C
onTroller
o
peraTIon
www.DaikinApplied.com 45
IOM 1242-2 • PATHFINDER
®
MODEL AWV CHILLERS
Economizer EXV Module
Table 24: Analog Inputs
#
Description
Signal Source
S1
Economizer Pressure Circuit #1
Ratiometric 0.5-4.5 Vdc
S2
Economizer Temperature Circuit #1 NTC 10K Thermister
S3
Economizer Pressure Circuit #2
Ratiometric 0.5-4.5 Vdc
S4
Economizer Temperature Circuit #2 NTC 10K Thermister
Table 25: EXV Stepper Outputs
Driver Description
A
Economizer EXV Circuit #1
B
Economizer EXV Circuit #2
Alarm/Limit Module
Table 26: Analog Inputs
#
Description
Signal Source
X3
Demand Limit
4-20 mA
Table 27: Digital Inputs
#
Description
Signal Off
Signal On
X1
External Alarm
External Device Failure External
Device OK
X5
Circuit #1 Switch Circuit Off
Circuit On
X6
Circuit #2 Switch Circuit Off
Circuit On
Table 28: Digital Outputs
#
Description
Output Off
Output On
DO1
Evaporator Water Pump 2
Pump Off
Pump On
DO3
Circuit #1 Fan Output #5
Fan(s) Off
Fan(s) On
DO4
Circuit #1 Fan Output #6
Fan(s) Off
Fan(s) On
DO5
Circuit #2 Fan Output #5
Fan(s) Off
Fan(s) On
DO6
Circuit #2 Fan Output #6
Fan(s) Off
Fan(s) On
RapidRestore
®
Module
Table 29: Digital Inputs
#
Description
Signal Off
Signal On
DI1
RapidRestore
Unlock
Lock Out Option
Unlock Option
DI2
Backup Chiller
Normal Chiller
Backup Chiller
Compressor VFDs
Table 30: Digital Inputs
#
Description
Signal Off
Signal On
H1
Circuit #
Mechanical High
Pressure Switch
Alarm
No Alarm
S6