7/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.8.6
R/W
0: No
1: Yes
9.8.7
Enable Room buffering
R/W
0: No
1: Yes
9.8.8
R/W
0~20 kW, step: 0,5 kW
20 kW
└─
Power consumption control
9.9.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.9.2
[4-09]
R/W
0: Current
1: Power
9.9.3
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.9.4
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.9.5
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.9.6
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.9.7
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.9.8
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.9
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.A
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.B
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.C
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.D
[4-01]
0: None
1: BSH
2: BUH
9.9.F
[7-07]
R/W
0: Disabled
1: Enabled
└─
Energy metering
9.A.1
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.A.2
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
└─
Sensors
9.B.1
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.B.2
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.B.3
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─
Bivalent
9.C.1
[C-02]
R/W
0: No
1: Bivalent
9.C.2
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.C.3
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.C.4
[C-04]
R/W
2~10°C, step 1°C
3°C
Installer settings
9.D
[C-09]
R/W
0: Normally open
1: Normally closed
9.E
[3-00]
R/W
0: No
1: Yes
9.F
[E-08]
R/W
0: disabled
1: Enabled
9.G
R/W
0: No
1: Yes
└─
Overview field settings
9.I
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.I
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
65°C
9.I
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-03]
R/W
-40~5°C, step: 1°C
-15°C
9.I
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
9.I
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Hysteresis
Alarm output
Auto restart
Power saving function
Disable protections
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
External sensor
Ext. amb. sensor offset
Averaging time
Bivalent
Boiler efficiency
Temperature
Limit 3
Limit 4
Priority heater
BBR16 activation (#)
Electricity meter 1
Electricity meter 2 / PV meter
Limit 4
Limit
Limit 1
Limit 2
Limit 3
Limit 2
Power consumption control
Type
Limit
Limit 1
Allow electric heaters
Limit setting kW
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_(*7) *SU*
(#) Only applicable in Swedish language.
4P644734-1 - 2021.02