background image

I

nstallatIon

www .DaikinApplied .com 

IM 1038 • VAV ACTUATOR ROOM SENSOR

2 .  Drill two 3/16-inch (4 .8 mm) mounting holes and mount 

the two plastic wall anchors flush to below the wall 

surface for stable mounting of the device . 

3 .  Cut a 1-inch (25 mm) center hole with a hole saw . 
4 .  Pull about three inches (75 mm) of the cable through the 

hole in the base plate . 

5 .  Mount the room sensor base plate on the wall, noting the 

“UP” arrow: 

a .  Install the two mounting screws provided, but do 

not tighten . 

b .  Level the room sensor base plate for appearance . 

c .  Tighten the two mounting screws to the room 

sensor base plate . 

6 .  Do one of the following: 

a .  If the cable is terminated: Inspect the RJ-11 

connector for damage . 

b .  If the cable is non-terminated or if the RJ-11 was 

damaged: Cut the cable, leaving about three 

inches (75 mm) on the room sensor side of the 

drywall, and attach an RJ-11 connector with an RJ-

11 crimping tool . On the RJ-11 connectors, ensure 

that pin Number 1 connects to the same wire at 

each end of the cable . See Figure 3 . 

7 .  Plug the terminated cable into the RJ-11 connector on the 

back of the room sensor’s printed circuit board (PCB) . 

8 .  Feed the extra cable back through the hole . 
9 .  Snap the room sensor cover to the room sensor base 

plate by first hooking the room sensor front to the top 

latches, and then rotating the cover downward until it 

latches . 

10 .  Loosen the safety set screw at the bottom of the base 

one or two revolutions to lock the cover to the base . 

Be careful not to loosen too far as the screws can be 

completely removed from the base . 

11 .  Connect the room sensor to the Temperature Room 

Sensor port on the controller . 

This installation is now complete. 

Figure 3: Terminating the RJ-11 Connector  

 

Electrical Box and Rough-in Mounting, Typical 

 CAUTION

Over-tightening may cause the room sensor base plate to 

crack or bend . 

1 .  If a locator is attached to the rough-in device, remove the 

locator by removing the two screws and lightly rocking 

the locator to pull it free . 

2 .  Untie the twist tie and pull about three inches (75 mm) of 

the room sensor cable through the hole in the base plate . 

3 .  Mount the room sensor base plate on the wall, noting the 

“UP” arrow: 

a .  Install the two room sensor mounting screws 

provided, but do not tighten . 

b .  Level the room sensor base plate for appearance 

only . 

c .  Tighten the two mounting screws to the room 

sensor base plate . 

4 .  Continue with Drywall Mounting (No Rough-in), Typical, 

Steps 7 through 11 . 

This installation is now complete. 

Отзывы: