Is the continuity measurement correct? Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
Replace the reactor, see
3.11.2 Repair procedures
To remove the reactor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
100].
2
Open the compressor insulation.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
3
Remove the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
4
Disconnect the connector.
5
Remove the clip and remove the reactor from the compressor.
6
To install the reactor
1
Install the reactor in the correct location and install the clip.
2
Connect the reactor connector.
3
Install the cover of the compressor wire terminals.