background image

12 Starting up the system

Installer and user reference guide

12

BK+S

Wired remote controller

4P513690-1 – 2018.03

11.5

Opening the controller

11.5.1

Precautions when opening the controller

NOTICE

The controller PCB is mounted into the front casing. When
opening the controller, be careful not to damage the PCB.

NOTICE

When the front and rear casing are separated, make sure
the PCB does not come into contact with dust or moisture.

11.5.2

To open the controller

1

Insert  a  flat‑head  screwdriver  into  one  of  the  bottom  closing
mechanisms and slowly twist it.

12

Starting up the system

CAUTION

Before starting up the system, make sure:

▪ The indoor and outdoor unit wiring is completed.

▪ The  switch  box  covers  of  the  indoor  and  outdoor  units

are closed.

The  controller  gets  its  power  from  the  indoor  unit.  It  will  start  up  as
soon as it is connected. For the controller to be operable, therefore
make sure the indoor unit is powered on.

Once  the  controller  is  powered,  it  will  automatically  start  up.  If  it  is
the first and only controller that is connected to the indoor unit, it will
automatically  get  designated  as  master  controller.  For  a  second
controller  to  get  designated  as  slave  controller,  manual  action  is
required.  For  instructions,  see 

"12.2  To  designate  a  controller  as

slave" on page 12

.

12.1

Master and slave controller

a

b

c

d

a

Outdoor unit

b

Indoor unit

c

Master remote controller

d

Slave remote controller

On  the  information  screen,  master/slave  status  is  indicated  by  the
following icons:

Icon

Description

Master

Slave

For more information, see 

"13.4.1 Information screen" on page 13

.

INFORMATION

It is only possible to use a master and a slave controller of
the same type.

INFORMATION

In  case  digital  input  adapter  BRP7A5*  is  part  of  the
system,  it  is  not  possible  to  connect  and  designate  a
second  controller.  Connecting  a  second  controller  when
the  system  already  contains  the  adapter,  will  cause  the
adapter to go in error.

INFORMATION

If  a  slave  controller  does  not  display  the  home  screen  2
minutes after its designation, turn off the power and check
the wiring.

INFORMATION

After  re-designating  a  controller,  the  system  requires  a
power reset.

INFORMATION

The  following  functions  are  not  available  for  slave
controllers:

▪ "Auto" operation mode

▪ Individual airflow direction

▪ Filter auto clean

▪ Setback temperature setpoints

▪ Draught prevention

▪ Duty rotation

12.2

To designate a controller as slave

Prerequisite: 

A master controller is already connected to the indoor

unit.

1

Connect a second controller.

Result: 

It will start up automatically.

2

Wait for a U5 or U8 error to appear on the screen.

3

When  the  U5  or  U8  error  appears,  press 

  and  keep  it

pressed until "2" appears on the screen.

Result: 

The controller is now designated as slave.

Содержание BRC1H81K

Страница 1: ...Installer and user reference guide Wired remote controller English Installer and user reference guide Wired remote controller BRC1H81W BRC1H81K BRC1H81S ...

Страница 2: ...tem 12 12 1 Master and slave controller 12 12 2 To designate a controller as slave 12 13 Operation 13 13 1 Buttons 13 13 2 Screen 13 13 3 Status indicator 13 13 4 Information 13 13 4 1 Information screen 13 13 4 2 Information menu 14 14 Configuration 14 14 1 Installer menu 14 14 1 1 About the installer menu 14 14 1 2 Screen settings 14 14 1 3 Status indicator settings 15 14 1 4 Field settings 15 1...

Страница 3: ...ay or insecticide near the controller NOTICE To clean the controller do NOT use organic solvents such as paint thinner Possible consequence damage electric shock or fire 1 2 For the installer The precautions described in this document cover very important topics follow them carefully INFORMATION This controller is an option and cannot be used standalone Also see the installation and operation manu...

Страница 4: ...ngineering data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required For the user 3 Buttons c b d e a a ON OFF When OFF press to turn ON the system As a result the status indicator e will turn ON too When ON press to turn OFF the system As a result the ...

Страница 5: ...ation Indicates that Rotation mode is active Setback Indicates that the indoor unit is operating under setback conditions Icon Description Ventilation Indicates that a heat reclaim ventilation unit is connected INFORMATION For information on the operation mode and ventilation mode icons see 6 1 Operation mode on page 5 and 6 5 1 Ventilation mode on page 8 respectively Most icons are related to thi...

Страница 6: ...ll automatically switch to defrost operation During defrost operation the indoor unit fan will stop operation and the following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minutes Hot start VRV only During hot start the indoor unit fan will stop operation and the following icon will appear on the home screen INFORMATION When the system is ...

Страница 7: ...te Result The fields become editable 3 Set the date and time Set with and Confirm with Cycle through the menu until all fields are set correctly Result You set the date and the time INFORMATION Confirming the value in a field will automatically bring you to the next field To finish making settings and leave the menu navigate to and confirm the value in the last field 6 4 Airflow 6 4 1 Airflow dire...

Страница 8: ... the fan speed 1 Navigate to the fan speed menu 2 Use and to adjust the fan speed 3 Press to confirm Result The indoor unit changes its fan speed and the controller returns to the home screen 6 5 Ventilation INFORMATION Ventilation settings can ONLY be made for heat reclaim ventilation units 6 5 1 Ventilation mode The heat reclaim ventilation unit can operate in various operation modes Icon Ventil...

Страница 9: ...doka Assistant app is installed and running Prerequisite Your mobile device supports Bluetooth version 4 2 1 Open the Madoka Assistant app and follow the instructions from there 7 Maintenance and service 7 1 Overview Maintenance and service When the system needs to be maintained or serviced consult your dealer When the following indoor unit components are due for maintenance you will be confronted...

Страница 10: ...y consists of the following stages 1 Determining how you want to route the electrical wiring and nipping away a piece of the rear casing accordingly 2 Mounting the rear casing to the wall 3 Connecting the electrical wiring 4 Closing the controller 11 2 Mounting the controller 11 2 1 About mounting the controller Before you can mount the controller you have to determine the wiring routing and accor...

Страница 11: ...T included NOTICE When wiring run the wiring away from the power supply wiring in order to avoid receiving electric noise external noise INFORMATION P1 and P2 have no polarity 11 3 2 To connect the electrical wiring Connect controller terminals P1 P2 to indoor unit terminals P1 P2 From the top P1P2 From the rear P1P2 From the left P1P2 From the bottom P1P2 11 4 Closing the controller 11 4 1 Precau...

Страница 12: ...oller as slave on page 12 12 1 Master and slave controller a b c d a Outdoor unit b Indoor unit c Master remote controller d Slave remote controller On the information screen master slave status is indicated by the following icons Icon Description Master Slave For more information see 13 4 1 Information screen on page 13 INFORMATION It is only possible to use a master and a slave controller of the...

Страница 13: ... information through status icons Standard Detailed a b c 19 a b c a Messages b Active operation mode c Setpoint temperature Home screen mode is set with remote controller field setting R1 7 Home screen For more information see Remote controller field settings on page 19 Backlight The screen backlight has the following states State Description ON For the controller to be operable the screen backli...

Страница 14: ...r instructions on how to enter the information menu see 14 1 Installer menu on page 14 and Information on page 27 14 Configuration 14 1 Installer menu 14 1 1 About the installer menu In the installer menu you can make the following settings Category Icon Settings Screen settings Brightness Contrast Status indicator settings Intensity Category Icon Settings Field settings Indoor unit field settings...

Страница 15: ...ions on how to make field settings see 14 1 4 Field settings on page 15 For an overview of remote controller field settings see Remote controller field settings on page 19 To set status indicator intensity Prerequisite You are in the installer menu 1 Navigate to the status indicator intensity menu 2 Use and to adjust status indicator brightness 3 Press to confirm Result The status indicator adjust...

Страница 16: ...s you do NOT set the unit number The settings will then apply to all indoor units that are part of that group Second level Setting SW A setting is a settable parameter These are the settings you are making In the field settings tables find the available setting numbers in the SW column Value A value is one of a fixed set of values that you can choose for a setting When the value field contains a t...

Страница 17: ...ing component 3 Use and to change the value of that field setting component 4 Press to confirm that value 5 In the first level select to move to the second level 6 In the second level navigate and select in the same way as you did in the first level 7 Select to confirm and activate made settings SW 00 8 At all times select to go back a level ...

Страница 18: ...sor set the increase decrease increments 1 C 0 5 C 13 23 00 High air outlet velocity set in case of high ceiling applications h 2 7 m 2 7 m h 3 m 3 m h 3 5 m 01 Airflow direction set in case an indoor unit is equipped with an option kit that blocks the airflow 4 way flow 3 way flow 2 way flow 03 Airflow function set whether the indoor unit is equipped with a decoration panel at its air outlet Equi...

Страница 19: ... C 10 2 0 C 11 2 5 C 12 3 0 C 6 7 Home screen 0 Detailed 1 Standard 1 8 Backlight no operation timer 0 5 seconds 1 10 seconds 2 20 seconds 0 9 Status indicator faintness 0 0 OFF 1 1 2 2 3 3 4 5 5 7 6 9 7 11 8 13 9 15 10 17 11 20 9 10 Backlight faintness 0 0 OFF 1 1 2 2 3 3 4 4 5 5 5 11 Status indicator mode 0 Normal 1 Hotel setting 1 2 Hotel setting 2 2 13 Bluetooth Low Energy advertising 0 Always...

Страница 20: ...ellaneous settings Group address and Airnet address DIII Group address To control the system with central control equipment you need to set addresses for Groups Group and or Units Group Unit The Group address and Airnet address menu has two levels You define groups and or units in the first level and set or release addresses for those groups and or units in the second Address Description First lev...

Страница 21: ... settings To RELEASE an address that was previously set change to and then apply settings AirNet address To connect the system to the AirNet monitoring and diagnostics system you need to set AirNet addresses for Indoor units I U Outdoor units O U The Group address and AirNet address menu has two levels You define groups and or units in the first level and set and release an address for those group...

Страница 22: ... controller 4P513690 1 2018 03 Address Description First level Indoor unit I U Define the indoor unit for which you want to set an AirNet address Proceed to the next level Outdoor unit O U Define the outdoor unit for which you want to set an AirNet address Proceed to the next level ...

Страница 23: ...gital input adapter see the installation manual of the digital input adapter In case the digital input adapter does not function properly the external input interlock menu is not available in the installer menu In case a centralised controller is additionally part of the system external input interlock is controlled by the centralised controller The digital input adapter is then overruled To make ...

Страница 24: ... setpoint range and setpoint range limitation 22 C Reset Heat SP Default Reset Setting heating setpoint See indoor unit s setpoint range and setpoint range limitation 22 C INFORMATION When the value for a parameter is this means that when the timers expires nothing changes for that parameter and the current active value is kept Window contact logic Window contact B1 Key card contact B2 Time Action...

Страница 25: ... the previous state When the key card contact is opened while the window contact is open the delay timer will start running When the delay timer expires the reset timer will start running When the reset timer expires the previous state is updated to the Default Reset Setting state Example 1 1 You remove the key card Result The indoor unit continues operating normally until the delay timer expires ...

Страница 26: ... Cooling Heating masterhood on page 26 Cooling Heating masterhood corresponds to the following status icon The behaviour of this status icon is according to the following table If a controller displays Then NO status icon The indoor unit connected to that controller is Cooling Heating master a CONSTANT status icon The indoor unit connected to that controller is slave to a Cooling Heating master BL...

Страница 27: ...g masterhood menu 2 Press to release the indoor unit from its masterhood Result The indoor unit is released from its masterhood Result The controllers of all indoor units display a blinking changeover under centralised control icon Information About the information menu In the information menu you can find the following information Information Description SW1 Controller software ID Ver Controller ...

Страница 28: ... Prerequisite You are close to the controller 1 In the app tap the controller that you want to pair with Result The operating system of your mobile device sends out a pairing request Result The controller displays the following screen 2 In the app accept the pairing request 3 On the controller accept the pairing request by pressing Result The app is paired with the controller INFORMATION Once pair...

Страница 29: ...hange the operation mode Change the setpoint Change the fan speed Change the airflow direction Read out notifications Category Control Configuration and advanced operation Make controller and indoor unit settings General Remote controller firmware update Notifications Remote controller settings Master slave status Screen Status indicator Date and time About Remove bonding information Energy saving...

Страница 30: ...date and time menu you send date and time information to the remote controller from the app You can choose to either send the date and time information of your mobile device Synchronise or to manually create and send date and time information INFORMATION If the controller is disconnected from the power for more than 48 hours the date and the time need to be set again INFORMATION The clock will mai...

Страница 31: ...bility of this function depends on the type of indoor unit 15 5 13 Setpoint range Set a limitation to the temperature setpoint range of both Cooling and Heating operation INFORMATION This function cannot be used when the indoor units are controlled by a centralised controller INFORMATION The default setpoint range limits for both Heating and Cooling operation is 16 C 32 C regardless of whether or ...

Страница 32: ...set a timespan for it INFORMATION To use this function it is required that the indoor units are equipped with a self cleaning decoration panel optional accessory 15 5 20 AirNet address Assign AirNet addresses to the indoor and outdoor units this to connect the system to the AirNet monitoring and diagnostics system First select a unit by way of its unit number then assign it an AirNet address 15 5 ...

Страница 33: ...units can remain inactive during normal operation After a set time i e Rotation cycle time the inactive unit will start operation and a previously active unit will become inactive i e duty rotation Because the units only operate alternately the lifespan of the system increases Backup having a backup unit allows for system redundancy If an active unit goes into error Duty rotation makes sure an ina...

Страница 34: ...behave correspondingly 12 Return to the Test operation menu 13 Tap Stop test operation Result The indoor units leave test operation mode Normal operation is possible again 14 Go to 6 Operation on page 5 and confirm if the indoor unit s behave according to the information set out there 15 Check the error history If required solve the cause of the errors and perform the test operation again INFORMAT...

Страница 35: ...Wipe the screen and other surface parts of the controller with a dry cloth 17 Troubleshooting 17 1 Error codes of the indoor unit When the indoor unit is in error the controller will display on the home screen and confront you with an error screen as soon as you try to enter the main menu Solve the cause of the error and press to remove the error screen For an overview of indoor unit error codes a...

Страница 36: ... is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 18 1 Connection diagram 18 1 1 Typical layout P1 P2 P1 P2 18 1 2 Typical layout for group control 0 1 2 P1 P2 P1 P2 P1 P2 P1 P2 Group control master and slave controller 0 1 2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 ...

Страница 37: ...reference guide 37 BRC1H81W K S Wired remote controller 4P513690 1 2018 03 Group control controller digital inputs adapter BRP7A5 0 1 2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 18 1 3 Controller DIII central control equipment F1 F2 P1 P2 P1 P2 F1 F2 ...

Страница 38: ......

Страница 39: ......

Страница 40: ...4P513690 1 2018 03 Copyright 2018 Daikin ...

Отзывы: