Troubleshooting
Service manual
51
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
171].
Possible cause:
Faulty main PCB.
2
Perform a check of the outdoor unit fan motor. See
217].
Possible cause:
Faulty outdoor unit fan motor.
3
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >4%),
▪
Power drop,
▪
Short circuit.
4
Clean the outdoor heat exchanger. See
309].
Possible cause:
Dirty outdoor heat exchanger.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.59 L4-00 – Outdoor unit: Malfunction of inverter radiating fin temperature rise
Trigger
Effect
Reset
Radiating fin thermistor
measures a too high
temperature.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the outdoor unit fan motor. See
217].
Possible cause:
Faulty outdoor unit fan motor.
2
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >4%),
▪
Power drop,
▪
Short circuit.
3
Perform a check of the main PCB. See
171].
Possible cause:
Faulty main PCB.
Prerequisite:
Stop the unit operation via the user interface.
4
Turn OFF the respective circuit breaker.