English
10
OPERATION MODE SETTINGS
8.
Any one of the following operation modes can be selected for the
fi lter auto cleaning of the self-clean panel.
Operation mode
Description
(1) Scheduled
timer operation
Performs fi lter auto cleaning during the
designated period selected from eight
periods.
(2) 00:00-to-03:00
operation
Performs fi lter auto cleaning during the
factory-set period of time (00:00 to 03:00).
(3) Auto control
operation
Performs fi lter auto cleaning according to the
control reference.
In consultation with the customer, set the desired operation mode
by referring to the instructions on
Filter Auto cleaning
and
Filter
Auto clean setting
in the operation manual for the Self Cleaning
decoration panel.
At the time of delivery, refer to the contents of descriptions (1)
through (3) in the above table and explain the customer when fi lter
auto cleaning will start.
FIELD SETTINGS
9.
Make settings in consultation with the customer according to the
installation and usage conditions of the air conditioner. The
following three settings are possible.
Dust quantity settings.
9-1
Make settings according to the quantity of dust in the room.
Standard quantity of dust (General offi ces)
•
Large quantity of dust (Stores dealing in clothing)
•
Panel indicator (green) On/Off.
9-2
The panel indicator (green) can display the following operating
conditions. Make indicator settings according to the request of the
customer.
Indicator
Operating conditions
Remarks
Green
Lit
Air-conditioning
operation
The indicator is turned off
before shipping.
Flash-
ing
Filter auto cleaning
The red lamp to inform the customer of the time of dust collection
will not be turned off.
Make fi eld settings according to the installation manual of the
remote controller. (Settings in bold cells are made before shipping.)
Setting
item
Mode
No.
FIRST
CODE
NO.
SECOND CODE NO.
01
02
03
04
Dust
quantity
settings
14
(24)
(9)
Standard
quantity of
dust
Large
quantity of
dust
–
–
Panel
indicator
(green)
on/off
14
(24)
(4)
On while in
air-conditioning
operation and
fi lter cleaning
operation.
Possible to
turn on while
in fi lter
cleaning
operation only.
Off while in
air-conditioning
operation and fi lter
cleaning operation.
* Factory settings
–
TEST OPERATION
10.
Perform the test operation of the Self Cleaning decoration panel
after the test operation of the indoor unit is fi nished.
The test operation of the Self Cleaning decoration panel is not
possible while the indoor unit is in operation.
Note
Perform the test operation of the product after referring to “a. Test
items on completion of work”.
Check that the EL. COMPO. BOX lids of the
10-1
indoor unit, outdoor unit, and self-clean
panel, respectively, are closed.
Turn the indoor unit power on.
10-2
The panel will go into initialization operation after the power is
turned on.
Conduct the test operation of the panel two
10-3
minutes after the power is turned on.
Confi rm the cleaning operation of the fi lter with the remote
controller.
Test operation method with remote controller
Stop the operation of the panel if the panel is in air-conditioning
1.
operation.
Continue pressing the Cancel button at least 4 seconds while the
2.
backlight is lit. The local setting menu will appear.
Select
3.
Filter auto clean test
from the local setting menu, and
press the Menu/Enter button.
“
4.
” will appear on the basic screen.
The display will disappear when the test operation is fi nished.
The required test operation time is approximately 10 minutes (in
the case of setting the standard quantity of dust).
1.
2.
Set temperature
28
°C
Cool
Return
Setting
Press and hold
Cancel button for
4 seconds or
longer during
backlight lit.
3.
Return
Setting
Field setting
Outdoor status display
Fan forced operation ON
Main/Sub changeover
Filter element sign OFF
Filter auto clean test
Brush/Filter Sign OFF
1/2
Press Menu/Enter
button.
4.
Set temperature
28
°C
Cool
Return
Setting
“Filter auto cleaning”
will be displayed.
Backlight for LCD
Press any button and the backlight will be lit for approximately
30 seconds.
Perform the operation of buttons while the backlight is lit (except the
On/Off button).
Test items on test operation
Test items
Remedy
Check
result
Is the fi lter rotating?
Check the
connector
connections.
Are the fl aps fi xed horizontally?
Is “
” displayed on the screen of
the remote controller?
The remote controller will display “AH” if the self-clean panel has
*
an error.
Note
After the test operation of the product is fi nished, refer to “b. Test
items before delivery” in the installation manual.
01_EN_3P257556-1.indd 10
01_EN_3P257556-1.indd 10
9/3/2009 4:05:41 PM
9/3/2009 4:05:41 PM