Special Control
Si18-525B
118
Function
3.4
Pump-down Residual Operation
When activating compressor, if the liquid refrigerant remains in the heat-exchanger, the liquid
enters into the compressor and dilutes oil therein resulting in decrease of lubricity.
Therefore, the pump-down residual operation is performed to collect the refrigerant in the heat-
exchanger when the compressor is down.
3.4.1 Pump-down Residual Operation in Cooling Operation
3.4.2 Pump-down Residual Operation in Heating Operation
3.5
Restart Standby
Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the
refrigerant system.
Actuator
Outdoor unit operation
Compressor
124 Hz
Outdoor unit fan
Fan control
Four way valve
OFF
Main electronic expansion valve (EV1)
2000 pls
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP)
OFF
Receiver gas discharging valve (SVG)
ON
→
OFF
Ending conditions
•
30 sec.
•
Pe<0.5 MPa
•
Td>110
°
C
or
Actuator
Outdoor unit operation
Compressor
52
→
124 Hz
Outdoor unit fan
STEP8
Four way valve
ON
Main electronic expansion valve (EV1)
0 pls
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP)
ON
→
OFF
Receiver gas discharging valve (SVG)
ON
→
OFF
Ending conditions
•
3 min.
•
Pe<0.25 MPa
•
Td>110
°
C
or
Actuator
Operation
Remarks
Compressor
OFF
Outdoor unit fan
OFF
Four way valve
Keep former condition.
Main electronic expansion valve (EV1)
0 pls
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP)
OFF
→
ON
Receiver gas discharging valve (SVG)
OFF
Ending conditions
5 min.
Содержание D-Series
Страница 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Страница 33: ...List of Functions Si18 525B 20 List of Functions ...
Страница 34: ...Si18 525B Specifications 21 Part 2 Specifications 1 Specifications 22 1 1 Cooling Only 22 1 2 Heat Pump 42 ...
Страница 71: ...Specifications Si18 525B 58 Specifications ...
Страница 107: ...Printed Circuit Board Connector Wiring Diagram Si18 525B 94 Printed Circuit Board Connector Wiring Diagram ...
Страница 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Страница 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Страница 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Страница 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Страница 443: ...BP Unit Si18 525B 430 Removal Procedure The clamps are to be kept in stock Step Procedure Points Clamps Q0529 ...
Страница 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Страница 475: ...Si18 525B vi Index ...