Connect the service monitoring tool to monitor the high pressure.
If the measured output voltage value matches the voltage determined through the
measured pressure, but the pressure via the service monitoring tool is NOT correct,
replace the applicable PCB.
The measured voltage is inside the
expected range?
Action
Yes
Refrigerant pressure sensor is OK.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Continue with the next step.
6
Unplug the refrigerant pressure sensor connector X17A and measure the
voltage (power supply) between pins 3–4 on main PCB.
Result:
The measured voltage MUST be +5 V DC.
Is the measured v5 V DC?
Then
Yes
Replace the refrigerant pressure sensor,
see
No
Perform a check of the main PCB, see
171].
3.19.2 Repair procedures
To remove the refrigerant pressure sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
230].
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
291].
Prerequisite:
If needed, remove any parts or insulation to create more space for
the removal.
1
Cut all tie straps that fix the refrigerant pressure sensor harness.
2
Disconnect the refrigerant pressure sensor connector from the PCB.
3
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
4
Wrap a wet rag around the components near the refrigerant pressure sensor.
Heat the brazing point of the refrigerant pressure sensor pipe using an oxygen
acetylene torch and remove the refrigerant pressure sensor pipe from the
refrigerant pipe using pliers.