8 Disposal
Installation manual
12
(A)(F)TXP20~3 FTXF20~3 FTXF20~25B5V1B
Daikin room air conditioner
3P519299-1H – 2019.09
Prerequisite:
Test run should be performed in accordance with the
operation manual of the indoor unit to make sure that all functions
and parts are working properly.
1
In cooling mode, select the lowest programmable temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.
2
When the test run is finished, set the temperature to a normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3
The system stops operating 3 minutes after the unit is turned
OFF.
7.2.1
To perform a test run in winter season
When operating the air conditioner in
Cooling
mode in winter, set it
to test run operation using the following method.
For FTXP and ATXP units
1
Press
,
, and
simultaneously.
2
Press
.
3
Select
.
4
Press
.
5
Press
to switch the system on.
Result:
Test run operation will stop automatically after about
30 minutes.
6
To stop operation, press
.
For FTXF units
7
Press to switch the system on.
8
Press the centre of
,
, and
simultaneously.
9
Press
twice.
Result:
will appear on the display. Test run operation is
selected. Test run operation will stop automatically after about
30 minutes.
10
To stop operation, press .
INFORMATION
Some of the functions CANNOT be used in the test run
operation mode.
If a power failure occurs during operation, the system automatically
restarts immediately after power is restored.
8
Disposal
Dismantling of the unit and treatment of the refrigerant, oil and other
parts MUST comply with the applicable legislation.