IOM 1242-2 • PATHFINDER
®
MODEL AWV CHILLERS
50 www.DaikinApplied.com
C
onTroller
o
peraTIon
Circuit Test Mode Set Points
Circuit test mode set points can be changed when either the unit mode is Test, or the circuit mode is Test. When neither the unit nor
the circuit are in Test mode, all the circuit test mode set points for the circuit are automatically changed back to their ‘off’ values.
Description
Default
Range
Test 100% VR Solenoid Output
Off
Off, On
Test 75% VR Solenoid Output
Off
Off, On
Test 50% VR Solenoid Output
Off
Off, On
Test Liquid Line Solenoid Output
Off
Off, On
Test Liquid Injection Solenoid Output
Off
Off, On
Test Evaporator EXV Position
0%
0 to 100%
Test Economizer EXV Position
0%
0 to 100%
Test Condenser Fan Output 1
Off
Off, On
Test Condenser Fan Output 2
Off
Off, On
Test Condenser Fan Output 3
Off
Off, On
Test Condenser Fan Output 4
Off
Off, On
Test Condenser Fan Output 5
Off
Off, On
Test Condenser Fan Output 6
Off
Off, On
Test Condenser Fan VFD Speed
0%
0 to 100%
NOTE:
Settings for outputs should be available based on the selected unit configuration settings.