1.2
Jumper Settings
1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two wireless remote controllers can be set
for different addresses.
How to set the different addresses
Control PCB of the indoor unit
(1) Remove the front grille. (3 screws)
(2) Remove the electrical box (1-screw).
(3) Remove the drip proof plate. (4 tabs)
(4) Cut the address jumper
JA
on the control PCB.
Wireless remote controller
(1) Slide the front cover and take it off.
(2) Cut the address jumper
J4
.
1.2.2
Jumper Setting
(R4417)
ADDRESS
JA
ADDRESS
JA
EXIST
1
CUT
2
ADDRESS
J4
EXIST
CUT
1
2
J4
(R4418)
Jumper
(On indoor control PCB)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto-restart
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB
Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
Fan speed setting
;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>
Содержание ATXS35EV1B7
Страница 1: ...SiBE04 824 Applied Models z Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series...
Страница 11: ...Introduction SiBE04 824 x...
Страница 12: ...SiBE04 824 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 14: ...SiBE04 824 Specifications 3 Part 2 Specifications 1 Specifications 4...
Страница 17: ...Specifications SiBE04 824 6 Specifications...
Страница 25: ...Printed Circuit Board Connector Wiring Diagram SiBE04 824 14 Printed Circuit Board Connector Wiring Diagram...
Страница 85: ...Instruction SiBE04 824 74 Operation Manual...
Страница 147: ...Check SiBE04 824 136 Service Diagnosis...
Страница 227: ...Outdoor Unit SiBE04 824 216 Removal Procedure...
Страница 237: ...Wiring Diagrams SiBE04 824 226 Appendix...