6 Electrical installation
Installation manual
20
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685229-1A – 2022.05
6.3.4
External backup heater kit
For models without integrated backup heater, you can install the
external backup heater kit (EKLBUHCB6W1).
If you do so, then under certain conditions you also need to install a
bypass valve kit (EKMBHBP1).
See:
▪
"To connect the backup heater kit"
▪
▪
"To connect the bypass valve kit"
To connect the backup heater kit
The installation of the external backup heater kit is described in the
installation manual of the kit. However, certain parts of it are
superseded by the information described here. It concerns the
following:
▪ To connect the backup heater kit power supply
▪ To connect the backup heater kit to the outdoor unit
Wires: See installation manual of the backup heater kit
[9.3]
Backup heater
To connect the backup heater kit power supply
CAUTION
To guarantee the unit is completely earthed, ALWAYS
connect the backup heater power supply and the earth
cable.
WARNING
The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.
Depending on the configuration (wiring on X14M, and settings in
[9.3]
Backup heater
), the backup heater capacity can vary. Make
sure that the power supply is in accordance with the backup heater
capacity, as listed in the table below.
Backup
heater type
Backup
heater
capacity
Power
supply
Maximum
running
current
Z
max
(Ω)
*6W
3 kW
1N~ 230 V
13 A
—
6 kW
1N~ 230 V
26 A
(a)(b)
—
6 kW
3N~ 400 V
8.6 A
—
9 kW
3N~ 400 V
13 A
—
(a)
This equipment complies with EN/IEC 61000‑3‑11 (European/
International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated current ≤75 A) provided
that the system impedance Z
sys
is less than or equal to Z
max
at the
interface point between the user's supply and the public system. It
is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
a system impedance Z
sys
less than or equal to Z
max
.
(b)
Electrical equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current >16 A and ≤75 A per
phase).
1
Connect the backup heater power supply. A 4‑pole fuse is used
for F1B.
2
If required, modify the connection on terminal X14M.
Capacity –
Power supply
F1B
X14M
3 kW 1N~ 230 V
6 kW 1N~ 230 V
L
L
N
N
F1B
1N~ , 50 Hz
230 V AC
F1B.2+4
F1B.6+8
L
N
Q3DI
1 2 3 4 5 6
X14M
6 kW 3N~ 400 V
9 kW 3N~ 400 V
F1B
L1 L2
N
L3
3N~ , 50 Hz
400 V AC
Q3DI
F1B.6
F1B.8
L3
F1B.4
L2
F1B.2
L1
N
1 2 3 4 5 6
X14M
3
Fix the cable with cable ties to the cable tie mountings.
During connection of the backup heater, miswiring is possible. To
detect possible miswiring, it is highly recommended to measure the
resistance value of the heater elements. Depending on the capacity
and power supply, following resistance values (see table below)
should be measured. ALWAYS measure the resistance on the
contactor clamps K1M, K2M, and K5M.
3 kW
1N~ 230 V
6 kW
1N~ 230 V
6 kW
3N~ 400 V
9 kW
3N~ 400 V
K1M/1
K5M/13
52.9Ω
52.9Ω
∞
∞
K1M/3
∞
105.8Ω
105.8Ω
105.8Ω
K1M/5
∞
158.7Ω
105.8Ω
105.8Ω
K1M/3
K1M/5
26.5Ω
52.9Ω
105.8Ω
105.8Ω
K2M/1
K5M/13
∞
26.5Ω
∞
∞
K2M/3
∞
∞
52.9Ω
52.9Ω
K2M/5
∞
∞
52.9Ω
52.9Ω
K2M/3
K2M/5
52.9Ω
52.9Ω
52.9Ω
52.9Ω
K1M/5
K2M/1
∞
132.3Ω
∞
∞
Example measure resistance between K1M/1 and K5M/13:
Содержание ALTHERMA
Страница 49: ......
Страница 50: ......
Страница 51: ......
Страница 52: ...4P685229 1A 2022 05 Copyright 2022 Daikin Verantwortung für Energie und Umwelt ...