3-4 Determine the direction of controller wiring outlet (back
outlet, left outlet, top left outlet, top center outlet).
3-4-1 Back outlet
3-4-2 Left outlet
Cut off resin area (hatched area).
Cut off thin area (hatched area) with nippers
or the like, and then remove burr with a file or
the like.
3-4-3 Top left outlet
3-4-4 Top center outlet
Cut off thin area (hatched area) with nippers
or the like, and then remove burr with a file or
the like.
Cut off thin area (hatched area) with nippers
or the like, and then remove burr with a file or
the like.
3-5 Conduct wiring.
1. Switch box and transmission wiring are not attached.
2. Do not directly touch the Printed Circuit Board.
CAUTION
Wiring Specifications
Wiring Type
Sheathed vinyl cord or cable (2 cores) (
*
1)
Wiring Size
0.75~1.25 mm
2
Wiring Length Max. 500m (
*
2)
*
1. Some countries may require a shielded wiring.
Refer to Installation manual attached to the indoor unit.
*
2. This will be the total extended length in the system when doing group control.