DS1 SWITCH
SW1 ON (Master controller) – When connecting one
remote controller only or when connecting two remote
controllers one controller must be selected to Master.
(Second controller is optional BRCSZC)
SW1 OFF (Sub controller) - When connecting two
remote controllers one controller must be selected to
Sub controller. (Second controller is optional BRCSZC)
SW2 Must remain in the ON position.
SW3 Must remain in the ON position.
SW4 ON (Start Up Delay Timer OFF)-The indoor fan
will start once the unit initialisation time is completed.
SW4 OFF (Start Up Delay Timer ON)-The indoor fan
will not start until at least 60 seconds has passed.
It is advisable when using spring return zone motors to
set SW4 OFF this will allow at least 60 second for the
zone motor to open before the indoor fan starts.
DS1 SWITCH
SW1 - ON = Master controller
SW1 - OFF = Sub controller
SW2 - No Function
SW3 - No Function
SW4 - ON = Start Up Delay Timer OFF
SW4 - OFF = Start Up Delay Timer ON
12
DS1
1
2
3
4
ON
OFF
Note 6.
Layout 1 (No Common Zone)
It is recommended to set the field set code to “Keep 1
Zone ON” One zone will remain on at all times when the
air conditioning unit is in operation to ensure damage to
the ducting system will not occur by over pressurising.
(1b - 4 - 01)
Layout 2 (Common Zone)
You can set “All Zones OFF” You will be able to
manually switch all the zones off if required.
(1b - 4 - 02)
ZONE 1
ZONE 2
ZONE 1
COMMON
ZONE 2
Duct Configuration
Back of controller
S8
Interface
PCB
Earth post
Earthed shield link
Adapter
How To Connect BRCW902A15 Extension Cable
(Optional Accessories)
DS1 Switch Settings
A two-digit code will flash on the
LCD screen when a fault occurs.
(Brief description of fault codes can
be found on Pg. 13.)
The inspection display will appear
once the TEST/EXIT button is
pressed. The inspection screen will
store the last fault code. To clear
the fault code press the clear
button for 4 seconds or until 00
appears. There are some fault
codes that will clear if the power is
switched OFF and then back ON again.
To enter the test mode press the
TEST/EXIT button twice. During the
test mode the system will be forced
to function according to the mode
set. The compressor will be forced to
operate for 30 minutes.
Fault Mode
Inspection Mode
Test Mode
MODE
FAN
TEMP
ADJUST
BUTTON
TEMP
SHIFT
7 DAY
TIME CLOCK
ON/OFF
TIMER
ENTER
CLEAR
TEST/EXIT
DAY TIME
ZONE1
ZONE2
ZONE3
ZONE4
SEL SENSOR
FIX SENSOR
ZONE5
ZONE6
ZONE7
ZONE8
MODE
FAN
TEMP
ADJUST
BUTTON
TEMP
SHIFT
7 DAY
TIME CLOCK
ON/OFF
TIMER
ENTER
CLEAR
TEST/EXIT
DAY TIME
ZONE1
ZONE2
ZONE3
ZONE4
SEL SENSOR
FIX SENSOR
ZONE5
ZONE6
ZONE7
ZONE8
MODE
FAN
TEMP
ADJUST
BUTTON
TEMP
SHIFT
7 DAY
TIME CLOCK
ON/OFF
TIMER
ENTER
CLEAR
TEST/EXIT
DAY TIME
ZONE1
ZONE2
ZONE3
ZONE4
SEL SENSOR
FIX SENSOR
ZONE5
ZONE6
ZONE7
ZONE8
Layout 1
Layout 2
Содержание BRC230Z4
Страница 2: ...2 ...