Control Specification
SiBE041134EB
44
Functions and Control
3.6
Freeze-up Protection Control
During cooling operation, the signal sent from the indoor unit determines the frequency upper
limit and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is
divided into zones.)
The operating frequency limitation is judged with the indoor heat exchanger temperature.
3.7
Heating Peak-cut Control
During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
A
(°C)
B
(°C)
C
(°C)
11
9
7
(R22433)
Reset zone
Indoor heat exchanger
thermistor temperature
Up zone
Keep zone
Dropping zone
Stop zone
0˚C
C
˚C
B
˚C
A
˚C
13˚C
RXS20/25K2V1B
RXS20/25K3V1B
RXS20/25L2V1B
ARXS25L2V1B
RXS20/25L3V1B
ARXS25L3V1B
A
(ºC)
65
63
B
(ºC)
56
56
C
(ºC)
53
53
D
(ºC)
51
51
E
(ºC)
46
46
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
Indoor heat exchanger
thermistor temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R22434)
D
˚C
C
˚C
B
˚C
A
˚C
E
˚C