Unit installation
Installer reference guide
29
FTXM20~42+ATXM20~35R2/5V1B + FTXM50~7
ATXM50R2V1B
Daikin room air conditioner
4P518023-8G – 2020.06
Ø16
Ø18
NOTICE
▪
Install the drain hose with a downward slope.
▪
Traps are NOT permitted.
▪
Do NOT put the end of the hose in water.
▪
Drain hose extension.
To extend the drain hose, use a field supplied hose with
inner Ø16 mm. Do NOT forget to use a heat insulation tube on the indoor section
of the extension hose.
a
a
b
c
Ø16
Ø16
a
Drain hose supplied with the indoor unit
b
Heat insulation tube (field supply)
c
Extension drain hose
▪
Rigid polyvinyl chloride pipe.
When connecting a rigid polyvinyl chloride pipe
(nominal Ø13 mm) directly to the drain hose as with embedded piping work, use
a field supplied drain socket (nominal Ø13 mm).
a
b
c
Ø18
a
Drain hose supplied with the indoor unit
b
Drain socket with nominal Ø13 mm (field supply)
c
Rigid polyvinyl chloride pipe (field supply)
▪
Condensation.
Take measures against condensation. Insulate the complete drain
piping in the building.
1
Insert the drain hose in the drain pipe as shown in the following figure, so it
will NOT be pulled out of the drain pipe.
≥50
mm
6.4.2 To connect the piping on right side, right-back, or right-bottom
INFORMATION
The factory default is right-side piping. For left-side piping, remove the piping from
the right side and install it on the left side.