Daikin BRC1D71 Скачать руководство пользователя страница 7

 

 

 

BRC1D71
Remote controller
3P166742-2

Installation manual

 

5

 

Mode 

No.

Note 1

FIRST 
CODE 

NO.

Description of setting

SECOND CODE NO. Note 2

01

02

03

04

 

10(20)

0

 

Filter Contamination - Heavy/Light
(Setting for spacing time of display time 
to clean air filter)
(Setting for when filter contamination is 
heavy, and spacing time of display time to 
clean air filter is to be halved)

 

Ultra long 

life filter

Approx. 

10.000 

hrs.

Approx. 

5.000 

hrs.

Long life

 filter

Approx. 

2.500 

hrs.

Approx. 

1.250 

hrs.

Standard 

filter

Approx. 

200 hrs.

Approx. 

100 hrs.

1

 

Long-life filter type (setting of filter sign indication 
time). (Change setting when ultra-long filter is 
installed)

 

Long-life 

filter

Ultra-long life 

filter

2

 

Thermostat sensor in remote controller

 

Use

Not use

3

 

Spacing time of display time to clean air filter count 
(setting for when the filter sign is not to be displayed)

 

Display

Do not 

display

12(22)

1

 

ON/OFF input from outside (setting for when forced 
ON/OFF is to be operated from outside).

 

Forced OFF

ON/OFF 

operation

2

 

Thermostat differential changeover (setting for when 
using remote sensor).

 

2°F

1°F

13(23)

3

 

Selection of air flow function (setting for when using 
a decoration panel for outlet).

 

Equipped

Not 

equipped

4

 

Air flow direction range setting.

 

Upper

Normal

Lower

15(25)

3

 

Drain pump operation with humidifying.

 

Equipped

Not 

equipped

1b

0

 

Permission level setting

 

Level 2

Level 3

1

 

Away function

 

Not  permitted

 

Permitted

2

 

Thermostat sensor in remote controller (for limit 
operation and away function only)

 

Use

Not use

Light

Hea

vy

✦✷✤✩✩✪✧✥-✥_✲N.❇m ✷❂❈❆ 5 ✾❆❅n❆s❅❂❖, O❄❏o❃❆❍ 5, ✥✣✣5 ✩:✥✣ ✷M

Содержание BRC1D71

Страница 1: ...Remote controller BRC1D71 INSTALLATION MANUAL _ m s m 5 5 M...

Страница 2: ...1 1 1 4 4 1 2 2 1 2 3 3 S M S S M PCB 1 2 5 5 6 6 P2 P1 P2 P1 1 1 6 2 3 4 5 7 7 SETTING UNIT No GROUP c a 3 1 4 7 b 5 6 2 d e 8 8 1 2 2 2 2 _ L m n s O o 5 5 5 M...

Страница 3: ...ESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR THE USE WITH THE EQUIPMENT AND HAVE...

Страница 4: ...er 4 wired from the rear 5 wired from the top 6 notch the part for the wiring to pass through with nippers etc NOTE When wiring run the wiring away from the power supply wiring in order to avoid recei...

Страница 5: ...e mounted on the indoor unit the indoor unit setting may have to be changed Refer to the instruction manual for each optional accessory Refer to figure 7 Procedure Refer to figure 7 1 When in the norm...

Страница 6: ...e number inside the parentheses is selected indoor units can also be set individually 2 The SECOND CODE No is set to 01 when shipped from the factory 3 Do not make any settings not given in the table...

Страница 7: ...life filter 2 Thermostat sensor in remote controller Use Not use 3 Spacing time of display time to clean air filter count setting for when the filter sign is not to be displayed Display Do not display...

Страница 8: ...3P166742 2 EM05A054 0511 HT _ m n s O o 5 5 M...

Отзывы: