Components
Service manual
244
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
5
Measure the inductance of the reactor using an LCR meter.
Result:
The inductance MUST be as follows:
Measuring points
Inductance
d‑e
104~116 µH
Is the inductance measurement
correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
Replace the reactor, see
3.18.2 Repair procedures
As the reactors are part of the main PCB, replace the complete main PCB. See
171].
3.19 Refrigerant pressure sensor
3.19.1 Checking procedures
To perform an electrical check of the refrigerant pressure sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
230].
1
Turn ON the power of the unit.
2
Connect a pressure gauge to the gas service port. Read the pressure.
3
Using the graphic below, determine the expected sensor output voltage based
on the pressure obtained in the previous step.
-0.5
-0.5
0
0.5
1
1.5
2
2.5
3
3.5
4
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
a
b