 230V to the 208V tap Refer to w...

Страница 9: ...holes in the unit base must be sealed including those around conduit nuts to prevent water leakage into building All required conduit and fittings are to be field supplied Supply voltage to roof top...

Страница 10: ...connection is supplied on the end of the unit and bottom of the drain pan for condensate piping An external trap must be installed for proper condensate drainage Hand tighten drain fitting to the drai...

Страница 11: ...installation instructions All electric power all gas hot water or steam line connections and the condensate drain installation have been made to each unit on the job These main supply lines must be f...

Страница 12: ...run high stage CFM below 300 CFM per ton evaporator freezing or poor unit performance is possible Evaporator Fan Rotation Check Check that fan rotates clockwise when viewed from the drive side of unit...

Страница 13: ...GROOVES 5 Ensure all keys are in place and the set screws tight before starting drive Recheck set screws and belt tension after 24 hours service NOTE Future adjustments should be made by loosening th...

Страница 14: ...ly checked so postpone the test to another day when conditions are more suitable but DO NOT FAIL TO TEST If the outdoor ambient is low and the unit operates properly on the heating cycle you may check...

Страница 15: ...dels with V or S in the 8th position of the model number For 2 speed models the indoor blower will operate on low speed when in Fan Only mode or while in first stage Cooling mode Unit will operate on...

Страница 16: ...also act as check valves to allow for the reverse of refrigerant flow When the heat pump is on the heating cycle the outdoor coil is functioning as an evaporator The temperature of the refrigerant in...

Страница 17: ...rently have sharp edges and it is necessary that the installer and service personnel exercise caution Preventive maintenance is the best way to avoid unnecessary expense and inconvenience Have this sy...

Страница 18: ...allow air entering the indoor coil to drop below 65 F Air below this temperature will cause low discharge pressure thus low suction pressure and excessive defrost cycling resulting in low heating outp...

Страница 19: ...1 51 2481 1003 1 28 DBC090 S HIGH STATIC HORIZONTAL1 ESP In H2O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VL40 and AK84H re...

Страница 20: ...44 1 8 3732 1096 2 32 2781 1053 1 51 ESP In H2O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VL40 and AK84H respectively or eq...

Страница 21: ...O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VL40 and AK74H respectively or equivalents DBC120 V STANDARD STATIC DOWNSHOT1 CF...

Страница 22: ...5348 1144 4 26 4928 1106 3 77 4389 1068 3 19 3762 1030 2 22 ESP In H2O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VP44 and AK...

Страница 23: ...P CFM RPM BHP CFM RPM BHP 0 1 3532 620 1 05 3276 600 0 78 0 2 3601 663 1 13 3264 620 0 93 2947 600 0 67 0 3 3654 707 1 18 3323 663 1 00 2955 620 0 81 2617 600 0 57 0 4 3728 748 1 24 3377 707 1 05 3011...

Страница 24: ...2 83 2797 1058 2 10 DBH102 V STANDARD STATIC DOWNSHOT1 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 1 3933 610 1 29 0 2 4039 655 1 46 3658 611 1 20 0 3 4172 693 1 66 3763...

Страница 25: ...DOWNSHOT1 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 1 4836 649 1 73 4463 610 1 41 0 2 4976 692 1 97 4557 650 1 60 4177 610 1 30 0 3 4641 693 1 82 4213 653 1 47 3783 61...

Страница 26: ...2 5963 762 2 57 5529 721 2 24 5102 681 1 69 4625 642 1 43 0 3 5716 762 2 40 5241 721 2 06 4778 681 1 53 4276 642 1 27 0 4 5439 762 2 22 4929 721 1 87 4429 681 1 36 3910 642 1 12 0 5 5581 805 2 90 5131...

Страница 27: ...24 30 1 20 7 25 4 3 1 25 30 27 9 30 4 3 33 3 35 1 29 2 30 4 3 1 34 6 35 50 5 60 4 3 55 9 60 1 51 7 60 4 3 1 57 1 60 73 80 4 3 78 4 80 1 74 3 80 4 3 1 79 7 80 18 3 20 4 3 22 6 25 1 19 3 20 4 3 1 23 6...

Страница 28: ...0 45 9 45 6 50 50 9 6 8 7 3 3 3 0 55 5 54 3 60 60 46 6 52 6 50 60 9 6 8 7 58 6 63 5 60 70 3 3 3 0 50 7 56 4 60 60 9 6 8 7 3 3 3 0 62 7 67 2 70 70 85 7 97 7 90 100 9 6 8 7 97 7 109 100 110 3 3 3 0 89 8...

Страница 29: ...25 1 2 18 5 20 3 5 1 2 22 25 21 25 3 5 25 4 30 1 2 22 5 25 3 5 1 2 26 9 30 39 1 40 3 5 43 5 45 1 2 40 6 45 3 5 1 2 45 45 57 1 60 3 5 61 5 70 1 2 58 6 60 3 5 1 2 63 70 Model Number Electrical Rating C...

Страница 30: ...35 1 24 5 30 4 3 1 28 8 35 27 9 30 4 3 33 3 35 1 29 2 30 4 3 1 34 6 35 50 5 60 4 3 55 9 60 1 51 7 60 4 3 1 57 1 60 73 80 4 3 78 4 80 1 74 3 80 4 3 1 79 7 80 22 1 25 4 3 26 4 30 1 23 1 25 4 3 1 27 4 30...

Страница 31: ...60 6 60 3 70 70 9 6 8 7 3 3 3 0 70 2 69 0 80 80 57 3 57 3 70 70 9 6 8 7 66 9 67 4 80 80 3 3 3 0 60 6 60 3 70 70 9 6 8 7 3 3 3 0 70 2 71 1 80 80 89 6 102 90 110 9 6 8 7 102 112 110 125 3 3 3 0 93 7 10...

Страница 32: ...1 2 23 4 25 3 5 1 2 26 9 30 22 4 25 3 5 26 8 30 1 2 23 9 25 3 5 1 2 28 3 30 40 5 45 3 5 44 8 45 1 2 42 45 3 5 1 2 46 3 50 58 5 60 3 5 62 9 70 1 2 60 70 3 5 1 2 64 4 70 Model Number Electrical Rating...

Страница 33: ...22 2 25 4 3 1 26 5 30 43 8 45 4 3 48 1 50 1 44 8 45 4 3 1 49 1 50 66 3 70 4 3 70 6 80 1 67 3 70 4 3 1 71 6 80 88 9 90 4 3 93 2 100 1 89 9 90 4 3 1 94 2 100 19 8 25 4 3 24 1 30 1 20 8 25 4 3 1 25 1 30...

Страница 34: ...0 48 9 48 6 60 60 9 6 8 7 3 3 3 0 58 5 57 3 60 60 84 7 90 7 90 100 9 6 8 7 94 3 99 4 100 100 3 3 3 0 88 0 93 7 90 100 9 6 8 7 3 3 3 0 97 6 102 100 110 124 136 125 150 9 6 8 7 133 145 150 150 3 3 3 0...

Страница 35: ...26 5 30 1 2 24 2 25 3 5 1 2 27 7 30 41 45 3 5 44 5 45 1 2 42 2 45 3 5 1 2 45 7 50 59 60 3 5 62 5 70 1 2 60 2 70 3 5 1 2 63 7 70 77 1 80 3 5 80 6 90 1 2 78 3 80 3 5 1 2 81 8 90 Model Number Electrical...

Страница 36: ...1 24 4 30 4 3 1 28 7 30 45 9 50 4 3 50 2 60 1 46 9 50 4 3 1 51 2 60 68 5 70 4 3 72 8 80 1 69 5 70 4 3 1 73 8 80 91 100 4 3 95 3 100 1 92 100 4 3 1 96 3 100 22 25 4 3 26 3 30 1 23 25 4 3 1 27 3 30 44...

Страница 37: ...3 5 60 5 70 1 2 58 2 60 3 5 1 2 61 7 70 75 1 80 3 5 78 6 80 1 2 76 3 80 3 5 1 2 79 8 80 EH B 7M46 45 43 3 DBH1207S 575 3 60 2 5 1 39 5 2 0 33 3 5 2 speed Belt Drive High Static 3 3 5 EH B 7M16 15 14...

Страница 38: ...5 9 6 8 7 3 3 3 0 156 167 175 175 182 200 200 225 9 6 8 7 192 209 200 225 3 3 3 0 186 203 200 225 9 6 8 7 3 3 3 0 195 212 200 225 33 2 40 4 3 37 5 45 1 34 2 40 4 3 1 38 5 45 55 7 60 4 3 60 70 1 56 7 6...

Страница 39: ...30 40 8 45 3 5 44 3 45 1 2 42 45 3 5 1 2 45 5 50 58 9 60 3 5 62 4 70 1 2 60 1 70 3 5 1 2 63 6 70 76 9 80 3 5 80 4 90 1 2 78 1 80 3 5 1 2 81 6 90 Optional Powered Convienience Optional Power Exhaust Po...

Страница 40: ...d on the flanges around the duct openings and the gasket is APPENDIX C UNIT DIMENSIONS Horizontal Discharge Vertical Discharge Bottom of Unit NOTE For horizontal discharge remove supply and return duc...

Страница 41: ...903S 2400 X X X X X X DBC0904S 2400 X X X X X X DBC0907S 2400 X X X X X X DBC1023S 2750 X X X X X X DBC1024S 2750 X X X X X X DBC1027S 2750 X X X X X X DBC1203S 3250 X X X X X X DBC1204S 3250 X X X X...

Страница 42: ...ITH PINK STRIPE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED TN TAN WH WHITE YL YELLOW YL PK YELLOW WITH PINK STRIPE POWER AND CONTROLS WIRING DIAGRAM DBH 090 120 LINE VOLTAGE 208 230...

Страница 43: ...G IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT...

Страница 44: ...44...

Страница 45: ...45...

Страница 46: ...46 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 47: ...47 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 48: ...2020 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincom...

Отзывы: