Field Setting
ESIE09-08A
94
Test Operation
3.1.3
Detailed Explanation of Setting Modes
[0] Remote control setup
[0-00] User permission level
The remote controller can be programmed to make certain buttons and functions unavailable for the
user. There are 2 permission levels defined. Both levels (level 2 and level 3) are basically the same,
the only difference is that for level 3 no water temperature settings are possible (see table below).
By default no level is defined so all buttons and functions are operable (no level enabled). The actual
permission level is determined by field setting. For permission level 2, set field setting [0-00] is to 2,
for permission level 3, set field setting [0-00] to 3.
Once the field setting is set, the chosen permission level is not yet active. Enabling the selected
permission level is done by simultaneously pressing buttons
pi
and
pj
immediately
followed by simultaneously pressing buttons
s
and
ba
, and keeping all 4 buttons pressed for at
least 5 seconds. Note that no indication on the remote controller is given. After the procedure the
blocked buttons will not be available anymore.
Deactivating the selected permission level is done on the same way. Here the default level becomes
active again. All buttons and functions are operable.
[0-01] Room temperature compensation value
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This can be
used as countermeasure for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is then used for
controlling the system and will be displayed in the temperature read-out mode. See also
"[9] Automatic temperature compensation" setting for compensation values for leaving water
temperature and domestic hot water temperature.
[0-03] Status: defines whether the ON/OFF instruction can be used in the schedule timer for
space heating.
The schedule timer for space heating can be programmed on 2 different ways: based on the
temperature set point (both leaving water temperature and room temperature) and based on the ON/
OFF instruction.
Notes :
By default space heating based on temperature set point (method 1) is enabled, so only temperature shifts
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
0
Remote control setup
00
User permission level
2
2~3
1
—
01
Room temperature compensation value
0
–5~5
0.5
°C
03
Status: space heating schedule timer mode
1 (ON)
0/1
—
—
Permission
level 2
level 3
Operation ON/OFF
Operable
Operable
Domestic water heating operation ON/OFF
Operable
Operable
Setting the leaving water temperature
Operable
—
Setting the room temperature
Operable
Operable
Quiet mode ON/OFF
—
—
Weather dependent set point operation ON/OFF
Operable
—
Setting the clock
—
—
Programming the schedule timer
—
—
Schedule timer operation ON/OFF
Operable
Operable
Field settings
—
—
Error code display
Operable
Operable
Test operation
—
—
Содержание ALTHERMA HT ERSQ 011 AA
Страница 2: ......
Страница 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii...
Страница 13: ...ESIE09 08A General Information 1 Part 1 General Information 1 Model Names of Indoor Outdoor Units Tanks 2...
Страница 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information...
Страница 17: ...ESIE09 08A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Unit 8...
Страница 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1...
Страница 38: ...Functional Parts Layout ESIE09 08A 26 Refrigerant Circuit 2 6 EKHTSU 200 260 A AB AC Front view Tank sensor...
Страница 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit...
Страница 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51...
Страница 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit...
Страница 125: ...ESIE09 08A Field Setting Test Operation 113...
Страница 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting...
Страница 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1...
Страница 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1...
Страница 251: ...ESIE09 08A Wiring Diagrams Appendix 241...
Страница 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1...
Страница 257: ...ESIE09 08A Wiring Diagrams Appendix 247...
Страница 260: ...Wiring Diagrams ESIE09 08A 250 Appendix...
Страница 266: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08A 256 Appendix Inverter PC board C C W U V...
Страница 288: ...3 Way Valve ESIE09 08A 278 Appendix...