12 Technical data
Installer reference guide
26
AZQS100~14 AZQS100~140B7Y1B
Split system air conditioners
4P3855291 – 2014.08
Multiple rows of units
Layout
If
Then (mm)
≥1000
≥200
≥2000
≥100
≥3000
≥600
≥1500
b
≥100
≥100
≥100
≥100
≥100
≥100
H
B
H
U
H
B
≤½H
U
b≥250
½H
U
<H
B
≤H
U
b≥300
H
B
>H
U
NOT allowed
Stacked units (max. 2 levels)
If
Then
There is danger of drainage dripping and freezing between the upper
and lower units.
Install a roof between the upper and lower units.
Install the upper unit high enough above the lower unit to prevent ice
buildup at the upper unit's bottom plate.
A
≥500
≥1000
A
≥500
≥300
A
Roof
There is no danger of drainage dripping and freezing between the
upper and lower units.
It is not required to install a roof, but seal the gap between the upper
and lower units to prevent discharged air from flowing back to the
suction side through the bottom of the unit.
≥100
≥300
B
≥100
≥1000
B
B
Sealed gap