background image

7

For air handler installation, follow the installation procedure 

below.

1.  Remove the front access panel.

2. 

Remove access valve fitting cap and depress the valve 

system to release pressure. No pressure indicates 

possible leak.

3. 

Replace the fitting cap.

4.  Remove the copper cap on both the liquid line and 

suction line. The copper caps caused by the refrigerant 

lines. DO NOT USE ANY FORM OF CUTTING 

METHOD. CUTTING THE CAPS MAY RESULT IN 

THE GENERATION OF COPPER SHAVINGS OR 

COPPER DUST.

5.  Insert liquid line into liquid tube expansion and  

 

slide grommet about 18” away from braze joint.

6.  Braze suction line set into suction tube expansion and 

slide insulation about 18” away from braze joint.

7.  Braze joints and quench all brazed joints with water or 

wet rag upon completion of brazing.

10.3 Thermal Expansion Valve System Adjustment 

The following information for the indoor unit should be 

verified before attempting to charge system or adjust TXV 

if 

necessary.

1.  Total static presssure is .3” WC or less.

2. 

Airflow is correct for installed unit. 

3. 

Airflow tables are in the installation manual and Spec 

Sheet for Indoor Unit. 

4. 

Complete airflow tables and charging information are in 

Service Manual RS6200006.

5.  The outdoor temperature must be 60°F or higher. 

6.  Set the room thermostat to COOL, fan switch to AUTO

7.  Set temperature control well below room temperature. 

Superheat adjustments should not be made until indoor 

ambient conditions have stabilized. This could take up 

to 24 hours depending on the indoor temperature and 

humidity. Before checking superheat run the unit in cooling 

for 10 minutes or until refrigerant pressures stabilize. 

Use the following guidelines and methods to check unit 

operation and ensure that the refrigerant charge is within 

limits.

1.  Purge gauge lines. Connect service gauge manifold to 

base-valve service ports. 

2.  Temporarily install a thermometer on the liquid 

line at the liquid line service valve and 4-6” from 

the compressor on the suction line. Ensure the 

thermometer makes adequate contact and is insulated 

for best possible readings. Use liquid line temperature 

to determine subcooling and vapor temperature to 

determine superheat. 

3.  Check subcooling and superheat. The system should 

have a subcooling of 8°F +/- 1°F and superheat of 8°F 

+/- 1°F. If subcooling and superheat are low, adjust 

TXV to 8°F +/- 1°F superheat, then check subcooling.

A. If subcooling is low and superheat is high, add 

charge to raise subcooling to 8°F +/- 1°F, then 

check superheat.

B. If subcooling and superheat are high, adjust 

TXV valve to 8°F +/- 1°F superheat, then check 

subcooling.

Superheat Adjustments (Only if necessary)

1.  Attach a pipe clamp thermometer near the suction line 

service valve at the outdoor unit.

A. Ensure the thermometer makes adequate contact 

for the best possible readings.

2.  TXV-based systems should have a Superheat value of 

8°F +/- 1°F. 

3.  Adjust Superheat by turning the TXV valve stem 

clockwise to 

increase

 and 

counterclockwise

 to 

decrease

. Adjustments should be made opening or 

closing the vlave by no more that 1/4 turn at a time. 

Allow the system to stabilize to 15 to 20 minutes before 

making additional adjustments if necessary. 

4.  After adjustments are complete, replace cap on 

adjustment stem and tighten 1/6 turn. 

5.  Remove gauges and check the Schrader ports for 

leaks and tighten valve cores if necessary. Install caps 

finger tight. 

WARNING

THIS PRODUCT IS FACTORY-SHIPPED WITH R410A/R22 AND 

DRY NITROGEN MIXTURE GAS UNDER PRESSURE. USE AP-

PROPRIATE SERVICE TOOLS AND FOLLOW THESE INSTRUC-

TIONS TO PREVENT INJURY. 

11 MAINTENANCE

Periodic Checkup and Service

This unit is designed to provide many years of dependable,

trouble-free comfort when properly maintained. Proper 

maintenance will consist of annual checkups and cleaning 

of the internal electrical and heat transfer components by 

a qualified service technician. Failure to provide periodic 

checkup and cleaning can result in excessive operating 

cost and/or equipment malfunction. 

Heater Kit Service

This comfort equipment comes pre-installed with a UL 2-40 

certified heater kit. In times of replacement, please ensure 

that only a UL 2-40 certified kit is utilized. 

Содержание AWSF18SU16 Series

Страница 1: ...R PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS...

Страница 2: ...SERIOUS PROPERTY DAMAGE OR PERSONAL INJURY REDUCED UNIT PERFORMANCE AND OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF DEVICES THAT HAVE NOT BEEN APPROVED OR CERTIFIED BY THE MANUFACTURER CONTENTS...

Страница 3: ...of carbon monoxide CO poisoning resulting from the exhaust emissions If a furnace or air handler is installed in an enclosed area such as a garage utility room or parking area and a carbon monoxide p...

Страница 4: ...g guidelines If possible allow adequate length of tubing such that the coil may be removed for inspection or cleaning services from the cabinet without disconnecting the tubing Note These air handlers...

Страница 5: ...ADIAN ELECTRIC CODE CSA C22 1 FAILURE TO OBSERVE THIS WARNING CAN RESULT IN ELECTRICAL SHOCK THAT CAN CAUSE PERSONAL INJURY OR DEATH WARNING 7 1 Building Electrical Service Inspection This unit is des...

Страница 6: ...ped with the unit When these requirements are satisfied the unit achieves the following airflow leakage when tested in accordance with ASHRAE Standard 193 Cabinet air leakage less than 2 at 1 0 inch H...

Страница 7: ...ction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line temperature to determine subcooling and vapor temperature to determine superheat 3...

Страница 8: ...24 VAC 18 Gauge 24 VAC Y R G W C Y Y Note Connect T2 T3 or T4 to the Y terminal to the outdoor unit See Table 5 for correct CFM selec on T1 T5 Figure 3 NOTE Connect appropriate speed tap Pink Purple Y...

Страница 9: ...3 Equalizer Must be connected to the 1 4 SAE connection on the suction line 4 Charge Ensure the system is properly charged There MUST be a minimum of 10 F Sub Cooled liquid at the valve inlet If the...

Страница 10: ...ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer...

Страница 11: ...ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer...

Страница 12: ...ING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WIRING DIAGRAM AWSF30LU16 AWST30LU14 Wiring is subject to change Always refer...

Страница 13: ...ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer...

Страница 14: ...he unit without first discussing your plans with your dealer or other qualified servicer Restricted airflow could lead to poor operation and or severe equipment damage Likewise it is important to keep...

Страница 15: ...WB F DB F WB F Heating Supply Air Temperature DB F Temperature Rise DB F Delta T Difference between Supply and Return Temperatures DB F AirHandler Coil InverterMatched INVERTERAH COILONLY Check EEV an...

Страница 16: ...page DAIKIN AMANA BRAND GOODMAN BRAND DAIKIN AMANA BRAND GOODMAN BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regist...

Отзывы: