3 Operation

Operation manual

8

D035A1/4AA + D035A4AA

Wall-mounted condensing boiler

3P469438-5D – 2017.06

#

Description (short)

Unit

A02

Actual domestic hot water temperature

°C

A03

Actual flue temperature

°C

A04

(a)

Actual outdoor temperature (if outdoor
sensor is connected, otherwise "--")

°C

A05

(a)

Actual solar temperature (if solar sensor is
connected, otherwise "--")

°C

A06

Actual water pressure

bar

A07

Actual domestic hot water flow rate

l/min

A08

(b)

Current set point of burner capacity

%

A09

(b)

Actual capacity of boiler in relation to
nominal capacity

%

A10

(c)

Actual phase of the burner

A11

Status of On-Off room thermostat,
indicate heat demand (HC1)

A12

Actual error code of boiler

A13

Actual fan speed (rpm/100)

rpm

A14

Current setpoint of boiler pump

%

(a)

Not applicable if the sensor is not connected.

(b)

Maximum value for central heating = 91%
Maximum value for domestic hot water = 100%

(c)

A10=0: Standby mode, burner is not active
A10=1: Start-up, preparation to ignition
A10=2: Ignition and flame stabilisation phase
A10=3: Release control (burner is on, operation phase)
A10=4: Post-purge phase

To use the info menu

1

Press  the  "Enter"  button  when  the 

  icon  is  displayed  on  the

menu level 1 screen.

2

Select an index between 00 and 14 with the right dial. Press the
"Back" button to return to menu level 1 screen.

a

a

Index

3.5.3

User settings menu

User settings menu: Parameters (short)

The  user  settings  menu  ( )  comprises  parameters  that  can  be
changed  and  adjusted  by  users.  You  can  read  out  and  adjust  the
parameters according to your preferences.

NOTICE

If you are not sure about the function of the parameter, do
not change it. Contact your service agent.

#

Description

Unit Default Range

U00

Summer-winter switch over
temperature

°C

20

10~30

U01

Heating slope

0

0~40

U02

Central heating ECO mode

0

0~1

U03

Domestic hot water comfort
mode

0

0~1

U04

Domestic hot water set value

°C

50

35~60

U05

Set value for the room
thermostat at day mode

°C

21

10~30

U06

Set value for the room
thermostat at reduced mode

°C

18

10~30

#

Description

Unit Default Range

U07

Set value for the flow
temperature at day mode

°C

50

35~80

U08

Set value for the flow
temperature at reduced mode

°C

35

35~80

U09

Domestic hot water comfort
mode user record dependency

1

1, 2 or

24

U10

Room temperature setpoint
used by Daikin Opentherm
room thermostat during night

°C

18

10~30

User settings menu: Parameters (detailed)

#

Description

U00

When using outdoor sensor, above this parameter
value of outside temperature, the boiler senses the
season as summer and does not activate central
heating although there is demand. Summer-winter
switching has a hysteresis of ±1ºC.

i.e: When this parameter is adjusted to 20ºC, the boiler
switches to summer mode at 21ºC and switches back
to winter mode at 19ºC.

U01

This value is used when only outside sensor is
connected to the boiler (No Opentherm room
thermostat connection). The parameter heating slope is
important to adapt the weather compensation to the
individual heating system, the building and the thermal
insulation. 

The heating slope can be adjusted from 0

to 40. The heating slope needs to be increased to
increase the boiler central heating set temperature.
Colder regions require a higher heating slope value.

Note: 

To activate weather compensation, the heating

slope value must be higher than "5".

U02

Enabling / disabling central heating ECO mode.

1 = enabled, 0 = disabled

U03

Enabling / disabling domestic hot water comfort mode.

1 = enabled, 0 = disabled

U04

Domestic hot water set value (Same function that can
be done via the right dial when domestic hot water
mode is enabled).

U05

When On-Off room thermostat and outdoor sensor are
both connected, this parameter value is the virtual room
temperature setpoint when there is a heat demand.

U06

When On-Off room thermostat and outdoor sensor are
both connected, this parameter value is the virtual room
temperature setpoint when there is no heat demand.

Note: 

For this parameter value to be active, reducing

mode has to be enabled by your service agent,
otherwise central heating mode will not be activated
when there is no heat demand.

U07

When On-Off room thermostat is connected and
outdoor sensor is not connected, this parameter value
is the central heating water temperature setpoint when
there is a heat demand.

U08

When On-Off Room thermostat is connected and
outdoor sensor is not connected, this parameter value
is the central heating water temperature setpoint when
there is not a heat demand.

Note: 

For this parameter value to be active, reducing

mode has to be enabled by your service agent,
otherwise central heating mode will not be activated
when there is no het demand.

Содержание D2CND028A1AA

Страница 1: ...Operation manual Wall mounted condensing boiler English Operation manual Wall mounted condensing boiler D2CND028A1AA D2CND028A4AA D2CND035A1AA D2CND035A4AA D2TND028A4AA D2TND035A4AA...

Страница 2: ...low Model Type Domestic hot water supply Filling loop D2CND028A1AA D2CND028 Instantaneous Internal D2CND028A4AA D2CND028 Instantaneous External Model Type Domestic hot water supply Filling loop D2CND0...

Страница 3: ...and adhesives in the vicinity of the unit These substances can cause corrosion even in the flue system DANGER Do not damage or remove any seals on components Only qualified persons are allowed to alt...

Страница 4: ...s indicator The status indicator gives first level feedback on the operation mode and status of the boiler Status Description Standby When there is no heat demand the status indicator shows this with...

Страница 5: ...on is shown on the home screen The icon blinks if domestic hot water operation is active Operation mode Description Winter mode Both domestic hot water operation mode and central heating operation mod...

Страница 6: ...ft dial Increasing or decreasing the setpoint value reflects to the central heating water temperature and the room temperature respectively The and icons are shown on the screen when central heating o...

Страница 7: ...dling When an error occurs the normal behaviour of the user interface is interrupted and the status of the status indicator is affected However be aware that not all errors have the same effect on the...

Страница 8: ...dependency 1 1 2 or 24 U10 Room temperature setpoint used by Daikin Opentherm room thermostat during night C 18 10 30 User settings menu Parameters detailed Description U00 When using outdoor sensor...

Страница 9: ...lvent free soap CAUTION Sprays solvents or cleaning agents containing chlorine can damage the exterior the fittings or the control unit Do not use them for cleaning purposes 5 Energy saving tips Opera...

Страница 10: ...to restart If problem repeats contact your service agent E1 67 Missing calibration Perform reset If problem repeats contact your service agent E1 68 Ion base value is outside the factory limits or sav...

Страница 11: ...4AA Wall mounted condensing boiler 3P469438 5D 2017 06 Problem Solution UA 68 BCC is not compatible with PCB BCC ID Contact your service agent UA 69 BCC is not compatible with PCB firmware Contact you...

Страница 12: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469438 5D 2017 06...

Отзывы: