background image

4 Installation

Installation manual

12

D035A1/4AA + D035A4AA

Wall-mounted condensing boiler

3P469346-5E – 2017.06

4.6

Underfloor heating requirements

Underfloor  heating  systems  apparently  require  higher  flow  rate  and
lower  ΔT.  This  boiler  can  be  connected  to  an  underfloor  heating
system without use of a second pump and low loss header because
of  its  high  pump  capacity.  Direct  connection  is  possible  when  the
system is well designed and pressure loss is low enough.

When  the  boiler  is  connected  to  underfloor  heating  installation,  the
maximum  central  heating  set  temperature  must  be  limited  to  50°C
and the pump operation temperature difference must be adjusted to
10 Kelvin in the service settings menu. To change this setting, refer
to the servicing instructions.

WARNING

Make  sure  parameter  changes  explained  above  are  done
to avoid discomfort of the user.

4.7

Residual pump lift graph

The  residual  pump  lift  graph  shows  the  amount  of  pump  lift  (mbar)
that remains for the central heating circuit.

0

0

100

200

300

400

500

600

700

800

200

400

600

800

1000

1200

1400

1600

1800

A (mbar)

B (l/h)

A

Residual pump lift (mbar)

B

Flow (l/h)

4.8

Connections

4.8.1

Piping connections

Piping connections of models D2CND028A1AA,
D2CND028A4AA, D2CND035A1AA and D2CND035A4AA

Below, find the piping connections of the unit.

A

B

D

E

H

C

F

G

A

Central heating return connection, 3/4"

B

Domestic cold water inlet connection, 1/2"

C

Condensate trap discharge

D

Domestic hot water outlet connection, 1/2"

E

Central heating supply connection, 3/4"

F

Gas inlet connection, 3/4"

G

Filling valve (for D2CND028A1AA and D2CND035A1AA)

H

Safety valve discharge

B

F

D

a

b

E

A

Valve

Strainer
Tee connection

Double check valve + filling hose
Disconnector

a

Isolation valve on domestic hot water supply pipe is
tentative.

b

External filling group used with model D2CND028A4AA
and D2CND035A4AA. Use a disconnector or a double
check valve according to local regulations.

Isolation  valves  and  strainers  should  be  used  just  before  the
appliance piping inlet as shown in figure above.

Ensure that necessary gaskets are placed.

Note: 

Optional  Daikin  connection  kit  can  be  used  and  it  is

recommended to use it.

Piping connections of models D2TND028A4AA and
D2TND035A4AA

Below, find the piping connections of the unit.

B

D

C

A

E

G

F

A

Central heating return connection, 3/4"

B

Storage tank return connection, 3/4"

C

Condensate trap discharge

D

Storage tank supply connection, 3/4"

E

Central heating supply connection, 3/4"

F

Gas inlet connection, 3/4"

G

Safety valve discharge

Содержание D2TND028A4AA

Страница 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler D2CND028A1AA D2CND028A4AA D2CND035A1AA D2CND035A4AA D2TND028A4AA D2TND035A4AA...

Страница 2: ...tatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumie...

Страница 3: ...must be appropriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for...

Страница 4: ...ce must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user and his her surroundings The manufacturer i...

Страница 5: ...allation from frost damages It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperatu...

Страница 6: ...he unit Installation manual 6 D2CND028 035A1 4AA D2TND028 035A4AA Wall mounted condensing boiler 3P469346 5E 2017 06 Bottom view of models D2TND028A4AA and D2TND035A4AA 90 30 100 103 30 125 7 72 132 1...

Страница 7: ...s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Internal filling valve included in model D2CN...

Страница 8: ...19 0 59 3 32 0 59 4 19 LPG G31 Consumption min max m h 0 2 1 09 0 2 1 38 0 2 1 09 0 2 1 38 Combustion products mass flow rate min max G20 g s 2 2 12 35 2 2 15 47 2 2 12 35 2 2 15 47 Combustion produc...

Страница 9: ...oilers 37 C and for other heaters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions expl...

Страница 10: ...o the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas forma...

Страница 11: ...13 m 1 5 bar h h System water height m p System charge pressure bar According to the graph below there is no need to install an additional expansion vessel for the systems with a water volume in the...

Страница 12: ...1 Piping connections Piping connections of models D2CND028A1AA D2CND028A4AA D2CND035A1AA and D2CND035A4AA Below find the piping connections of the unit A B D E H C F G A Central heating return connec...

Страница 13: ...ious damages in installation or boiler or cause discomfort of the user The manufacturer is not responsible for any damage that may occur this way The installation of the boiler should be in compliance...

Страница 14: ...or fire A main switch or other means for disconnection having a contact separation in all poles providing full disconnection under overvoltage category III shall be installed in the fixed wiring Be s...

Страница 15: ...9346 5E 2017 06 PG9 PG7 PG7 PG9 Holes on the bottom sheet that are reserved for cable glands are covered with insulation material The insulation material must be bored if glands are to be used Note Un...

Страница 16: ...Wall mounted condensing boiler 3P469346 5E 2017 06 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Models D2CND028A1AA D2CND028A...

Страница 17: ...ip Card Ext2 X10 Personal computer production interface Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal stri...

Страница 18: ...lations The boiler must be installed so that the terminal is exposed to external air Position of the terminal must allow the free passage of air across it at all times Pluming may occur at the flue te...

Страница 19: ...length L is measured from lip of the elbow to end of the flue terminal L a L Flue duct length a Distance of outer lip of terminal to outer wall a 50 mm Note Flue ducts are inserted 45 mm into elbows...

Страница 20: ...Elbow 60 100 90 Optional e 90 elbow 60 100 f 45 elbow 60 100 g Tee 60 100 with measurement point h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Maximum allowable length of the ue duct up to commo...

Страница 21: ...mm 1 0 m Equivalent length of options 90 elbow 80 mm 2 0 m Subtract equivalent length value of bends from the allowable flue length value Note The air intake length is 3 metres In case of longer air...

Страница 22: ...cular and rough 140 18 2 53 5 Allowable flue length for C93x DN 80 Flex circular and rough 130 11 6 34 1 DN 80 Flex circular and rough 120 4 4 13 0 DN 80 Flex square and rough 140 23 8 69 9 DN 80 Flex...

Страница 23: ...100 EKFGP4661 45 elbow 80 125 EKFGP4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKF...

Страница 24: ...disconnector or a double check valve according to local regulations After all system connections are performed with care perform the following steps 1 Connect the appliance to the main power supply Du...

Страница 25: ...ount the front cover connect the unit to the main power supply 4 10 2 To modify settings for gas conversion 1 Enter the menu section from the user interface Select service settings by using the left d...

Страница 26: ...nutes even if there is demand First 0 2 minutes The electronic gas adaptive system calibrates itself Next 8 10 minutes The boiler performs the low water temperature function You can skip this function...

Страница 27: ...plain the function of the boiler error mode Emphasise that if an error is indicated refer to Error codes in the operation manual Inform the user about frost protection function and advise never to cut...

Страница 28: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469346 5E 2017 06...

Отзывы: