OH08-1
Remote Controller (Wireless Type)
Control Systems
69
2
(Example)
If the time to clean air filter is set to “Filter Contamination-Heavy”, set Mode No. to “10”, FIRST CODE NO.
to “0”, and SECOND CODE NO. to “02”.
NOTE
z
The SECOND CODE NO. is factory set to “01”. However, for the following cases it is set to “02”.
z
Air Flow Direction Range Setting
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are
equal. (For group control, refer to the installation manual attached to the indoor unit for group control.)
Test Operation
z
Perform test operation according to the instructions in the installation manual attached to the indoor
unit.
z
After refrigerant piping, drain piping, and electric wiring, operate according to the table to protect the
unit.
[PRECAUTIONS]
1. Refer to malfunction diagnosis in the installation manual attached to the indoor unit for split types.
2. Refer to malfunction diagnosis in the installation manual attached to the outdoor unit for VRV system
types.
MODE
NO.
FIRST
CODE
NO.
DESCRIPTION OF SETTING
SECOND CODE NO. NOTE)
01
02
03
10
0
Filter Contamination-
Heavy/Light (Setting for
spacing time of display
time to clean air filter)
(Setting for when filter
contamination is heavy,
and spacing time of
display time to clean air
filter is to be halved)
Ultra-long-
life type
light
approx.
10,000
hours
heavy
approx.
5,000 hours
-
Long-life
type
approx.
2,500 hours
approx.
1,250 hours
Standard
type
approx.
200 hours
approx.
100 hours
1
Long-life filter type (Setting of filter
sign indication time)
(Change setting when Ultra-long-life
filter is installed)
Long-life filter
Ultra-long-life filter
-
3
Spacing time of display time to clean
air filter count
(Setting for when the filter sign is not
to be displayed)
Display
Do not display
-
13
0
High ceiling setting (Setting for when
installed in a ceiling higher than 2.7 m)
Normal
High Ceiling 1
High
Ceiling 2
1
Selection of Air Flow Direction
(Setting for when a blocking pad kit
has been installed)
F
T
W
4
Air Flow Direction Range Setting
Upper
Normal
-
Order
Operation
(1)
Open gas side stop valve.
(2)
Open liquid side stop valve.
(3)
Electrify crank case heater for 6 hours. (Not necessary for cooling type units)
(4)
Set to cooling with the remote controller and push
button to start operation.
(5)
Push
button twice and operate in TEST OPERATION.
(6)
Push
button and confirm its operation.
(7)
Push
button and operate normally.
(8)
Confirm its function according to the operation manual.