D-EOMOAH00903-21_01EN - 22 / 37 

6.10.2  Alarm list 

Next table shows all alarm strings that appears on screen when an alarm occurs, with the respective causes and 
solutions list. 

Alarm String 

Description 

Possible causes & solutions 

Outside temp: 

-no sensor 
-over range 
-under range 
-shortd loop 
 

Error condition on the outside 
temperature sensor: 
measured temperature out of 
the allowable range or error 
condition on the sensor. 

Error 

Causes 

Solutions 

no 
sensor 

Sensor not connected 

Check the wiring 
connection of the 
temperature sensor with 
the controller or (if it is 
powered) with the 
electrical power 

over 
range 

Measured value over 
max limit 

If the measured value is 
wrong replace the sensor 

under 
range 

Measured value under 
range 

If the measured value is 
wrong replace the sensor 

shortd 
loop 

The sensor could be 
broken 

Disconnect the 
temperature sensor from 
the controller and 
measure the resistance 
value of the sensor. Refer 
to the datasheet of the 
sensor for the resistance 
nominal value of sensor 

Room temp: 

-no sensor 
-over range 
-under range 
-shortd loop 
 
 

Error condition on the room 
air temperature sensor: 
measured temperature out of 
the allowable range or error 
condition on the sensor. 

Error 

Causes 

Solutions 

no 
sensor 

Sensor not connected 

Check the wiring 
connection of the 
temperature sensor with 
the controller or (if it is 
powered) with the 
electrical power 

over 
range 

Measured value over 
max limit 

If the measured value is 
wrong replace the sensor 

under 
range 

Measured value under 
range 

If the measured value is 
wrong replace the sensor 

shortd 
loop 

The sensor could be 
broken 

Disconnect the 
temperature sensor from 
the controller and 
measure the resistance 
value of the sensor. Refer 
to the datasheet of the 
sensor for the nominal 
resistance. 

Return temp: 

-no sensor 
-over range 
-under range 
-shortd loop 

Error condition on the return 
air temperature sensor: 
measured temperature out of 
the allowable range or error 
condition on the sensor. 

Error 

Causes 

Solutions 

no 
sensor 

Sensor not connected 

Check the wiring 
connection of the 
temperature sensor with 
the controller or (if it is 
powered) with the 
electrical power 

over 
range 

Measured value over 
max limit 

If the measured value is 
wrong replace the sensor 

Содержание D-AHU Professional AH-ERQ-U

Страница 1: ...Digital AHU ADK D STREAM Revision 01 Date 06 2021 Supersede D EOMOAH00903 21EN OPERATING MANUAL D EOMOAH00903 21_01EN...

Страница 2: ...13 6 7 Setpoints 14 6 8 I O Overview 17 6 9 Time Scheduler 18 6 10 Alarm handling 21 6 11 About Unit 28 7 Modbus nodes diagnostic and alarms 30 7 1 Node HardwareErr 30 7 2 Node CommErr 30 7 3 Node In...

Страница 3: ...unication state is the BLUE led D EOMOAH00903 21EN 0 March 2021 First edition 1 2 Notice 2014 Daikin Applied Europe Cecchina Roma All rights reserved throughout the world The following are trademarks...

Страница 4: ...some other way All handling that affects the prescribed disconnection of the protective extra low voltage AC 24 V must be avoided Disconnect the supply voltage before opening the apparatus cabinet Ne...

Страница 5: ...g 1 AH ERQ U The AH ERQ U is connected with the Daikin ERQ condensing unit 2 AH W U The AH Water U is connected with an external device that provides hot water or cold water used in a water heat excha...

Страница 6: ...d Red Hardware Error Flashing Green BSP startup phase The controller needs time for starting Flashing Yellow Application not loaded Flashing Yellow Red Fail safe mode in case that the BSP upgrade was...

Страница 7: ...e starts according to the sequence shown in the figure above The same sequence describes also the devices turn off order by following the opposite direction ensuring that the upper devices are directl...

Страница 8: ...ath Main Menu Ctrl Source Main Menu item Value Description Control Source Local BMS Local a HMI unit control managed directly from the controller interface or automatically via time scheduler Refer to...

Страница 9: ...below HMI Path Main Menu Actual Mode Main Menu item Value Description Actual Mode Off On Ventilation Economy Off AHU in Off mode All devices installed on the AHU fans cooling heating coil dampers etc...

Страница 10: ...in alarm state This state is displayed when an alarm has been detected Manual AHU in Test mode The AHU is in this state when Local Switch is set to Test Refer to Local Switch page for more details Pa...

Страница 11: ...U Offset if present Winter mode Temperature Heat R U Offset if present Supply Fan Display the actual setpoint value for the supply fan This value is the sum of the basic setpoint plus the offset evalu...

Страница 12: ...HU In this mode all controls are active and setpoints related to temperature regulation and fans control are the normal setpoints Refer to Setpoints page to change normal setpoints Ventilation Switch...

Страница 13: ...he changeover is managed via a Building Management System BMS through BACnet or Modbus protocol communication For additional information on summer winter changeover logics and settings refer to Summer...

Страница 14: ...the AHU Current State Summer Winter Display the current state in which the AHU is operating Auto mode settings Tmp Used Return Room Outside Select the temperature monitored to determine the Summer Win...

Страница 15: ...e control selected Band Temp Economy 10 Heat C Deadzone temperature setpoint in Economy mode Available only when temperature regulation with deadzone control selected Pursuit 10 40 C Pursuit mode temp...

Страница 16: ...nt in case of defrost of the condensing unit ERQ Available only if fan defrost limitation control enabled Supply filter Warning 1 2 3 4 0 1000 Pa Differential Pressure threshold for Warning on supply...

Страница 17: ...Digital inputs can be connected to alarm signals coming from different installed devices in the AHU Fan Damper Pressure Switch Water Pump etc or to external switches Emergency stop Unit enable Analog...

Страница 18: ...r for more details Copy schedule Off On Copy Monday schedule to all weekdays Tuesday Active Passive Active if the present day is Tuesday Refer to Day Scheduler for more details Sunday Active Passive A...

Страница 19: ...ue is set incorrectly i e it is less than the previous the AHU will not work properly and it could be always keep ON or OFF 6 9 2 Calendar exception and Calendar fix off Exception days are defined in...

Страница 20: ...1 2009 is an exception date Start date Mo 00 Every Monday is an exception day Start date Evn 00 The days for the entire month are exception day for each even month February April June August etc Examp...

Страница 21: ...itches to OFF state and controls remain locked until the alarm condition is restored An example of critical alarm is a fan fault 6 10 1 Alarm restore When an alarm is displayed on the controller follo...

Страница 22: ...p no sensor over range under range shortd loop Error condition on the room air temperature sensor measured temperature out of the allowable range or error condition on the sensor Error Causes Solution...

Страница 23: ...nder range If the measured value is wrong replace the sensor shortd loop The sensor could be broken Disconnect the temperature sensor from the controller and measure the resistance value of the sensor...

Страница 24: ...alarm condition Causes Solutions The alarm signal of the water pump is not connected to the controller Check the wiring connection between the input Cooling Heating coil pump alarm of the controller a...

Страница 25: ...larm occurs when the alarm signal from the external condensing unit is active Causes Solutions The alarm signal of the condensing unit is not connected to the controller Check the wiring connection be...

Страница 26: ...Causes Solutions Return fan is far from the set point for a predefined period Check return fan condition Retrn Hum rel under range Return Room air humidity over limit or error condition on the air hu...

Страница 27: ...ify if in the alarm list there is some alarm related to the return temperature sensor and in this case refer to it Supply tmp fire alm Alarm Supply air temperature too high possible presence of fire C...

Страница 28: ...e the DIP switch value refer to the wiring diagram ERQ 1 alarm Alarm Digital input related to the ERQ 1 is closed Causes Solutions Error on the ERQ Check the operating manual of the ERQ ERQ 2 alarm Al...

Страница 29: ...29 37 Through this section it is possible to Visualize and modify date and time Visualize useful information about software application installed Visualize the actual controller IP address and firmwa...

Страница 30: ...ne from the Modbus communication Notification MT4 LED 5 Yellow Delay 10sec Reset type Automatic Countermeasure Node could be offline because of a Hardware Error or because is not powered on Led alive...

Страница 31: ...tErr RtrnTmpSenf RtrnFanPressSenf In order to associate Node InOutErr with each sensor fault it is necessary to browse the I O section in the HMI or examine the wiring diagram 7 6 2 Node CommErr behav...

Страница 32: ...on the temperature setpoint Enabling and disabling of the Occupancy function Set date and time View actual fan speed 8 1 Buttons Overview 1 On Off AHU state changeover 2 Home Return button Enabling Di...

Страница 33: ...s On when the AHU is in Auto mode The actual AHU state and the relative icon On Off Ventilation or Economy are based on Time Scheduler settings Heating Cooling This icon is On when the AHU is in Venti...

Страница 34: ...n screen page without taking any action either press the Home button again or wait for 5 seconds 8 5 Date and time 3 To change the date and time displayed on the main screen follow these steps 1 Press...

Страница 35: ...steps 1 Press the Summer Winter changeover button 2 Navigate through the different available states by pressing or buttons 3 Confirm the change of state by pressing for at least 1 second the Confirm b...

Страница 36: ...it must be sealed on the device side as currents of air in the conduit can affect the sensor reading The admissible ambient conditions must be observed Local installation regulations must be observed...

Страница 37: ...nt and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicit...

Отзывы: