14 Configuration

Installer and user reference guide

25

BRK+S
Wired remote controller
4P513689-1A – 2018.03

Key card contact logic

Window contact B1

Key card contact B2

Time

Action

Contact closed (window closed)

Contact closed (key card IN)

▪ —

▪ Delay timer<Time<Reset timer

▪ Time>Reset timer

▪ The unit operates normally.

▪ If  the  reset  timer  has  not

expired,  the  unit  returns  to  the
previous  state  before  opening
the contact.

▪ If  the  reset  timer  has  expired,

the  unit  returns  to  the 

"Default

Reset  Setting"

  (see 

"External

input 

interlock 

settings

overview" on page 23

).

Contact closed (window closed)

Contact open (key card OUT)

Time<Delay timer

Normal indoor unit operation.

Contact closed (window closed)

Contact open (key card OUT)

Time>Delay timer

Unit operation is forced off:

▪ Depending  on  whether  the

Setback  function  is  enabled,
Setback will work or not.

▪ Not  possible  to  turn  on/off  the

unit with the controller's ON/OFF
button.

▪ After  the  delay  timer  has

expired, the reset timer will start
counting.

INFORMATION

▪ The  "previous  state"  can  be  the  on/off  state,  operation

mode, cooling setpoint, and heating setpoint.

▪ When using the contacts, the fan speed as well as the

Setback cooling and heating setpoints can be changed
at any time, without losing changes.

▪ The fan speed is stored independently for the two main

operation  modes  (Heating  and  Cooling).  Separate  fan
speed  settings  are  saved  for  Heating  operation  mode
on  the  one  hand,  and  Cooling,  Dry  and  Fan  only
operation mode on the other hand.

▪ When closing the contact, changes made while the key

card  contact  is  open  and  the  delay  timer  has  not
expired (normal operation) will not be saved.

Combination of window contact and key card contact logic

▪ The  window  contact  has  priority  over  the  delay  timer  and  the

Setback 

functionality 

of 

the 

key 

card 

contact:

When the window contact is opened while the key card contact is
open,  the  delay  timer  will  immediately  expire  if  it  is  still  running,
and  Setback  will  not  work  anymore.  The  reset  timer  will
immediately  start  counting  or  will  not  reset  when  it  was  already
running.

▪ The  reset  timer  functionality  of  the  key  card  contact  has  priority

over  the  window  contact  when  returning  to  the  previous  state:
When the key card contact is opened while the window contact is
open,  the  delay  timer  will  start  running.  When  the  delay  timer
expires  the  reset  timer  will  start  running.  When  the  reset  timer
expires,  the  previous  state  is  updated  to  the  "

Default  Reset

Setting

" state.

Example 1

1

You remove the key card.

Result: 

The  indoor  unit  continues  operating  normally  until  the

delay timer expires.

2

You open the window before the delay timer expires.

Result: 

The indoor unit stops immediately. It is not possible to

turn the unit on or off, the Setback functionality does not work,
the  delay  timer  stops  counting,  and  the  reset  timer  starts
counting.

3

You insert the key card again.

Result: 

An  update  of  the  previous  state  occurs.  The  unit  is

forced  off  and  the  Setback  functionality  is  still  disabled  (see

"Window contact logic" on page 24

).

IF

 the reset timer HAS NOT expired before inserting the key

card, the previous state is the same as the original state
because there was only a change to the original state.

IF

 the reset timer HAS expired before inserting the key card,

the previous state is the "

Default Reset Setting

" state.

4

You close the window.

Result: 

The  unit  reverts  to  the  previous  state.  The  previous

state depends on the expiration of the reset timer.

Example 2

1

You open the window.

Result: 

The unit stops immediately. It is not possible to turn the

unit on or off with the ON/OFF button, the Setback functionality
does not work, and the delay timer does not start counting.

2

You remove the key card.

Result: 

The delay timer starts counting.

3

You close the window again.

Result: 

There is no change in state. It is as if you never opened

the window (Setback will work if enabled).

IF

 the delay timer HAS expired before closing the window, the

reset timer will have started counting. Closing the window has
no influence on the reset timer.

IF

 the delay timer HAS NOT expired before closing the window,

it will expire immediately and the reset timer will start counting.
When the reset timer expires, the previous state is updated to
the "Default Reset Setting" state.

4

You insert the key card again.

Result:

IF

 the reset timer HAS NOT expired before inserting the key

card, the unit returns to the state before the window was
opened (last "on" state);

IF

 the reset timer HAS expired before inserting the key card,

the unit goes to the "Default Reset Setting" state.

Содержание BRC1H519K

Страница 1: ...Installer and user reference guide Wired remote controller English Installer and user reference guide Wired remote controller BRC1H519W BRC1H519K BRC1H519S...

Страница 2: ...m 12 12 1 Master and slave controller 12 12 2 To designate a controller as slave 12 13 Operation 13 13 1 Buttons 13 13 2 Screen 13 13 3 Status indicator 13 13 4 Information 13 13 4 1 Information scree...

Страница 3: ...ay or insecticide near the controller NOTICE To clean the controller do NOT use organic solvents such as paint thinner Possible consequence damage electric shock or fire 1 2 For the installer The prec...

Страница 4: ...ngineering data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authenti...

Страница 5: ...ation Indicates that Rotation mode is active Setback Indicates that the indoor unit is operating under setback conditions Icon Description Ventilation Indicates that a heat reclaim ventilation unit is...

Страница 6: ...t the system will automatically switch to defrost operation During defrost operation the indoor unit fan will stop operation and the following icon will appear on the home screen The system will resum...

Страница 7: ...ycle through the menu until all fields are set correctly Result You set the date and the time INFORMATION Confirming the value in a field will automatically bring you to the next field To finish makin...

Страница 8: ...s to confirm Result The indoor unit changes its fan speed and the controller returns to the home screen 6 5 Ventilation INFORMATION Ventilation settings can ONLY be made for heat reclaim ventilation u...

Страница 9: ...ructions from there 7 Maintenance and service 7 1 Overview Maintenance and service When the system needs to be maintained or serviced consult your dealer When the following indoor unit components are...

Страница 10: ...he controller 11 2 1 About mounting the controller Before you can mount the controller you have to determine the wiring routing and accordingly remove a piece of the controller s rear casing The wirin...

Страница 11: ...1 Precautions when closing the controller CAUTION Never touch the internal parts of the controller CAUTION When closing the controller be careful not to pinch the wiring NOTICE To prevent damage make...

Страница 12: ...1 Information screen on page 13 INFORMATION It is only possible to use a master and a slave controller of the same type INFORMATION In case digital input adapter BRP7A5 is part of the system it is not...

Страница 13: ...ssages b Active operation mode c Setpoint temperature Home screen mode is set with remote controller field setting R1 7 Home screen For more information see Remote controller field settings on page 19...

Страница 14: ...r instructions on how to enter the information menu see 14 1 Installer menu on page 14 and Information on page 27 14 Configuration 14 1 Installer menu 14 1 1 About the installer menu In the installer...

Страница 15: ...ions on how to make field settings see 14 1 4 Field settings on page 15 For an overview of remote controller field settings see Remote controller field settings on page 19 To set status indicator inte...

Страница 16: ...s you do NOT set the unit number The settings will then apply to all indoor units that are part of that group Second level Setting SW A setting is a settable parameter These are the settings you are m...

Страница 17: ...ing component 3 Use and to change the value of that field setting component 4 Press to confirm that value 5 In the first level select to move to the second level 6 In the second level navigate and sel...

Страница 18: ...sor set the increase decrease increments 1 C 0 5 C 13 23 00 High air outlet velocity set in case of high ceiling applications h 2 7 m 2 7 m h 3 m 3 m h 3 5 m 01 Airflow direction set in case an indoor...

Страница 19: ...C 10 2 0 C 11 2 5 C 12 3 0 C 6 7 Home screen 0 Detailed 1 Standard 1 8 Backlight no operation timer 0 5 seconds 1 10 seconds 2 20 seconds 0 9 Status indicator faintness 0 0 OFF 1 1 2 2 3 3 4 5 5 7 6...

Страница 20: ...ellaneous settings Group address and Airnet address DIII Group address To control the system with central control equipment you need to set addresses for Groups Group and or Units Group Unit The Group...

Страница 21: ...settings To RELEASE an address that was previously set change to and then apply settings AirNet address To connect the system to the AirNet monitoring and diagnostics system you need to set AirNet ad...

Страница 22: ...controller 4P513689 1A 2018 03 Address Description First level Indoor unit I U Define the indoor unit for which you want to set an AirNet address Proceed to the next level Outdoor unit O U Define the...

Страница 23: ...gital input adapter see the installation manual of the digital input adapter In case the digital input adapter does not function properly the external input interlock menu is not available in the inst...

Страница 24: ...setpoint range and setpoint range limitation 22 C Reset Heat SP Default Reset Setting heating setpoint See indoor unit s setpoint range and setpoint range limitation 22 C INFORMATION When the value f...

Страница 25: ...the previous state When the key card contact is opened while the window contact is open the delay timer will start running When the delay timer expires the reset timer will start running When the res...

Страница 26: ...Cooling Heating masterhood on page 26 Cooling Heating masterhood corresponds to the following status icon The behaviour of this status icon is according to the following table If a controller display...

Страница 27: ...g masterhood menu 2 Press to release the indoor unit from its masterhood Result The indoor unit is released from its masterhood Result The controllers of all indoor units display a blinking changeover...

Страница 28: ...Prerequisite You are close to the controller 1 In the app tap the controller that you want to pair with Result The operating system of your mobile device sends out a pairing request Result The contro...

Страница 29: ...hange the operation mode Change the setpoint Change the fan speed Change the airflow direction Read out notifications Category Control Configuration and advanced operation Make controller and indoor u...

Страница 30: ...date and time menu you send date and time information to the remote controller from the app You can choose to either send the date and time information of your mobile device Synchronise or to manually...

Страница 31: ...ORMATION The availability of this function depends on the type of indoor unit 15 5 13 Setpoint range Set a limitation to the temperature setpoint range of both Cooling and Heating operation INFORMATIO...

Страница 32: ...n it is required that the indoor units are equipped with a self cleaning decoration panel optional accessory 15 5 20 AirNet address Assign AirNet addresses to the indoor and outdoor units this to conn...

Страница 33: ...units can remain inactive during normal operation After a set time i e Rotation cycle time the inactive unit will start operation and a previously active unit will become inactive i e duty rotation Be...

Страница 34: ...behave correspondingly 12 Return to the Test operation menu 13 Tap Stop test operation Result The indoor units leave test operation mode Normal operation is possible again 14 Go to 6 Operation on page...

Страница 35: ...Wipe the screen and other surface parts of the controller with a dry cloth 17 Troubleshooting 17 1 Error codes of the indoor unit When the indoor unit is in error the controller will display on the ho...

Страница 36: ...is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 18 1 Connection diagram 18 1 1 Typica...

Страница 37: ...ference guide 37 BRC1H519W K S Wired remote controller 4P513689 1A 2018 03 Group control controller digital inputs adapter BRP7A5 0 1 2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 18 1 3 Controller DIII central con...

Страница 38: ......

Страница 39: ......

Страница 40: ...4P513689 1A 2018 03 Copyright 2018 Daikin...

Отзывы: